10260S Series Actuators

 Top Cover Assembly Kit Instruction

Document Number

Form: 62-86-33-25

Effective: 09/01

Supersedes: none

Overview

These instructions apply to the following kit: 51500324-501 Top Cover Assembly with Display Upgrade
Kit
 and its application to the 10260S Series Actuators.  This kit allows you to add or replace the local
display/keypad control function to 10260S actuators.

Summary

The top cover assembly of the 10260S contains the display and keypad components which are the local
interface for actuator operation.   The transformer is also mounted inside the top cover.  The transformer uses
the input power to provide internal voltages to the power distribution and main PWA.  See Figure 1.  Follow
the procedure in Table 1 to install or replace the top cover assembly.

Tools Needed

To perform the installation procedure, you will need the following tools:

 

Medium Flat-blade screwdriver

 

Medium Phillips screwdriver

 

Small needle-nosed pliers

Procedure

WARNING

Disconnect power before accessing components inside the actuator.

ATTENTION

When working with Printed Wiring Assemblies (PWAs) always protect against electrostatic discharge by
wearing a grounded wrist strap.

Summary of Contents for 10260S Series

Page 1: ...nts which are the local interface for actuator operation The transformer is also mounted inside the top cover The transformer uses the input power to provide internal voltages to the power distribution and main PWA See Figure 1 Follow the procedure in Table 1 to install or replace the top cover assembly Tools Needed To perform the installation procedure you will need the following tools Medium Fla...

Page 2: ...able 1 Top Cover Assembly Installation Procedure Step Action 1 Remove AC power to the actuator 2 Remove the seven screws and separate the extended cover from the actuator case See Figure 1 Lay extended cover assembly on a flat surface 3 Remove seven screws and the top cover from the actuator case See Figure 1 Lay top cover assembly on a flat surface Procedure continued on next page ...

Page 3: ...n PWA Remove black and gray wire leads at pins 5 and 6 of the connector Mark as necessary for reassembly 6 Disconnect cable from P5 connector on the main PWA Disconnect ribbon cable from P4 connector on the Main PWA if present See figure Main CPU PWA P5 P4 7 Cut any cable ties to free the transformer wires from other cables if necessary 8 Disconnect the green wire of the transformer from the chass...

Page 4: ...sformer black red and white and alter as necessary For 120 Vac power input Cut red wire and crimp with wire nut For 240 Vac power input Cut black wire and crimp with wire nut Insert the unaltered wire into pin 3 of the Ppwr connector and the white wire into pin 4 of the connector 14 Connect the transformer primary green wire to the chassis ground on the actuator case 15 Insert the black and gray w...

Page 5: ...overage Honeywell will repair or replace without charge those items it finds defective The foregoing is Buyer s sole remedy and is in lieu of all other warranties expressed or implied including those of merchantability and fitness for a particular purpose Specifications may change without notice The information we supply is believed to be accurate and reliable as of this printing However we assume...