background image

Hoffman

|

Controls

2463 Merrell Road, Dallas, Texas 75229  •  Phone:  (972) 243-7425  •  Fax: (972) 247-8674  •  Toll Free:  1-888-HCC-1190

www.hoffmancontrols.com 

 

Form:  173-0229-001 Rev B

Temperature to Resistance Table - Key Point Values

Table 1

Temp

ºF

Sensor

(Ohms)

Temp

ºF

Sensor

(Ohms)

Temp

ºF

Sensor

(Ohms)

  40.0 

26,109 

64.0 

13,823 

88.0 

7,685

  42.0 

24,712 

66.0 

13,139 

90.0 

7,332

  44.0 

23,398 

68.0 

12,492 

92.0 

6,997

  46.0 

22,160 

70.0 

11,881 

94.0 

6,679

  48.0 

20,996 

72.0 

11,3033 

96.0 

6,378

  50.0 

19,899 

74.0 

10,8509 

98.0 

6,092

  52.0 

18,872 

76.0 

10,2095 

100.0 

5,820

  54.0 

17,903 

78.0 

9,750  

102.0 

5,561

  56.0 

16,990 

80.0 

9,287  

104.0 

5,316 

  58.0 

16,128 

82.0 

8,848  

106.0 

5,094

  60.0 

15,315 

84.0 

8,433  

108.0 

4,873

  62.0 

14,547 

86.0 

8,056  

110.0 

4,662

  40.0 

26,109 

64.0 

13,823 

88.0 

7,685

  42.0 

24,712 

66.0 

13,139 

90.0 

7,332

  44.0 

23,398 

68.0 

12,492 

92.0 

6,997

  46.0 

22,160 

70.0 

11,881 

94.0 

6,679

  48.0 

20,996 

72.0 

11,3033 

96.0 

6,378

  50.0 

19,899 

74.0 

10,8509 

98.0 

6,092

  52.0 

18,872 

76.0 

10,2095 

100.0 

5,820

  54.0 

17,903 

78.0 

9,750  

102.0 

5,561

  56.0 

16,990 

80.0 

9,287  

104.0 

5,316 

  58.0 

16,128 

82.0 

8,848  

106.0 

5,094

  60.0 

15,315 

84.0 

8,433  

108.0 

4,873

  62.0 

14,547 

86.0 

8,056  

110.0 

4,662

  40.0 

26,109 

64.0 

13,823 

88.0 

7,685

  42.0 

24,712 

66.0 

13,139 

90.0 

7,332

  44.0 

23,398 

68.0 

12,492 

92.0 

6,997

  46.0 

22,160 

70.0 

11,881 

94.0 

6,679

  48.0 

20,996 

72.0 

11,3033 

96.0 

6,378

  50.0 

19,899 

74.0 

10,8509 

98.0 

6,092

  52.0 

18,872 

76.0 

10,2095 

100.0 

5,820

  54.0 

17,903 

78.0 

9,750  

102.0 

5,561

  56.0 

16,990 

80.0 

9,287  

104.0 

5,316 

  58.0 

16,128 

82.0 

8,848  

106.0 

5,094

  60.0 

15,315 

84.0 

8,433  

108.0 

4,873

  62.0 

14,547 

86.0 

8,056  

110.0 

4,662

c.

Above Selected Span and Range,

The motor(s) will start

and remain at full speed when temperatures are above the 

high end of the range adjust

.

d.

Simple Test:

  If Sensor 1 is not connected, motor runs at full speed.

Important:

  Always use Sensor 1 input.

Step 3

Making unit ready for normal operation.

1.

  Disconnect power to the unit & reconnect the  disabled com-

pressor.

2.

  Reconnect power to the unit & observe operation.

3.

  Verify operation as described above by monitoring  liquid line 

temperature and observing motor speed.

Troubleshooting Guide

1.

  Check wiring, review instructions.

2.

  Additional 24 VAC transformer needed. 

See "

GENERAL

" section instructions

3.

  Normal operation.

4.

  Motor protected.

5.

  Check Heat Pump Mode Jumpers “DA” 

and “RA”.

1.

  Check wiring, review instructions.

2.

  Replace control.

3.

  Charge system.

4.

  Replace Sensor.

5.

  Normal operation.

6.

  Switch DA/RA jumper position.

1.

  Raise Min. RPM speed.

2.

  Replace motor.

1.

  Additional 24 VAC transformer needed. 

See "

GENERAL

" section instructions

2.

  Relocate per instructions.

3.

  Compare FLA rating to measured FLA.

4.

  Replace Sensor.

5.

  Replace Motor.

6.

  Recharge system. Add or remove refrig-

erant. (Liquid line must not indicate 

vapor/gas.)

7.

  Adjust or replace expansion valve, cap 

tube or orifice to provide proper control 

of  lowside.

8.

  Reset Range Adjust up (CW) to provide 

evaporator temperature above 32°F.

Motor Will 

Not Run

Motor Runs

 at Full Speed 

Only

Motor 

Overheats

1.

  Improper installation. Motor not wired correctly.

2.

  24 VAC not in phase with motor line voltage.

3.

  Sensor below 50°F up to 70°F.

4.

  Motor “OFF” on internal overload.

5.

  Heat Pump applications; control not providing full speed during 

defrost cycle.

1.

  Motor not wired correctly.

2.

  Motor not wired correctly. Control damaged.

3.

  Low refrigerant. (Hot gas in liquid line.)

4.

  Sensor opened. (Verify Ohms vs. Temp.)

5.

  Sensor above 80°F up to 100°F.

6.

  Heat Pump Mode improperly programmed.

1.

  Minimum speed set too low.

2.

  Motor design not applicable for variable speed  operation.

1.

  24 VAC not in phase with motor line voltage.

2.

  Sensor not properly located or attached to liquid line.

3.

  Fan blade does not load motor at full RPM (speed).

4.

  Sensor Ohms vs. Temperature measured not in  compliance with 

values in Table 1.

5.

  Motor design not applicable for variable speed operation.

6.

  System not properly charged.

7.

  Expansion valve is not properly metering refrigerant; cap tube or

orifice not properly sized for low ambient operation.

8.

  Low evaporation and head pressure.

Motor Will

 Not Modulate 

Properly

 Condition

Cause

Solution

 Condition

Checkout Procedure Con't

Summary of Contents for 816-10DH

Page 1: ... by the Installer Service Technician General CAUTION Failure to read and understand the accompa nying instructions and diagrams or failure to complete the Checkout Procedure prior to energizing the Control may result in permanent damage to the Control The 816 10DH Controller requires the installation of an addi tional line voltage to 24VAC transformer VAC transformer V 10VA minimum This additional...

Page 2: ...ure the Sensor to the liquid line Stretch the tape slightly as you wrap the tape around the sensor and liquid line Use all the tape lapping the Sensor Firm mechanically clean contact is required between the metal tab of the Sensor and the liquid line When using one sensor always use the control s S1 and COM terminals DO NOT use tie wraps or hose clamps to secure sensor to liquid line Sensor elemen...

Page 3: ...MOTOR GND 4 IF REQ LINE Microprocessor Controller S2 S1 COM Wiring Diagram for the 816 10DH Figure 4 3 50 55º 80 70 75º 100 Range Adjust Min Speed LOAD LINE 24VAC Faster Sleeve Slower Ball HPGND Span H P Model 816 10DH Featuring Range Span Adjust 30º 25º DA RA HP24V www hoffmancontrols com C 10 Amps 115 208 230 460 600 VAC 50 60 Hz Hoffman Controls 1 2 3 4 MOTOR GND 4 IF REQ LINE Microprocessor Co...

Page 4: ...ower to the unit observe operation 3 Verify operation as described above by monitoring liquid line temperature and observing motor speed Troubleshooting Guide 1 Check wiring review instructions 2 Additional 24 VAC transformer needed See GENERAL section instructions 3 Normal operation 4 Motor protected 5 Check Heat Pump Mode Jumpers DA and RA 1 Check wiring review instructions 2 Replace control 3 C...

Reviews: