PRODUCT PARTS

 

 TSE-A100 Self-Contained Smoke Generator

 •  

Punk Stick (Part No. TSE-P100)

APPLICATION

The Hochiki America TSE-A100 is one of the most
advanced units of its kind and is the result of extensive
research and development aimed at making the job of
testing detectors a simple and efficient operation .

The TSE-A100 can be used to test all types of smoke
detectors by applying smoke from an internal smoke
source.

Although this is not a calibrated amount of smoke, the
TSE-A100 is an excellent choice for periodic functional
testing of smoke detectors.

OPERATION

Testing a Detector
Once you have prepared the TSE-A100, follow the steps
in this section to test smoke detectors.

NOTE:  Allow 30 to 60 seconds after igniting punk stick
for sufficient smoke generation.

TSE-A100 SELF-CONTAINED SMOKE GENERATOR

Specifications subject to change without notice.

SPECIFICATIONS

Rated Voltage

3 VDC

Battery

2 - "D" Batteries

Combustion Material

Punk  Stick

(

7 mm diameter, 150 mm long)

Weight

5 Lbs.

Length

5.25 to 14.1 feet

Color

Brown

Tests all types of smoke detectors.

Completely self contained and portable.

Extends from 5.25 feet to 14.1 feet.

Internal Smoke Source.

Non-Toxic Smoke Source.

Unit includes shoulder sling carrying case.

Optional adapter for high velocity conditions.

Exhaust function to clear detector.

Built-in filter to prevent tar residue from adhering to
the surface of the detector.

                      

 

Continued on back

Preparation

1.

Remove the TSE-A100 from its carrying case.

2.

Unscrew the combustion chamber from the
bottom of  the TSE-A100.

3.

Unscrew the punk stick holder retainer from
the combustion chamber.

4.

Insert a punk stick into the punk stick holder in
the combustion chamber.

5.

Light the punk stick with a flame.

6.

Reassemble the combustion chamber.

7.

Screw the combustion chamber back into the
bottom of  the TSE-A100

8.

Extend the telescopic pole of  the TSE-A100 to
a length which enables you to reach the
detector you wish to test.

STANDARD FEATURES

Summary of Contents for TCH-B100

Page 1: ...uring that sensor protrusions align with programmer grooves 2 Press the left gray button to switch programmer on A battery check message will appear followed by the device s address Unprogrammed sensors will read address 127 3 Set the required address by incrementing the left and right gray buttons the display will show three red flashing dots if the address being programmed is different from the ...

Page 2: ...sensor to factory for servicing DISPLAY MESSAGES bAt On upon power up battery check Also on when battery is low Low battery good for up to 3 000 address setting operation E0 Attempting to set an address beyond 127 E1 Attempting to program an address with no device connected E2 Can not find device after power up E3 Invalid sensor response E4 Can not find the device program E5 Device read error E6 F...

Page 3: ...F CONTAINED SMOKE GENERATOR Specifications subject to change without notice SPECIFICATIONS Rated Voltage 3 VDC Battery 2 D Batteries Combustion Material Punk Stick 7 mm diameter 150 mm long Weight 5 Lbs Length 5 25 to 14 1 feet Color Brown Tests all types of smoke detectors Completely self contained and portable Extends from 5 25 feet to 14 1 feet Internal Smoke Source Non Toxic Smoke Source Unit ...

Page 4: ...amber to the 1 position to turn the power off 2 Compress the telescopic pole to its shortest length 3 Replace the TSE A100 in its carry case 4 Store in a cool dry place 5 For extended storage remove the batteries Testing a Detector continued 1 Rotate the combustion chamber so the 2 arrow line sup with the power indicator screw The fan powers on and a steady flow of smoke is released from the tip o...

Page 5: ...tectors Choose either a Hand held or 15 stainless steel extension pole with easy grip black handle NSTT Tests HochikiAmerica SIJ 24 and SLR 24 835 series smoke detector with a reed switch Choose either a Hand held or 15 stainless steel extension pole with easy grip black handle No combustion material needed No meter batteries or screwdriver required Meets outlined requirements in the NFPA72 Inspec...

Page 6: ...igned to remove the outer covers of the ALG AIE and SLR series sensors detectors NSTT A100 The SIJ 24 and SLR 24 835 series detectors manufactured with magnetically activated dual reed switches for sensitivity testing can be sensitivity tested with the NSTT A100 This meets the requirements of a UL listed calibrated test without the use of combustion materials The NSTT A100 is in compliance with th...

Page 7: ... Type FireNET Family Programming Cable Length 10 feet 3 meters Left Connector 10 Pin Serial Female Right Connector 9 Pin DB9 Female X187 Non Jacketed Version S187 Jacketed Version X187 and S187 are used to program the FireNET family of panels FN P187 Printer Interface cable is used to connect a serial printer to the FireNET family of panels FN V187 VoiceNET Serial Interface Cable is used to interc...

Page 8: ... Length 10 feet 3 meters Left Connector 10 Pin Serial Female Right Connector 25 Pin Serial male SPECIFICATIONS FN V187 CableType VoiceNET Integration Cable Cable Length 10 feet 3 meters Left Connector 10 Pin Serial Female Right Connector 2 Wire Pin male WIRING DIAGRAMS FNV MP INTERFACE REFER TO FIRENET MANUAL V 1 86 OR HIGHER PROGRAMMING INTERFACE PRINTERINTERFACE ...

Reviews: