The National Fire Protection Association (NFPA) is the expert authority that local fire departments and fire safety code
enforcement authorities look to for fire safety standards and codes. Their codes are developed through a consensus standards
development process approved by the American National Standards Institute. The NFPA codes are used as guidelines by most
fire code enforcement agencies. Since these codes are guidelines, your local Authority Having Jurisdiction (AHJ) for fire code
enforcement may make the final determination. The summary chart below is based upon guidelines for facilities protected by
standard sprinkler systems.
(3)
The ThinPrep products NFPA ratings are listed in a table below this chart.
Use this chart to help you determine your maximum storage limits for flammable and combustible liquids.
Maximum Quantities of Flammable and Combustible Liquids in Laboratory Units Outside of Inside Liquid Storage Areas
(4)
Lab Unit Fire
Hazard Class
Flammable
&
Combustible
Liquid Class
NFPA
Code
Quantities in Use
Quantities in Use and Storage
Max per 100ft
2
(9.2m
2
) of
Lab Unit
(5)
Max Quantity per Lab
Unit
Max per 100ft
2
(9.2m
2
) of
Lab Unit
(5)
Max Quantity per Lab Unit
Gallons Liters Vials
(8)
Gallons Liters Vials
(8)
Gallons Liters Vials
(8)
Gallons Liters Vials
(8)
A (High)
I 45-2015
10 38 1900 480
1820
91,000
20 76
3800 480 1820
91,000
I, II, IIIA
45-2015
20
76
3800
800
3028
151,400
40
150
7500
1600
6060
303,000
B
(6)
(Moderate)
I 45-2015
5 19
950
300
1136
56,800
10
38
1900
480
1820
91,000
I, II, IIIA
45-2015
10
38
1900
400
1515
75,750
20
76
3800
800
3028
151,400
C
(7)
(Low)
I 45-2015
2
7.5
375
150
570
28,500
4 15
750
300
1136
56,800
I, II, IIIA
45-2015
4
15
750
200
757
37,8520
8
30
1500
400
1515
75,750
D
(7)
(Minimal)
I
45-2015 1
4 200 75 284
14,200 2 7.5 375 150 570
28,500
I, II, IIIA
45-2015
1
4
200
75
284
14,200
2
7.5
375
150
570
28,500
Maximum Quantities of PreservCyt Solution (Class IC) That Can Be Stored per Fire Area
(9)
Outside a Safety Flammable Cabinet
Location NFPA
Code
Gallons
Liters
Vials
(8)
General Warehouse
(10)(12)(13)
30-2015
120
460
23,000
Liquid Warehouse
(3,11)
30-2015
Unlimited
Unlimited
Unlimited
Office, to include Exam Rooms
30-2015
10
38
1900
Allowable Quantities of PreservCyt Solution That Can Be Stored in a Liquid Storage Room
Location NFPA
Code
Gallons
Liters
Vials
(8)
Maximum allowable storage per ft
2
in an inside storage room that is smaller than 150ft
2
in size.
30-2015
5
19
950
Maximum allowable storage per ft
2
in an inside storage room that is larger than 150ft
2
and less than
500ft
2
in size.
30-2015 10
38
1900
(1)
Solution classifications: PreservCyt – Class IC; CytoLyt – Class II; CellFyx – Class IB
(2)
This information is Hologic’s summary of the various regulations. To view the codes in their entirety, please refer to NFPA 30 and NFPA 45.
(3)
A Liquid Warehouse shall have a sprinkler system that complies with the appropriate system indicated in NFPA 30.
(4)
An Inside Liquid Storage Area is a storage room totally enclosed within a building and having no exterior walls.
(5)
A Laboratory Unit is the area surrounded by firewalls per NFPA 30
Flammable and Combustible Liquids Code
.
(6)
Reduce quantities by 50% for B laboratory units located above the 3
rd
floor.
(7)
Reduce quantities by 25% for C and D laboratory units located on the 4
th
-6
th
floors of a building and reduce quantities by 50% for C and D laboratory units above the
6
th
floor
(8)
20ml PreservCyt vials.
(9)
A Fire Area is the area of a building separated from the remainder of the building by construction having a fire resistance of at least 1-hour and having all
communicating openings properly protected by an assembly having a fire resistance rating of at least 1-hour per NFPA 30
Flammable and Combustible Liquids Code.
Summary of Contents for ThinPrep 3000
Page 1: ......
Page 4: ...The ThinPrep Processor The ThinPrep Processor ...
Page 5: ...MAN 03939 001 Rev 004 page 1 of 13 Instructions for Use ...
Page 18: ...Table of Contents Table of Contents ...
Page 23: ...1 Introduction 1 Introduction ...
Page 42: ...2 ThinPrep 3000 Installation 2 ThinPrep 3000 Installation ...
Page 55: ...3 PreservCyt and CellFyx Solutions 3 PreservCyt and CellFyx Solutions ...
Page 71: ...4 Sample Collection and Preparation 4 Sample Collection and Preparation ...
Page 80: ...5 Instrument Operation 5 Instrument Operation ...
Page 105: ...6 Maintenance 6 Maintenance ...
Page 148: ...7 Troubleshooting 7 Troubleshooting ...
Page 205: ...8 Staining and Coverslipping 8 Staining and Coverslipping ...
Page 212: ...9 The ThinPrep Pap Test Training Program 9 The ThinPrep Pap Test Training Program ...
Page 215: ...10 User Interface Screens 10 User Interface Screens ...
Page 226: ...Index Index ...
Page 232: ...INDEX Index 6 ThinPrep 3000 Processor Operator s Manual This page intentionally left blank ...
Page 233: ...Service Information Service Information ...
Page 236: ...Ordering Information Ordering Information ...
Page 243: ...Safety Data Sheets Safety Data Sheets ...
Page 246: ...Appendix Appendix ...
Page 255: ......
Page 256: ......