Section 2: Mounting and Wiring
17
Dialer Capture Module
An optional Dialer Capture module (PRODCM)can be used for controls that send Contact ID alarm
signals via the control panel's dialer. The dialer capture module replaces the phone line and simulates
the phone service to the control panel. The alarms are then sent to AlarmNet for routing to the central
monitoring station.
1. Power down the communicator and disconnect the battery.
2. Install the Dialer Capture module by mating the module's connector to the edge connector on the
upper right side of the communicator's PCB. Make sure the module is fully seated in the
connector. Slip the module board under the snap tab to lock it in place as shown below.
3. Connect the control panel's Telco Ring (R) and Tip (T) terminals individually to the Ring and Tip
terminals on the Dialer Capture module (module terminals have no Ring/Tip polarity). See
diagram below.
Dialer Capture Module Connections
Do not connect the outside phone line to either the Dialer Capture module or the
control panel. There should be no connection to the outside phone line when using the
Dialer Capture module.
For replacement installations, make sure to disconnect the outside phone line when
using the Dialer Capture module with the communicator.
Dialer Capture Control Panel Programming Notes
After the Dialer Capture module has been installed, make sure the control panel is programmed for
the following.
•
Dialer operation is set for DTMF Tone Dialing for each phone number (pulse dialing is not
supported and must be disabled in the control panel)
•
PABX field is disabled (the Dialer Capture module does not communicate through a PABX)
•
Phone numbers and account numbers are programmed (to ensure the maximum number of
messages can be transmitted to the central station before a communication failure occurs, ensure
the control panel is programmed with a primary and secondary central station number)
•
Report format is set to Contact ID for each phone number
•
The maximum number of retry attempts is programmed
•
Desired zone and partition reports are enabled.