Document No: C-61-00003-3
▶
10seconds
When using muting function in dual protection mode, Muting 3 and Muting 4 are configured in the similar
way.
3.9.2 Muting stop condition
Muting function will stop when any one of the condition below is fulfilled:
a)
One of the muting inputs switches to OFF-state.
b)
When the predefined (preset) maximum muting time T2 exceeds (1 minute and above) (Figure 3-20).
c)
Objects are detected in the protection zone which is not covered by the muting zone.
d)
Error is detected by the self-diagnostics function.
e)
During muting state
when the area is switched to other area.
Figure 3-20 shows the muting sequence.
Maximum muting period (T2)
Maximum muting period can be selected from one of these values
▶
1 minute
▶
6 minutes
▶
12 minutes
▶
Unlimited
When using the muting function in dual protection mode, Muting 3 and Muting 4 are configured in the
similar way. Same applies for muting input sequence, time interval between inputs and maximum muting
period.
Figure 3-20 Muting sequence
Summary of Contents for UAM-05LP
Page 1: ... Document No C 61 00003 3 ...
Page 104: ... Document No C 61 00003 3 Figure 7 33 b Function Figure7 33 c Area ...
Page 107: ... Document No C 61 00003 3 Figure 7 36 a Project report tab Figure 7 36 b Error report tab ...
Page 148: ... Document No C 61 00003 3 13 External dimension 13 1 UAM 05LP ...
Page 149: ... Document No C 61 00003 3 13 2 Base mounting bracket ...
Page 150: ... Document No C 61 00003 3 13 3 Rear mounting bracket ...
Page 151: ... Document No C 61 00003 3 13 4 Cover Protection Bracket ...
Page 152: ... Document No C 61 00003 3 14 EC Declaration of conformity ...
Page 153: ... Document No C 61 00003 3 ...