2-31
• Engine Starts But Then Stalls
Check the fuel level in the tank.
Add fuel and then restart the engine.
Sufficient
Insufficient
Loosen the drain screw and check whether
fuel is reaching the carburetor.
Check for restriction in the fuel filter, fuel
valve or fuel tube (P. 7-2).
Fuel reaching the carburetor
Not reaching
the carburetor
Check whether an error code is displayed
on the i-Monitor when stopping the engine.
Refer to Failure By Error Code (P. 2-11).
Not displayed
Displayed
Check whether the overload indicator is on
when stopping the engine.
ON
OFF
To P. 2-32
Disconnect the AC appliance(s). Check
whether foreign substance is blocking the
cooling air duct causing overheating.
Check whether the generator is placed by
the side of a wall.
Set the generator in the correct position and
restart the engine and recheck.
Incorrect
Good
Check the harness connecting the inverter
unit and AC receptacle for open or short
circuit and for proper connection.
Check the harness connecting the inverter
unit and generator for open or short and for
proper connection.
Wire harness check points
R
Bu
Viewed from terminal side
GENERATOR
(SLAVE)
GENERATOR
(MASTER)
GENERATOR WIRE HARNESS
INVERTER
UNIT
INVERTER
UNIT
Bu: BLUE
R: RED
W: WHITE
W
Normal
Check the generator (P. 11-7).
Replace the stator (P. 11-5).
Normal
Abnormal
Replace or repair the main wire harness
and/or generator wire harness.
Abnormal
Replace the inverter unit and retest (P. 6-2).