OM-2226 / Operation and Maintenance Manual
60CU20 / Series 500062 / 400 Hz. Generator Set
May 2, 2013
Chapter 2-3
Page 17
(3) Current Limiting / Soft Starting Control
a
Press the “
STARTNG CURRENT
” push button to activate the current limiting and set the limit
to 1500 A.
b
Press the “
DC OUTPUT
” push button to close the contactors to apply the load to the load
bank. Observe the ammeter, the current should stay below 1500 A.
c
Discontinue the power delivery.
(4) Over-Voltage Protection
a
Press “
DC OUTPUT
” push button to close the DC output contactor. The blue “
DC OUTPUT
”
lamp will glow indicating that DC power is being delivered to the load bank.
b
Adjust the voltage adjustment potentiometer on the TRB PC Board to range of 32-34 VDC.
c
With 7 to 9 seconds after the trip voltage is reached, the contactor will open and an over-
voltage fault will be indicated on the fault code meter, which will read “
70.28
”
d
Reset the voltage back to 28.5 VDC.
(5) Under-Voltage Protection
a
Press “
DC OUTPUT
” push button to close the DC output contactor. The blue “
DC OUTPUT
”
lamp will glow indicating that DC power is being delivered to the load bank.
b
Adjust the voltage adjustment potentiometer on the TRB PC Board to less than 20 VDC.
c
With 7 to 9 seconds after the trip voltage is reached, the contactor will open and an under-
voltage fault will be indicated on the fault code meter, which will read “
70.29
”
d
Reset the voltage back to 28.5 VDC.
(6) Overload Protection
a
Press the “
STARTNG CURRENT
” push button to activate the current limiting and set the limit
to 1500 A.
b
Press “
DC OUTPUT
” push button to close the DC output contactor. The blue “
DC OUTPUT
”
lamp will glow indicating that DC power is being delivered to the load bank.
c
The contactor should open in 30 seconds. The fault code meter will read “
70.30
”
d
Discontinue power delivery and let the cables cool for 2-3 minutes.
e
Press the “
STARTNG CURRENT
” push button to activate the current limiting and set the limit
to 2000 A.
f
Press “
DC OUTPUT
” push button to close the DC output contactor. The blue “
DC OUTPUT
”
lamp will glow indicating that DC power is being delivered to the load bank.
Summary of Contents for 500062-DLX
Page 2: ......
Page 4: ......
Page 6: ......
Page 209: ......
Page 210: ......
Page 211: ......
Page 212: ......
Page 213: ......
Page 214: ......
Page 215: ......
Page 216: ......
Page 217: ......
Page 218: ......
Page 219: ......
Page 220: ......
Page 221: ......
Page 222: ......
Page 223: ......
Page 224: ......
Page 225: ......
Page 226: ......
Page 227: ......
Page 228: ......
Page 229: ......
Page 230: ......
Page 231: ......
Page 232: ......
Page 233: ......
Page 234: ......
Page 235: ......
Page 236: ......
Page 237: ......
Page 238: ......
Page 239: ......
Page 240: ......
Page 241: ......
Page 242: ......