- 4 -
LED Diagnostics:
Red (DC) Green (AC)
Red (BAT)
Status
ON
ON
ON
Normal operating condition.
ON
OFF
ON
Loss of AC. Stand-by battery supplying power.
OFF
ON
OFF
No DC output. Battery Trouble
OFF
OFF
OFF
Loss of AC. Discharged or no stand-by battery. No DC output.
ON
ON
OFF
Battery missing / Low battery.
Terminal Identification:
Terminal Legend Function/Description
L, G, N
Connect 115VAC 60 Hz. to these terminals: L to hot, N to Neutral. Do not use the [G] terminal..
+ DC ---
12VDC or 24VDC @ 2.5 amp continuous power-limited output.
AC Fail
NC, C, NO
Indicates loss of AC power, e.g. connect to audible device or alarm panel. Relay normally
energized when AC power is present. Contact rating 1 amp @ 28VDC. AC or brownout fail is
reported within 1 minute of event. To delay reporting of up to 6 hrs., cut “AC delay” jumper and
reset power to unit.
Bat Fail
NC, C, NO
Indicates low battery condition, e.g. connect to alarm panel. Relay normally energized when DC
power is present. Contact rating 1 amp @ 28VDC.
+ BAT ---
Stand-by battery connections. Maximum charge current 0.7 amp.
Enclosure Dimensions
(H x W x D)
:
13.5” x 13” x 3.25” (342.9mm x 330.2mm x 82.55mm)
Hochiki America Corp.
7051 Village Drive, Suite 100, Buena Park, CA 90621-2268, 714-522-2246, Fax: 714-690-7890, www.hochiki.com
IIFN-300ULX
G02N
1.40”
(36mm)
1.40”
(36mm)
4.85”
(123mm)
4.85”
(123mm)
1.40”
(36mm)
1.40”
(36mm)
5.10”
(130mm)
5.10”
(130mm)
13.0”
(330mm)
5.10”
(130mm)
6.5625”
(167mm)
1.20”
(31mm)
1.20”
(31mm)
1.20”
(31mm)
3.25”
(83mm)
3.25”
(83mm)
3.25”
(83mm)
3.25”
(83mm)
1.0”
(25mm)
1.0”
(25mm)
10.5”
(267mm)
1.0”
(25mm)
1.0”
(25mm)
0.75”
(19mm)
0.75”
(19mm)
0.9375”
(24mm)
0.9375”
(24mm)
11.0”
(279mm)
12.5”
(318mm)