RLV3150
5
33-00209ES—05
SETUP MENU
1.
Press the
Up
and
Down
buttons
simultaneously for three seconds
to enter the setup menu.
2.
Press the
Up
or
Down
button to
change the option.
3.
Press the
Up
and
Down
buttons
simultaneously and briefly to
advance to the next parameter.
4.
When the last parameter is dis-
played, press the
Up
and
Down
buttons for three seconds to save
any changes and exit the menu.
NOTE:
If you do not press any button
for 15 seconds, the thermostat
will automatically save any
changes you have made and
will then return to its normal
display.
IN CASE OF DIFFICULTY
Parameter
Options
Display and
default setting
Minimum setpoint
5°C - 30°C (41°F - 86°F)
NOTE:
The minimum setpoint cannot be
set higher than the value set for
the maximum setpoint.
Maximum setpoint
5°C - 30°C (41°F - 86°F)
NOTE:
The maximum setpoint cannot be
set lower than the value set for the
minimum setpoint.
PROBLEM
SOLUTIONS
Thermostat is hot.
This is normal unless the thermostat is too hot to touch. Ensure that the heater
capacity does not exceed the thermostat’s maximum load.
Wrong temperature is
displayed.
Avoid any of the following conditions:
The thermostat is exposed to an air draft.
The thermostat is located near or above a heat source such as a light dimmer.
Display disappears and
reappears after a few
minutes.
The thermal circuit breaker on the heater has temporarily opened. This can happen
if the heater is obstructed by furniture or curtain and has overheated, or if the
thermal circuit breaker is defective or too sensitive.
Display looks faded when
heating is activated.
The heater capacity is probably less than the thermostat minimum load
requirement. The thermostat cannot be used below that rating.