VR9205R SERIES 1000 DIRECT IGNITION GAS CONTROL WITH INTEGRATED GAS/AIR MODULE
3
69-2305—03
Dust or Grease Accumulation
Heavy accumulations of dust or grease can cause the
control to malfunction. Where dust or grease can be a
problem, provide covers for the control to limit
contamination.
Heat
Excessively high temperatures can damage the control.
Make sure the maximum ambient temperature at the
control does not exceed the rating of the control. If the
appliance operates at very high temperatures, use
insulation, shielding, and air circulation, as necessary, to
protect the control. Proper insulation or shielding should
be provided by the appliance manufacturer; verify proper
air circulation is maintained when the appliance is
installed.
INSTALLATION
When Installing this Product…
1.
Read these instructions carefully. Failure to follow
them could damage the product or cause a
hazardous condition.
2.
Check the ratings given in the instructions and on
the product to make sure the product is suitable for
your application.
3.
Installer must be a trained, experienced service
technician.
4.
After installation is complete, check out product
operation as provided in these instructions.
WARNING
Fire or Explosion Hazard.
Can cause property damage, severe injury
or death.
Follow these warnings exactly:
1. Disconnect power supply before wiring to
prevent electrical shock or equipment damage.
2. To avoid dangerous accumulation of fuel gas,
turn off gas supply at the appliance service
valve before starting installation, and perform
Gas Leak Test after installation is complete.
3. Always install a sediment trap in gas supply line
to prevent contamination of gas control.
4. Do not force the on-off switch. Use only your
fingers to operate the on-off switch. Never use
any tools. If the electronic on-off switch does
not operate by hand, the gas control should be
replaced by a qualified service technician.
Force or attempted repair may result in fire or
explosion.
5. Plan the installation as outlined below.
6. Plan for frequent maintenance as described in
the maintenance section.
Mounting position
The valve can be mounted 0 to 90 degrees in any
direction from the top of the valve facing up, including
outlet facing upward or downward. See Fig. 2. If the valve
is mounted horizontally; the top of the valve must be even
with or above the center line of the piping.
NOTE: A deviation of more than 3° from the OEM's orig-
inal design mounting orientation can result in an
unacceptable change in gas outlet pressure.
See OEM application installation guide.
To prevent blockage due to condensation, the positive air
pressure connection should not be connected to
combustion products.
Fig. 2. VR9205R Series 1000 mounting.
CAUTION
Equipment Damage Hazard.
Can burn out thermostat or transformer.
Applying a jumper across (or shorting) the valve
coil terminals, even temporarily, can burn out the
thermostat or transformer.
Follow the appliance manufacturers instructions if
available; otherwise use these instructions as a guide.
IMPORTANT
These gas controls are shipped with protective
seals over the inlet and outlet tappings. Do not
remove the seals until ready to install adapters
or connect the piping.
Converting Gas Control from Natural Gas
to LP Gas (or LP Gas to Natural Gas)
WARNING
Fire Or Explosion Hazard.
Can cause property damage, severe injury
or death.
VR9205R cannot be converted between LP or
Natural gas. To convert, see appliance
manufacturer for recommendations.
Install Bushings To Control
If bushings are being installed on the control, mount them
as follows:
Bushings
1.
Remove the seal over the control inlet or outlet.
2.
Apply a moderate amount of good quality pipe
compound to the bushing, leaving two end threads
bare. On an LP installation, use compound that is
resistant to LP gas. Do not use Teflon tape.
3.
Insert the bushing in the control and carefully thread
the pipe into the bushing until tight.
M29133
VERTICAL
PIPING
HORIZONTIAL
PIPING
INLET OR
OUTLET
0 TO 90°
0 TO 90°
TOP OF VALVE