HLP-NV Series
HLP-NV Series
-
59
-
C04.10 Motor Speed Direction
Default setting
2
Range
[0] Clockwise T h e m o t o r s h a f t r o t a t e s i n
clockwise direction. This setting
prevents the motor from running in
counterclockwise direction.
If par. C01.00 Configuration mode
has been set to Process Closed
Loop [3] this parameter must
always be set to Clockwise
[1] Counterclockwise
T h e m o t o r s h a f t r o t a t e s i n
counterclockwise direction. This
setting prevents the motor from
running in clockwise direction.
[2] Both With this setting the motor can run
in both directions. However,
the output frequency is limited to
the range: Motor Speed Low
Limit (par. C04.12) to Motor Speed
High Limit (par. C04.14).
●
Function:
A linear ramp applicable when Q-stop is activated. See par.
C05.1*, selection [4].
* only for NV4,NV5
C03.81 Quick Stop Ramp Time
Default setting 3.00/
30.00S*
Range
[0.05 - 3600 s]
Parameter group 4: Motor Limits
Parameter group for configuring limits and warning.
C04.1* Motor Limits
Use these parameters for defining the speed, torque and current working
range for the motor.
●
Function:
If terminals 96, 97 and 98 are connected to U, V and W
respectively, the motor runs clockwise when seen from the front.
●
ATTENTION!
This parameter cannot be adjusted while the motor is
running
●
Function:
Set the Minimum Motor Speed Limit corresponding to the
minimum output frequency of the motor shaft.
●
ATTENTION!
As the minimum output frequency is an absolute
value, it cannot be deviated from.
C04.12 Motor Speed Low Limit [Hz] Default setting 0.0HZ
Range
[0.0 - 400.0 Hz]