HLP-NV Series
HLP-NV Series
-
49
-
●
Function:
Select the thermistor input terminal.
●
ATTENTION!
Analog Input VIN cannot be selected for other
purposes when selected as thermistor resource.
Input Digital/Analog Supply Voltage Threshold Cut-out Values
Digital 10 V
<800 ohm - >2.9k ohm
Analog 10 V
<800 ohm - >2.9k ohm
Parameter group 2: Brakes
C02.0* DC-Brake
The purpose of DC-brake function is to brake a rotating motor by
applying DC-current to the motor.
C02.00 DC Hold Current
Default setting 50%
Range
[0 - 100%]
●
Function:
This parameter either holds the motor (holding torque) or
preheats the motor.
■ The parameter is active if DC Hold has been selected in either par.
C01.72 Start Function or par. C01.80 Function at Stop.
■ Enter a value for holding current as a percentage of the rated motor
current set in par. C01.24 Motor Current. 100% DC holding current
corresponds to I
M,N
.
●
ATTENTION!
Avoid 100% current too long as it may overheat the
motor.
C02.01 DC Brake Current
Default setting 50%
Range
[0 - 100%]
●
Function:
Set DC-current needed to brake rotating motor.
Activate DC-brake in one of the four following ways:
■ DC-brake command, see par. C05.1* choice [5]
■ DC Cut-in function, see par. C02.04
■ DC-brake selected as start function, see par. C01.72
■ DC-brake in connection with Flying Start, par. C01.73.
C02.02 DC Braking Time
Default setting 10.0S
Range
[0.0 - 60 s]
Set the time DC-braking current,
set in par. C02.01, must be
applied.
●
Function:
DC-braking time defines the period during which DC-brake
current is applied to the motor.
●
ATTENTION!
If DC-brake is activated as start function, DC-brake
time is defined by start delay time.