Mounting and Connection Instructions TouchCenter Keypad BUS-2
7.2 Installation hints
The BUS-2 connection lead must be a shielded lead. The shielding should not be used as 0V
feed lines.
The installation site of the energy supply should be as close as possible to the operating unit.
The following table contains the maximum conductor length:
Distance between energy supply and operating unit:
line cross-section of Ø 0.6mm
0.25 mm
line cross-section Ø 0.8mm
0.5 mm
Cross-section
No. of
Max.
Cross-section
No. of
Max.
(mm )
cores
distances (m)
(mm )
cores
distances (m)
0,25
1
20
0,5
1
40
0,5
2
40
1,0
2
80
0,75
3
60
1,5
3
120
1,0
4
80
2,0
4
160
1,25
5
100
2,5
5
200
2,5
9
180
4,5
6
360
Cable recommendation: JY(St) nx2x0.8Ø
In order to obtain optimum interference immunity, the connections should be as follows:
1.
Insulate lines, separate tracer wires.
2.
Shorten incoming and outgoing BUS lines, in so far as they exist and insert in the
terminals
3.
Use cable ties to fix the cables at the pull reliefs on the mounting plate.
4.
Shorten tracer wire(s) and solder to the shield terminal (soldering tab).
Keep the tracer wires of the shieldings as short as possible when soldering to the
soldering tab of the housing base.
"Conductor length”
=
=
2
2
2
2
8. Technical data
Power supply via BUS-2
Operating temperature range
-5 °C to +45 °C
Storage temperature range
-25 °C to +60 °C
Environmental class as per VdS
II
Protection class as per DIN 40 050
IP40
Dimensions (W x H x D)
184 x 129 x 34 mm
Screen diagonal
5,7” (14,48 cm)
Colour
Grey white (similar to RAL 9002)
Rated operating voltage
12 V DC
Operating voltage range
10 V to 15 V DC
Current consumption at 12 V DC
115 mA (idle)
160 mA (with illuminated display)
180 mA (with display and buzzer test
Dimensions (W x H x D) with VdS-Kit
184 x 129 x 40 mm