HLP-NV Series
HLP-NV Series
-
52
-
Parameter group 3: Reference/Ramps
Parameters for reference handling, definition of limitations, and
configuration of the frequency
converter's reaction to changes
3-0* Reference Limits
Parameters for setting the reference unit, limits and ranges.
C03.00 Reference Range
Default setting
0
Range
[0] Min - Max Reference setpoint ranges can have
positive values only.
Select this if running in Process
Closed Loop.
[1] -Max-+Max Ranges can have both positive and
negative values.
●
Function:
Select the range of reference and feedback signals. Values
can be both positive and negative, unless par. C01.00, Configuration
Mode, is set to Process Closed Loop [3]. In that case only positive
values are allowed.
C03.02 Minimum Reference
Default setting 0.000
Range
[-4999.000 -4999.000]
●
Function:
Enter value for minimum reference. The sum of all
internal and external referneces are clamped (limited) to the minimum
reference value, par. C03.02.
C03.03 Maximum Reference
Default setting 50.000
Range
[-4999.000 -4999.000]
●
Function:
Maximum Reference is adjustable in the range Minimum
Reference- 4999.
Enter value for Maximum Reference.
The sum of all internal and external references are clamped (limited)
to the maximum reference value, par. C03.03.