C01.29 Automatic Motor Tuning (AMT) Default setting
0
Range
[0] Off
AMT function is disabled.
[2] Enable AMT
AMT function starts running. This
may take up to 10 min. depending
on motor power rating.
●
Function
:
Use AMT to optimize motor performance.
● Stop VLT – make sure motor is at standstill
● Choose [2] Enable AMT
● Apply start signal
■ Via LCP: Press Hand On
■ Or in Remote On mode: Apply start signal on Terminal
RUN
●
ATTENTION!
To gain optimum tuning of frequency converter, run
AMT on a cold motor.
C01.3* Adv. Motor Data
Adjust advanced motor data using one of these methods:
1. Run AMT on cold motor. Frequency converter measures value from
motor.
2. Enter X1 value manually. Obtain value from motor supplier.
3. Use X1 default setting. Frequency converter establishes setting
based on motor nameplate data.
ATTENTION!
This parameter cannot be changed while motor runs.
C01.30 Stator Resistance (R1s)
Default setting
**
Range
Depending on motor data* [Ohm]
●
Function
:
Set stator resistance value.