Configuration 21
HRT1 HP-313
Display
Option
Menu item Description
SAPLE
1
1
to
80
Max Sample Time
Set maximum time in tenths of a
second to sample the input
frequency. This setting determines
the amount of time the HRT1 will
wait for the next input pulse before
returning to 0. For example, 80 = 8
seconds. Default is 1. Changing
this setting is only recommended for
low flow applications below 1 Hz.
1.000
outLo
Out Low
Sets flow rate value for 4 mA
output.
99.999
outHi
Out High
Sets flow rate value for 20 mA
output.
PuLSE S
oFF
oFF
1
10
100
Pulse Scale
Sets scale for pulse out. 1, 10, 100
units of total for one pulse out.
Pulses are scaled according to the
least significant digit of the
displayed total. For example, if
Total Decimal places is set to
0000000.0, and Pulse Scale is 1,
then 1 pulse is output for each tenth
(0.1) of a unit. Changing the Pulse
Scale to 10 would output one (1)
pulse for every 1.0 unit of volume.
OFF- turns pulse out off.
PuLSE F
8
1
2
4
8
Pulse Frequency
Sets frequency of burst of pulse out.
(1, 2, 4, 8)
PASS
1234
0000
to
9999
Password
Sets 4-digit password. Default
0000.
unit LoC
no
Yes
No
Lock Unit
Locks the unit. Password entry is
required to unlock the unit or make
any configuration changes after the
unit is locked.
Summary of Contents for HRT1
Page 2: ......
Page 3: ......
Page 4: ......
Page 14: ...Introduction 6 HP 313 HRT1 This Page Intentionally Left Blank...
Page 34: ...Operation and Maintenance 26 HP 313 HRT1 This Page Intentionally Left Blank...
Page 48: ...HART Communications 40 HP 313 HRT1 This Page Intentionally Left Blank...
Page 53: ...Appendix B Declaration of Conformity 45 HRT1 HP 313 APPENDIX B Declaration of Conformity...
Page 54: ...Appendix B Declaration of Conformity 46 HP 313 HRT1...