C01.56 V/F Characteristic - F
Default setting 0HZ
Range
[0 - 400 Hz]
●
Function:
This parameter is an array parameter [0-5] and is only
functional when par. C01.01, Motor Control Principle is set to V/F [0].
Enter frequency points to manually form a V/F characteristic
matching motor. Voltage at each point is defined in par. C01.55, V/F
Characteristic - U.
Make a V/F characteristic based on 6 definable voltages and
frequencies, see below figure.
Simplify V/F characteristics by merging 2 or more points (voltages and
frequencies), respectively, are set equal.
●
ATTENTION!
For par. C01.56 the following applies [0]≤ [1] ≤ [2] ≤
[3] ≤ [4] ≤ [5]
C01.6* Load Dependent setting
Parameters for adjusting the load dependent motor settings.
C01.60 Low Speed Load Compensation Default setting 100%
Range
[0-199 %]
●
Function:
Use this parameter to gain optimum V/F characteristic
when running at low speed.
Enter percentage in relation to load when motor runs at low speed.
Change-over point is automatically calculated based on motor size.