35
Hazard information
bus only. The Homematic IP Wired bus is a SELV
power circuit. The power supply of the building
installation and the Homematic IP Wired bus have
to be laid separately. Common cable routing for
power supply and the Homematic IP Wired bus in
installation and junction boxes is not permitted.
The required isolation for power supply of the
building installation to the Homematic IP Wired
bus must be observed at all times. Non-compli-
ance with the installation instructions can cause
fire or introduce other hazards.
For secure operation, the device has to be installed
in a power distribution panel according to VDE
0603, DIN 43871 (low-voltage sub-distribution
board), DIN 18015-x. The installation must be car-
ried out on a mounting rail (DIN rail) according to
EN 60715. Installation and wiring have to be per-
formed according to VDE 0100 (VDE 0100-410,
VDE 0100-510 etc.). Please consider the technical
connection requirements (TAB) of your energy
supplier.
When connecting to the device terminals, take
the permissible cables and cable cross sections
into account.