These
instructions
are
to
be
framed
and
placed
next
to
the
FireNET
2127/4127
control
panel
and
FN
‐
LCD
‐
N/FN
‐
LCD
‐
S
annunciators.
SOM
‐
R
FOR
RELEASING
FUNCTION:
ALARM
(ACTIVE
STATUS)
CONDITION:
During
an
Alarm
condition
the
Alarm
LEDs
will
pulse
on
and
off
on
the
panel
face,
the
local
buzzer
will
sound,
and
the
solenoid/bells/horns/strobes
will
be
activated.
The
location
text
of
the
alarm
point
as
programmed
into
the
fire
alarm
control
panel
will
be
displayed
on
the
LCD
display.
Additional
fire
events
can
be
viewed
by
pressing
the
“
More
Fire
Events”
button
and
using
the
Up/Down
Arrows
to
scroll
through
the
list.
To
silence
the
bells/horns,
enter
Access
Level
2
by
opening
the
front
door
of
the
enclosure,
then
press
the
“Alarm
Silence”
button.
The
Fire
LEDs
will
be
lit
continuously,
and
the
bells/horns
will
turn
off.
To
turn
the
bells/horns
back
on
again
press
the
“Resound
Alarm”
button.
The
“Reset”
button
will
turn
off
the
solenoid/bells/horns/strobes
and
return
the
fire
control
panel
to
a
normal
standby
condition.
DISABLE
CONDITION:
Turning
the
SOM
‐
R
‐
DS
(Keyswitch)
to
disable
position
will
cause
a
Supervisory
condition
and
the
Supervisory
LED
will
pulse
on
and
off
on
the
panel
face,
the
local
buzzer
will
sound.
The
location
text:
“
SOMR
IS
DISABLED”
will
be
displayed
on
the
fire
alarm
control
panel
LCD
display.
To
silence
the
local
buzzer,
enter
Access
Level
2
by
opening
the
front
door
of
the
enclosure,
then
press
the
“Panel
Sounder
Silence”
button.
The
Supervisory
LED
will
be
lit
continuously,
and
the
local
buzzer
will
turn
off.
Turning
keyswitch
back
to
enable
condition
will
return
the
fire
alarm
control
panel
to
a
normal
standby
condition.
Issued
5/24/09
P/N
1700
‐
09947
HA
‐
06
‐
143
Version
1.7