190797-YAD  /  190797M-YAD

TUSCAN UNIVERSAL CONTROLLER

INSTALLATION GUIDE

Summary of Contents for 190797-YAD

Page 1: ...l Systems All Rights Reserved ZA10002 YAD UK07 R01196 ZA10003 YAD UK07 R01196 ZA10004 YAD UK07 R01196 ZA10005 YAD UK07 R01196 ZA10006 YAD UK07 R01196 ZA10053 YAD UK07 R01196 190797 YAD 190797M YAD TUSCAN UNIVERSAL CONTROLLER INSTALLATION GUIDE ...

Page 2: ...se of this product or document All Installation and Commissioning work on Honeywell equipment should be carried out by suitably qualified personnel only Normal safety precautions and good working practice should be observed to prevent damage or injury at all times We welcome comments about our products and documentation Contact us at Honeywell Cooling Refrigeration Newhouse Industrial Estate Mothe...

Page 3: ...bit switch 3 is ON If gas defrost is required connect N C S G V to Relay 3 N C contact Defrost Heater ZA 10002 YAD Issue a 5 11 96 Product Part No Universal Controller 190797 YAD Warning Before you work on this equipment isolate the electrical supply and also the live feed to any incoming signals Remember that live signals may be derived from more than one source Features Controls and monitors HT ...

Page 4: ... Defrost Min Recovery Time 18 00 00 to 99 00 Min Sec 20 00 Defrost Max Recovery Time 19 00 00 to 99 00 Min Sec 30 00 Defrost Type 0 Elect 1 2 Gas 2 3 Gas 22 0 to 2 0 Defrost Alarm Temp 23 49 to 60 C 20 Defrost Mode 0 Local 1 Remote 24 0 to 1 0 Defrost Hold 0 Off 1 On 26 0 to 1 0 Pulse Defrost 0 Off 1 On 25 0 to 1 0 Pump Down 1 20 00 00 to 07 00 Min Sec 00 00 Pump Down 2 21 00 00 to 07 00 Min Sec 0...

Page 5: ...for errors or for incidental or consequential damages in connection with the furnishing performance or use of this product or document Relay 1 Relay 2 Relay 3 Relay 4 Relay 5 Note This simplified wiring diagram omits circuit protection ON 1 2 3 4 5 6 7 8 P6 Logging P5 Defrost terminate P4 Evaporator out P3 Evaporator in P2 Air off P1 Air on Temperature Probes Bit switches OPTIONS EXECUTE PAGE PAGE...

Page 6: ... 59 Hrs Mins 01 00 Number of Defrosts per Day 12 0 to 6 6 No Defrost Time 13 0 to 25 Hrs 7 Gas Defrost Detect 14 0 to 30 C 18 Defrost Terminate Temperature 15 49 to 30 C 10 14 Defrost Minimum Time 16 00 00 to 99 00 Min Sec 05 00 Defrost Maximum Time 17 00 00 to 99 00 Min Sec 24 00 25 00 Drain Down Time 18 00 00 to 20 00 Min Sec 01 30 Defrost Min Recovery Time 19 00 00 to 99 00 Min Sec 20 00 Defros...

Page 7: ...2 Plant fault 1 N L E Mains Supply DIN Box Display Fans Suction line valve N C Liquid line valve Setup unit extension cable screen red white black green blue green yellow white red CN7 CN8 P2 P1 CN9 CN10 CN11 CN12 CN13 CN14 CN15 CN5 CN6 CN4 CN3 CN2 CN1 YAD Controller on a Genus Network screen white black CN7 Controller on a Woodley Network Controller Fig 2 Position of probes should be in accordanc...

Page 8: ...efrost Detect 24 10 to 30 C 18 0 Defrost Minimum Time 26 00 00 to 05 00 Min Sec 05 00 Defrost Maximum Time 27 00 00 to 26 00 Min Sec 24 00 25 00 Defrost Terminate Temperature 25 6 to 14 C 10 14 Drain Down Time 28 00 00 to 03 00 Min Sec 01 30 Defrost Min Recovery Time 29 00 00 to 35 00 Min Sec 20 00 Defrost Max Recovery Time 30 15 00 to 35 00 Min Sec 30 00 Defrost Type 0 Elect 1 2 Gas 2 3 Gas 35 0 ...

Page 9: ...Case off Normal white green red Plant fault 2 Plant fault 1 N L E Mains Supply DIN Box Display Fans Setup unit extension cable screen red white black green blue green yellow white red CN7 CN8 P2 P1 CN9 CN10 CN11 CN12 CN13 CN14 CN15 CN5 CN6 CN4 CN3 CN2 CN1 YAD Controller on a Genus Network screen white black CN7 Controller on a Woodley Network Controller Fig 2 Position of probes should be in accord...

Page 10: ...60 C 10 Off Cycle Defrost Minimum Time 28 00 00 to 99 00 Min Sec 05 00 Off Cycle Defrost Maximum Time 29 00 00 to 99 00 Min Sec 24 00 Electric Defrost Max Temp 33 49 to 60 C 10 Electric Defrost Minimum Time 31 00 00 to 99 00 Min Sec 05 00 Electric Defrost Maximum Time 32 00 00 to 99 00 Min Sec 24 00 Defrost Start 26 00 00 to 23 59 Hrs Mins 01 00 Number of Defrosts per Day 27 0 to 6 6 No Defrost Ti...

Page 11: ...tric Defrost Heater is required connect to N O contact Case lights blinds Alarm wired to Relay 5 N C contact if bit switch 3 is ON ZA 10006 YAD Issue a 5 11 96 Product Part No Universal Controller 190797 YAD Warning Before you work on this equipment isolate the electrical supply and also the live feed to any incoming signals Remember that live signals may be derived from more than one source Featu...

Page 12: ...p 49 49 to 60 C 10 Section 3 Defrost Term Temp 52 49 to 60 C 10 Defrost Minimum Time 7 00 00 to 99 00 Min Sec 05 00 Defrost Maximum Time 8 00 00 to 99 00 Min Sec 24 00 25 00 Defrost Min Recovery Time 9 00 00 to 99 00 Min Sec 20 00 Defrost Max Recovery Time 10 00 00 to 99 00 Min Sec 30 00 Drain Down Time 11 00 00 to 20 00 Min Sec 01 30 Defrost Alarm Temp 12 49 to 60 C 20 Defrost Type 0 Elect 1 2 Ga...

Page 13: ... connect to N O contact Case lights blinds Alarm wired to Relay 5 N C contact if bit switch 3 is ON ZA 10053 YAD Issue a 5 11 96 Product Part No Universal Controller 190797 YAD Warning Before you work on this equipment isolate the electrical supply and also the live feed to any incoming signals Remember that live signals may be derived from more than one source Features Controls and monitors HT an...

Page 14: ... 10 Defrost Minimum Time 7 00 00 to 99 00 Min Sec 05 00 Defrost Maximum Time 8 00 00 to 99 00 Min Sec 24 00 25 00 Defrost Min Recovery Time 9 00 00 to 99 00 Min Sec 20 00 Defrost Max Recovery Time 10 00 00 to 99 00 Min Sec 30 00 Drain Down Time 11 00 00 to 20 00 Min Sec 01 30 Defrost Alarm Temp 12 49 to 60 C 20 Defrost Type 0 Elect 1 2 Gas 2 3 Gas 13 0 to 2 0 Defrost Mode 0 Local 1 Remote 14 0 to ...