background image

 

51 

7.5. ELECTRICAL INSTALLATION

 

 
7.5.1. GENERAL GUIDELINES 

All electrical work shall be carried out under the supervision of an authorized, licensed electrician. 

The present 

state adopted edition of the National Electrical Code as well as all local codes and regulations shall be 
complied with.

 

 

7.5.2. VERIFICATION OF POWER SUPPLY 

Prior to making any electrical connections or applying power to the pump, compare the power supply available at 
the pump station to the data on the unit's nameplate. Confirm that both voltage and phase match between pump 
and control panel. The voltage supplied at the pump shall be +5 / -10% of the nameplate value, frequency shall be 
+ / - 1% of the nameplate value, the voltage phase balance shall be within 1% and the maximum corrected power 
factor shall be 1.0. 

 
7.5.3. POWER LEAD WIRING  

HOMA pumps may be provided with 1 or more cables, depending on motor horsepower and operating voltage. 
Power leads L1, L2, & L3 may be provided as single conductor, or as multiple conductors. Multiple conductor 
configurations may use leads from separate cables, or may use two conductors within one cable. Please refer to 
wiring diagram in the appendix for specific connection details. The pump must be connected electrically through a 
motor starter with proper circuit breaker protection in order to validate warranty. Do not splice cables. 
 

7.5.4. THERMAL SWITCH WIRING 

Pumps are equipped with thermal switches embedded in the stator windings which are normally closed, 
automatically resetting switches. Switches will open when the internal temperature rises above the design 
temperature, and will close when the temperature returns to normal. Thermal switches must be wired to a current 
regulated control circuit in accordance with the NEC. 
Identify thermal switch leads marked T1 and T3 in the power or control cable. 
The resistance across the leads will be 0.5 Ohms. Thermal leads must be connected to the thermal overload relay 
located in the control panel. Thermal switch leads must be connected to validate warranty. 
 

Note: All sizes of Class 1, Div. 1 pumps for hazardous service must have thermal switch leads connected 
to a current regulated control circuit in accordance with NEC. 
 
7.5.5. SEAL PROBE WIRING  

The mechanical seal leak detector probe utilized in the pump is a conductive probe which is normally open. The 
intrusion of water into the seal chamber completes the electrical circuit. Control panel provisions will sense this 
circuit closure, and will provide indication or alarm functions depending on the panel design. 
Either single or dual wire systems may be provided. Single wire systems utilize one energizing conductor, and the 
pump casing and neutral lead as the ground or return portion of the circuit. The dual wire systems utilize two 
separate conductors for each leg of the circuit. 
With either system, the seal probe leads must be wired into a control circuit provided in the control panel.  This 
control circuit must energize the probe with a regulated power source, and sense the closed circuit in event of 
water intrusion  Indication and alarm functions must also be provided in the control circuit.  Please see control 
panel wiring diagram for seal probe connection points. 

 For Hazardous Area Classification Pumps, leak detector circuit must be in conformance with applicable NEC 

codes and regulations. 
 

7.5.6. START / RUN CAPACITORS AND RELAYS: 

All single phase motors require start and run capacitors along with a start relay to operate. Capacitors and relays 
must be sized for the specific motor. 
Capacitors are sized based on ideal conditions. 
The run capacitor may need to be resized to match the available field voltage. Each cap kit shipped is supplied 
with a wiring diagram and start up procedure. 
 

7.5.7. Variable Frequency Drives 
Special considerations must be taken when operating pumps with variable frequency drives (inverters).

 

The inverter circuit design, horsepower required by pump, motor cooling system, power cable length, operating 
voltage, and anticipated turndown ratio must be fully evaluated during the design stage of the installation. 
 

As a minimum, properly sized load reactors and filters must be installed between the inverter and the 
pump to protect the pump motor from damaging voltage spikes.

 Warranty coverage will not be provided on 

any pump motor that is operated with a variable frequency drive, unless the load side of the inverter is properly 
isolated from the pump. 
 
 

Summary of Contents for CHRS Series

Page 1: ...Version 03 2015 No 00510601 01 Original Betriebsanleitung Original Instruction Manual HOMA Pumpenfabrik GmbH Industriestr 1 D 53819 Neunkirchen Seelscheid 60 Hz Baureihe Serie CHRS HRS ...

Page 2: ...ped fluids 38 3 General description 38 3 1 Application 38 3 2 Types of use 38 3 3 Construction 38 4 Package Transport and Storage 41 4 1 Delivery 41 4 2 Transport 41 4 3 Storage 41 4 4 Returning to the supplier 42 5 Installation and Start Up 42 5 1 General 42 5 2 Installation 42 5 3 Start Up 45 5 4 Electrical system 45 5 5 Motor protection 46 5 6 Operation with a static frequency converter 46 5 7 ...

Page 3: ...Low Voltage Directive 06 95 EEC EC Directive explosion prooved operating material 94 9 EEC EC Directive construction products 11 305 EEC Relevant harmonized industrial standards EN 60335 2 41 EN 60335 1 EN 60204 Part 1 EN 61000 6 1 EN 60034 1 EN 61000 6 3 EN 61000 6 2 EN 55014 2 EN 61000 3 3 EN 50014 18 19 20 EN 12050 1 4 EN 61000 6 4 EN 55014 1 EN 61000 3 2 EN ISO 12100 1 and 2 Specially applied ...

Page 4: ...lace costs for the ride of the mechanicians to the location and from the installation place as well as costs for transport are not components of our warranty Hereby arose costs especially costs for checking and transport are bearing by the sender or operator of the pump This is also valid for an asserted warranty claim if a check results that the unit works faultless and is free of defects All pro...

Page 5: ...inated immediately by authorized personnel The product should only be operated if it is in proper working order During the agreed warranty period the product may only be repaired by the manufacturer or an authorized service workshop The manufacturer reserves the right to recall the damaged product to the factory for inspection 1 5 5 Exclusion from liability No liability will be assumed for product...

Page 6: ...ving the product The machine must always be switched off before any work is performed on it assembly dismantling maintenance installation The machine must be disconnected from the electrical system and secured against being switched on again All rotating parts must be at a standstill The operator should inform his her superior immediately should any defects or irregularities occur It is of vital i...

Page 7: ...ces such as soft startup control or frequency drives are used the relay manufacturer s specifications must be followed in order to conform to EMC Special separate shielding measures e g special cables may be necessary for the power supply and control cables The connections may only be made if the relays meet the harmonized EU standards Mobile radio equipment may cause malfunctions Beware of electr...

Page 8: ...pumped fluid differs in regard to composition corrosiveness abrasiveness TS content and many other aspects Generally our products can be used for many applications For more precise details see chapter 3 the machine data sheet and the order confirmation It should be remembered that if the density viscosity or the general composition change this can also alter many parameters of the product When swi...

Page 9: ... Year type test Year type test 12b Declaration of performance Declaration of performance 13 Build year Build year 14 Motor type Motor type 15 IE Marking IE Marking 16 Frequency Frequency 17 Voltage 3 phase Voltage 3 phase 18 Nominal current 3 phase Nominal current 3 phase 19 Motor RPM Motor RPM 20 Voltage Star connection Voltage Star connection 21 Nominal current Star connection Nominal current St...

Page 10: ...de manual pump re start All explosion proof models have both sets of sensors built in as described above with wire ends marked T1 T2 T3 They have to be connected accordingly as described above The temperature sensor set must be connected to the switchgear unit so that it switches off if it overheats Check of Direction of Rotation After the electrical connection has been made check that the agitato...

Page 11: ...unsecured If the product falls over injury can occur The product has to be stored at a place free from vibrations and agitation to avoid damage from the ball bearings We recommend a dry frost protected room with a temperature of between 5 C and 25 C for storage The product may not be stored in rooms where welding work is conducted as the resulting gases and radiation can damage the elastomer parts...

Page 12: ...at lifting gear can be fitted without any trouble since this is required for assembly and removal of the machine The maximum bearing capacity must be greater than the weight of the machine add on units and cable Electric power cables must be laid out in such a way that safe operation and non problematic assembly dismantling are possible at all times The electric power cables should be fastened pro...

Page 13: ...o the mixer Fasten the mixer to the motor bracket Item 12 as illustrated using two cylinder head screws Item 1 one cylinder head screw Item 2 and the associated U washers Items 3 4 Lay the connecting cable between the pipe clamps Item 6 and screw it to the motor bracket using two cylinder head screws and U washers Items 5 4 Great care should also be taken to ensure that the cable is always laid or...

Page 14: ...tem 1 Next hold the upper fastening on the anchor rods intended for that purpose and fasten the anchor rods with the nuts The position of the lower fastening has now been determined Use the supplied anchor rods and bonding anchor cartridges for fastening it No Description 1 lower fastening 2 upper fastening 3 angle clamp bracket 4 square tube 5 mixer 6 motor bracket 7 cable anchor clamp 8 stainles...

Page 15: ...the mixer is immersed at least half the diameter of the propeller Make sure that all necessary safety precautions have been carried out e g to prevent persons from falling into the tank After longer standstill of the mixer clean the propeller and motor surface from dried remains of mixing liquid in order to prevent cooling problems 5 4 Electrical system Observe the relevant local and national regu...

Page 16: ...in star delta mode is 3 seconds If the motor protection is not installed in the line set the motor protection to the rated current when fully loaded Starting transformer soft start Motor protection should be set to the rated current when fully loaded At partial load we recommend that motor protection is set 5 above the measured current at the operating point The maximum start up time at reduced vo...

Page 17: ...ing agents fires unshielded lighting and smoking are prohibited Machines which circulate fluids hazardous to health or which come into contact with them must be decontaminated It must be ensured that no dangerous gases can form or are present Ensure that all necessary tools and materials are available Tidiness and cleanliness guarantee safe and problem free operation of the machine After working o...

Page 18: ... arise bearings must be replaced at the manu facturer s works The oil in the oil chamber should be changed after every 6000 hours of operation Oil condition Place mixer horizontally so that one of the oil chamber screws is at the top Remove the screw and extract a small amount of oil If the oil is milky or cloudy it indicates a defective shaft seal In this case have the condition of the shaft seal...

Page 19: ...l specification bio degradable Shell Ondina 917 Remove used oil according to local regulations Oil capacity is 1 0 liter Steps 1 Remove screw 2 Release oil 3 4 Fill in correct quantity of oil see below table 5 Re fasten screw ...

Page 20: ...QUIPMENT INVENTORY AND INSPECTION Upon arrival of pump shipment carefully unpack all components and compare with shipping and purchase order documents to ensure that the order is complete Also inspect equipment for any damage that might have occurred in shipment If any problems are detected contact an authorized HOMA customer service immediately 7 4 TRANSPORTATION AND STORAGE PROCEDURE Always lift...

Page 21: ... leads connected to a current regulated control circuit in accordance with NEC 7 5 5 SEAL PROBE WIRING The mechanical seal leak detector probe utilized in the pump is a conductive probe which is normally open The intrusion of water into the seal chamber completes the electrical circuit Control panel provisions will sense this circuit closure and will provide indication or alarm functions depending...

Page 22: ... over tighten Install the profile gasket if not already installed at the factory into the guide claw with the large diameter fitted into the groove inside the claw Refer to the diagram included with the auto coupling kit for proper profile gasket installation Install suitable lifting chain of an adequate size and length to permit proper lowering and raising of the pump Properly locate the base and...

Page 23: ...mension drawing Foundation bolts are to be embedded in the concrete Suction Piping Suction piping should be at least as large as the pump inlet elbow suction If reducers are utilized they should be of the conical type If the liquid source level is below the volute horizontal centerline the reducer must be eccentric and installed with the level side up If the liquid level is above the pump volute h...

Page 24: ... PUMP OPTION The cooling jacket has been supplied based upon the specified operating conditions of this application It is important this jacket is function properly or the internal motor components could become damaged Several cooling configurations are available depending upon customer preference and system requirements You must know what configuration of cooling system is to be used with the pum...

Page 25: ...ped media The water inlet is routed into the jacket s lowest port and returned out of the highest port This option does NOT allow water to enter the pumped media and pump must be ordered from factory this way Required Hardware Mounting a regulating valve pressure gauge and automated block valve between the water supply and the upper jacket port is required The supply valve should be adjusted to al...

Page 26: ...32 Actual system head is higher than calculated or specified 33 Incorrect impeller rotation direction 34 Sump liquid level is below pump s minimum submergence requirement 35 Closed discharge valve or jammed check valve 36 Wear ring s worn If Applicable 37 Vortex at pump s suction 38 Discharge valve partially closed 39 Insufficient NPSHA Dry Pit Application 40 Actual system head is lower than speci...

Page 27: ...any external part that appears worn or damaged 5 SEAL CHAMBER OIL Note Use extreme care when removing the seal chamber plug as the chamber may become pressurized if seal failure has occurred Seal chamber oil should be checked for signs of water intrusion or other impurities any time the pump is removed from wet well To check the condition of the oil remove the oil fill plug Drain the chamber volum...

Page 28: ...e not to damage the sealing surface 10 Verify that seal chamber oil level is within of the indicated value Measurement is from oil level to the top of hole See IOM Manual for seal chamber oil volume if required 11 Remove the new sealing gasket from package and install it onto the seal probe plug 12 Install the seal probe with gasket into the opening taking care not to damage the cable Then tighten...

Page 29: ...uld have the highest current reading Lead Z2 start should have the lowest reading If Z2 current draw is greater than the current draw of either U1 or U2 a smaller size Run capacitor lower microfarad rating is required to correct the condition Example If a 60 µf Run capacitor was supplied change to a 50 µf Run capacitor and check current readings Typically only one step down in capacitor size is re...

Page 30: ...N A 0 5 1 1 400 lbs 181 kg 29HP 1750 P N A 0 4 0 7 500 lbs 227 kg Values should be as indicated between any 2 power leads Note Resistance values include 30 cable and should be within 10 of above value Above 30 HP resistance values between 230 and 460 volt machines very by less than 0 1 ohm Consult factory with specific requirements Impeller Bolt Torque 10mm 26ft lb 35Nm 12mm 45ft lb 61Nm 16mm 108f...

Page 31: ...seinrichtungen sind dann mit dem Lastkabel ausgeführt Aderbezeichnung Motor Überwachungseinrichtung Überwachungen in der Wicklung T1 T2 Temperaturbegrenzer 2 Schalter in Reihe T1 T4 Temperaturregler 2 Schalter in Reihe T1 T2 T3 Temperaturbegrenzer und regler K1 K2 PTC Kaltleiter 3 Kaltleiter in Reihe PT1 PT2 3 x PT100 einzeln ausgeführt PT3 PT4 PT6 PT6 Lagerüberwachung P1 P2 PT100 Lager oben P3 P4...

Page 32: ...ng devices are run from the power cable Cable identification Motor Monitoring system Monitoring in winding T1 T2 Temperature limiter 2 switches in series T1 T4 Temperature controller 2 switches in series T1 T2 T3 Temperature limiter and controller K1 K2 PTC Thermistor 3 thermistors in series PT1 PT2 3 x PT100 individually installed PT3 PT4 PT6 PT6 Bearings monitoring P1 P2 PT100 upper bearing P3 P...

Page 33: ... _____________________ ätzend nein ja welche Stoffe _____________________ mikrobiologisch nein ja welche Stoffe _____________________ explosiv nein ja welche Stoffe _____________________ radioaktiv nein ja welche Stoffe _____________________ sonstige Schadstoffen nein ja welche Stoffe _____________________ Rechtsverbindliche Erklärung Hiermit versichern wir dass die Angaben korrekt und vollständig...

Page 34: ...e no yes which substance __________________ microbiological no yes which substance __________________ explosive no yes which substance __________________ radioactive no yes which substance __________________ other substances no yes which substance __________________ Legally binding declaration We hereby certify that the returned parts have been cleaned carefully To the best of our knowledge they a...

Reviews: