Commissioning:
1. Check all electrical connections (Fig. 2).
2. Make sure that the controller software is
YAD.
3. Check / Set Bit Switches (Fig. 1).
4. Switch the controller ON.
5. Connect Set-up Unit to DIN Box Display
or controller (Fig. 2).
6. Check / Set operating parameters - see
list
7. Save values - if changed
8. Log the controller on to the network then
verify settings on Genus InTouch panel,
Set-up Unit or DIN Box Display.
9. Faults ?..........See ‘Fault Finding’.
Fault Finding:
Set-up Unit does not reach the first
screen.
•
If the red LED beside the display
connector is ON or flashing, then the
controller is faulty.
You cannot log the controller on to
the network.
•
There may be a controller with the same
name, already logged on the network.
•
There may be a maximum 32 controllers
already on the network segment.
•
Check on the InTouch panel, P.C. or
Supervisor.
Parameter
DIN
Range/Units
Default
Setting
Dsg
n.
Act.
Red Cycle Temperature
0
1 to 7 / °C
4
Red OT Alarm Temp.
2
7 to 10 / °C
8
Red UT Alarm Temp.
1
-3 to 4 / °C
2
Defrost Type:0=Elect.;1=Off Cyc.
3
0 to 1
0
Yellow Cycle Temperature
4
-1 to 4 / °C
1
Yellow OT Alarm Temp.
6
4 to 7 / °C
5
Yellow UT Alarm Temp.
5
-6 to 1 / °C
-1
Defrost Type:0=Elect.;1=Off Cyc.
7
0 to 1
0
White Cycle Temperature
8
4 to 12 / °C
8
White OT Alarm Temp.
10
11 to 14 / °C
12
White UT Alarm Temp.
9
1 to 6 / °C
4
Defrost Type:0=Elect.;1=Off Cyc.
11
0 to 1
1
Red Log OT Alarm
20
8 to 10 / °C
8
Red Log UT Alarm
19
-1 to 4 / °C
2
Yellow Log OT Alarm
22
5 to 7 / °C
5
Yellow Log UT Alarm
21
-2 to 1 / °C
0
White Log OT Alarm
24
12 to 14 / °C
12
White Log UT Alarm
23
3 to 7 / °C
4
Lead Cyc. Diff
12
0 to 30 / °C
1.5
Lag. Cut In
13
0 to 3 / °C
1
Lag Cut Out
14
0 to 3 / °C
1
Case Type: 0=Red ; 1=Yellow ;
2=White
16
0 to 2
0
Control Weight
15
0 to 100 / %
50
Display Weight
16
0 to 100 / %
50
Log Probe Type: 0=Off ;
1=Product ; 2=Alarm ;
3=Prod./Alarm
18
0 to 3
0
Off Cycle Defrost Max.Temp.
30
-49 to 60 / °C
10
Off Cycle Defrost Minimum Time
28
00:00 to 99:00/Min:Sec
05:00
Off Cycle Defrost Maximum Time
29
00:00 to 99:00/Min:Sec
24:00
Electric Defrost Max. Temp.
33
-49 to 60 / °C
10
Electric Defrost Minimum Time
31
00:00 to 99:00/Min:Sec
05:00
Electric Defrost Maximum Time
32
00:00 to 99:00/Min:Sec
24:00
Defrost Start
26
00:00 to 23:59/Hrs:Mins
01:00
Number of Defrosts per Day
27
0 to 6
6
No Defrost Time
41
0 to 25/ Hrs.
7
Alarm Delay
Fixed / Min:Sec
05:00
Drain Down Time
34
00:00 to 03:00/Min:Sec
01:30
Defrost Min. Recovery Time
35
00:00 to 35:00/Min:Sec
20:00
Defrost Max. Recovery Time
36
15:00 to 35:00/Min:Sec
30:00
Defrost Alarm Temp.
37
-49 to 60 / °C
20
Defrost Mode: 0=Local ;
1=Remote
38
0 to 1
0
Defrost Hold: 0=Off ; 1=On
40
0 to 1
0
Pulse Defrost: 0=Off ; 1=On
39
0 to 1
0
Hour
42
0 to 23
Minute
43
0 to 59
Day
44
0 to 31
Month
45
0 to 12
Year
46
0 to 99
BST / GMT Select: 0=Auto ;
1=Man.Off ; 2=Man.On
47
0 to 2
0
Lights/Blind: 0=Local ; 1=Remote
; 2=Man.Off ; 3=Man.On
48
0 to 3
0
Polarity: 0=N/O ; 1=N/C
49
0 to 1
0
Latch Alarm: 0=Off ; 1=On
25
0 to 1
0
Sunday (Blinds) Up / Down
50/51
00:00 to 23:59/Hrs:Mins
08:00/20:00
Monday (Blinds) Up / Down
52/53
00:00 to 23:59/Hrs:Mins
08:00/20:00
Tuesday (Blinds) Up / Down
54/55
00:00 to 23:59/Hrs:Mins
08:00/20:00
Wednesday (Blinds) Up / Down
56/57
00:00 to 23:59/Hrs:Mins
08:00/20:00
Thursday (Blinds) Up / Down
58/59
00:00 to 23:59/Hrs:Mins
08:00/20:00
Friday (Blinds) Up / Down
60/61
00:00 to 23:59/Hrs:Mins
08:00/20:00
Saturday (Blinds) Up / Down
62/63
00:00 to 23:59/Hrs:Mins
08:00/20:00
Gas Alarm: 0=Off ; 1=On
64
0 to 1
0
Minor Leak
65
0 to 3500 / ppm.
50
Major Leak
66
0 to 3500 / ppm.
200
Manual Defrost: 0=Off ; 1=On
99
0 to 1
0
YAD08d / 65EAEE
Display Alarm Messages:
AL
Temperature alarm
Ft
Probes 1 and 2 are faulty
LA
Log probe alarm
Pn
probe ‘n’ faulty or not connected
(Where ‘n’ = probe number)
EE
EEPROM fault
rr
Internal program fault
E1
Plant fault 1
E2
Plant fault 2
ES
Energy-Saving Mode
Store:............................................
Controller
Name:
Designer:.....................................
Date:............................................
Engineer:......................................
Date:.............................................
Comments:
Universal Controller -
Dyadic
ZA-10005-YAD
Issue a : 5/11/96