background image

7) Fault Stimulation

 

 

Remain in the Automatic mode. Using a short wire with both ends strip of insulation, connect one 
end to negative terminal T01. Touch the other end to Low Fuel Level alarm input T16. If the 

LFL 

parameter is set to ‘0’, then the display remain at 

Aut

 but alarm bell sounds and Low Fuel Level 

fault lamp flashes. If the  

LFL

  parameter is set to ‘1’, then the display flashes  

LFL

,   alarm bell 

sounds and Low Fuel Level fault lamp flashes. Press and release the 

MFB

 button once to accept 

the alarm. Bell is silenced and Low Fuel Level fault lamp remain lighted.
Next, touch the Over Speed alarm input T15. Notice how the display shows 

LFL

 but flashes the 

OSP

, the same with the fault lamps. Alarm bell sounds again. The DAMF-5 can differentiate a new 

fault once the old fault was accepted. Press and release the 

MFB

 button once to accept the alarm.

Now, touch the High Water Temperature alarm input T14 follow by External Fault Alarm alarm 
input T12. Notice again how the display shows 

LFL

 follow by 

OSP

 but flashes 

HWT

 and 

EFA

the same with the fault lamps. 

HWT

 and 

EFA

 are treated as new faults. 

Note; 

EFA

 does not have fault indicating lamp. Its fault lamp or lamps is located at the external 

alarm   annunciator   unit   which   is   added   when   the   local   fault   indication   in   the   DAMF-5   is 
insufficient. Press and release the  

MFB

  button twice to accept and reset the alarm. The display 

reverts back to 

Aut

.

To stimulate Fail To Start, you have to prepare a jumper wire from  

SFC

 input T04 to negative. 

This jumper connection can be done at the Termination Connectors side. If this test is done at site 
where the gen-set is connected and ready to start, remember to switch off the Starter Control 

MCB

Assuming that all parameter are set at default, to begin Fail To Start test, connect the jumper wire 
to negative. The display shows the 

SFt

 count down follow by the 

Crt

 count down and 

rSt

 count 

down. The 

Crt

 count down and 

rSt

 count down is repeated 6 times before  Fail To Start alarm is 

triggered. Notice the followings before the alarm is triggered, the Fuel Solenoid LED is lighted, 

FSR

 relay is energized, when 

Crt

 count down begins, the Starter LED is lighted and 

STR

 relay 

energizes, when 

rSt

 count down begins, the Starter LED is off and 

STR

 relay de-energizes. Once 

the alarm is triggered, the display flashes  

FtS

, alarm bell sounds and Fail To Start fault lamp 

flashes. Press and release the 

MFB

 button twice to accept and reset the alarm The display reverts 

back to 

Aut

.  At this stage the 

LOP

 fault cannot be tested because the gen-set did not start. LOP 

fault test is only done after Automatic Run. Do not remove the 

SFC

 input T04 jumper wire.

8) Automatic Run

 

 

Remain in the Automatic mode. To stimulate Generator Run, you have to prepare another jumper 
wire from 

GRR

 input T05 to negative. To begin, connect the 

SFC

 input T04 jumper to negative. 

The display shows the 

SFt

 count down follow by the 

Crt

 count down. During the 

Crt

 count down, 

connect the  

GRR

  input T05 to negative. The display shows the  

OPt

 count down follow by 

run 

with the moving 

_. _. _. 

 Note, the Fuel Solenoid LED is lighted. At this stage the 

LOP

 fault can be 

tested. Use the negative T01 wire and touch the 

LOP

 alarm input T13. The display shows the 

ESt 

count down, Fuel Solenoid LED off, Energize Stop LED lighted and 

LOP

 fault lamp flashes. After 

count down, the Energize Stop LED is off and the display flashes 

LOP

. Disconnect the 

SFC

 input 

T04 and 

GRR

 input T05 jumper wires from negative. Press and release the 

MFB

 button twice to 

accept and reset the alarm. During the 

 

 

ESt

    count down, the alarm cannot be accept or reset.

 

 

9) Automatic Shutdown

 

 

Remain in the Automatic mode. Repeat the Automatic Run until the display shows 

run

. To begin, 

disconnect the 

SFC

 input T04 jumper from negative. The display shows the 

Sdt

 count down follow 

by the  

ESt

  count down. Notice, when  

ESt

  count down starts, Fuel Solenoid LED off, Energize 

Page 9 of 12

HOKKIM

giving you control

Control & Protection Relays

Summary of Contents for DAMF-5

Page 1: ...is doing Next is the 3 digit 7 segment display This display is the most important interface as you will receive a host of information from it To help you understand we have provided the 3 digit abbreviations at the front face for easy reference You need to familiarize yourself with the abbreviations as during operation the display flashes at half second rate you have to be quick to catch what func...

Page 2: ...e open to feed diesel to the engine 4 ENERGIZE STOP To stop the gen set the ESR relay energize this LED lights and fuel is cut from the engine Note gen sets use either Fuel Solenoid or Energize Stop 5 24V When auxiliary supply is 20VDC and above this LED lights Maximum allowable voltage is 32VDC 6 12V When auxiliary supply is 15VDC and below this LED lights Minimum allowable voltage is 7VDC IMPORT...

Page 3: ...d Alarm bell sound and Low Fuel Level fault lamp flashes Alarm can be accepted 9 LOP Low Oil Pressure This display shows low oil pressure alarm has occur and gen set stopped and cannot be started After ESt count down press the MFB once to accept the alarm After clearing the fault press the MFB again to reset the alarm 10 LPt Lamp Test This display shows lamp test is being perform All alarm fault l...

Page 4: ...he next parameter 10 seconds of inactivity and the new value will be burn into the memory The display is shown when this is taking place In case auxiliary supply failure occurs in this stage the memory burning may not be complete and you may have to repeat the process 19 SFC Supply Fail Contact If the supply fail contact setting is 1 then the supply fail timer start when supply fail contacts close...

Page 5: ... mains supply fail the contacts close or open to start the gen set T05 GRR Generator Run Relay input from free contacts to negative When gen set has started its output voltage energizes this relay to close the contacts and stop the starter cranking Other wise also known as AFR AC Fail Relay T06 MFB Multi Function Button input from free contacts to negative This button is indeed used for many funct...

Page 6: ...Low Oil Pressure alarm output to lamp Type open collector to negative Flashes when Low Oil Pressure fault occurs T22 HWT High Water Temperature alarm output to lamp Type open collector to negative Flashes when High Water Temperature fault occurs T23 OSP Over Speed alarm output to lamp Type open collector to negative Flashes when Over Speed fault occurs T24 LFL Low Fuel Level alarm output to lamp T...

Page 7: ...minal Abbreviations Default Settings Diagram 3 Diagram 4 Note Lamp Test can only be performed in the Aut Mode Terminal Connection Diagram 5 Page 7 of 12 HOKKIM giving you control Control Protection Relays ...

Page 8: ...ff and the Energize Stop LED lighted If in use check that the Energize Stop relay energizes Wait for about 45 seconds until the LED goes off and the relay de energizes All other relays or lamps should be off but the supply LED remain lighted This confirms the Emergency Stop is functioning Reset the button to continue 4 View Default Settings Remain in the Off mode press and release the MFB button t...

Page 9: ... and rSt count down The Crt count down and rSt count down is repeated 6 times before Fail To Start alarm is triggered Notice the followings before the alarm is triggered the Fuel Solenoid LED is lighted FSR relay is energized when Crt count down begins the Starter LED is lighted and STR relay energizes when rSt count down begins the Starter LED is off and STR relay de energizes Once the alarm is t...

Page 10: ...rt alarm will be triggered After the GRR input T05 touches negative the display shows OPt count down and when finished displays run to indicate gen set is running Remember to note the usual when Crt count down begins the Fuel Solenoid Relay and Starter Relay energizes when rSt count down begins Fuel Solenoid Relay remain energized while Starter Relay de energizes 13 Test Stop The test stop is the ...

Page 11: ...r outputs are not shorted to positive of auxiliary supply 6 Make sure the alarm inputs resistance to negative is less then 500 ohms Higher resistance and the faults may not be triggered 7 Should alarm inputs give problem disconnect the wire from the DAMF 5 and test directly with jumper wire to negative 8 Do not connect power source to the inputs voltage higher then 12VAC will cause the internal fu...

Page 12: ...Contact selectable close 1 or open 0 to start Standard 5 nos fault alarms Expandable fault alarms using external annunciator to External Fault Alarm input First Fault Alarm new faults differentiated from old Alarm cancel does not cancel siren from next fault Master Alarm Relay output MAR for Building Automation system BAS etc New Hokkim JKM terminals for easier connections Easy wiring reduces labo...

Reviews: