background image

69-1136—1

2

208414, 208415 REPLACEMENT POWER SUPPLY KIT FOR ELECTRONIC AIR CLEANER

Remove and discard W8600E terminal block and
wiring. Set aside screws for future use.

Remove and set aside the sheetmetal screws holding
the board in place.

Discard the old power supply.

Disconnect the leads from 1, 2, 3, 4, P1, P2, P3, P4,
P5, P12, P14, P17, P18 and P21 on the old power
supply. See Fig. 2 through 5.

Fig. 1. Remove cover from power box.

M5764

POWER 
SUPPLY

M5676A

3

1

2

REMOVING COVER
FROM POWER BOX.

Fig. 2. Power supply location on F50F and F58F.

Plug the electronic air cleaner directly into the correct
voltage and frequency outlet or reconnect power for
directly wired devices. See Fig. 3 or 4 for internal
schematic. The air cleaner will operate properly at any
fan speed on a multispeed or modulated speed
system wired with conduit or plugged in.

NOTE:

To reduce the risk of electric shock, this product
has a grounding type plug that has a third
(grounding) pin. This plug will only fit into a
grounding type power outlet. If the plug does not
fit into the outlet, contact a qualified electrician to
install the proper outlet. Do 

not change the plug

in any way.

CHECKOUT

CAUTION

The following instructions are for use by qualified
personnel only.

With all components in place, turn on the air cleaner switch
and energize the system blower. Check the following
points of operation:

1. The neon light next to the on-off switch is on. If a

W8600E is part of the installation, check the wall
panel and make sure the ON LED is lit. The
W8600E CHECK LED will come on if there is a
problem with the high voltage power supply.

2. Turn off the system blower. The neon light should go

off after a few seconds. The neon light shows that
the air cleaner is energized and the high voltage
power supply is working properly.

3. Turn on the system blower. With the air cleaner

energized, push the test button. A snapping sound
indicates that the collector voltage is present on the
cell. The W8600E CHECK LED will come on when
the test button is held down.

4. With a multispeed blower, repeat steps 1 through 3

for each fan speed.

5. If operation is not as described, refer to the Trouble-

shooting and Service section.

Install New Power Supply

When replacing the power supply, reuse the remain-
ing leadwires in the air cleaner when removing the old
power supply.

Install W8600E terminal block and wiring supplied
with this kit using screws previously removed.

Align the mounting holes and mount the new power
supply in the air cleaner, using the sheetmetal screws
removed earlier. Orient the power supply so P1 and
P2 are toward the front (closest to the switch and
neon light).

Route the remaining leads so the P3 and P4 leads
are separate from the low voltage leads. Route all
high voltage leads around, rather than over, the power
supply board. Low voltage leads can go over the
power supply board.

Connect leads to the terminals on the new power supply.

IMPORTANT

Do not splice ionizer and collector leads. These
leads must be unbroken to avoid electrical shock
through the connector or tape covering the splice.

Summary of Contents for 208414

Page 1: ...se a hazard ous condition such as electrical shock 2 Check the ratings given in the instructions and on the product to make sure the product is suitable for your application 3 Installer must be a trained experienced service technician 4 After installation is complete check out product operation as provided in these instructions WARNING ELECTRIC SHOCK HAZARD SAFETY HAZARD CAN CAUSE ELECTRICAL SHOCK...

Page 2: ...t of the installation check the wall panel and make sure the ON LED is lit The W8600E CHECK LED will come on if there is a problem with the high voltage power supply 2 Turn off the system blower The neon light should go off after a few seconds The neon light shows that the air cleaner is energized and the high voltage power supply is working properly 3 Turn on the system blower With the air cleane...

Page 3: ... BOARD ORANGE GRAY VIOLET BLACK 1 INTERLOCK SWITCH 2 OUTPUT REDUCTION JUMPER 3 AIRFLOW SWITCH DISABLE JUMPER 4 RESISTOR FOR W8600 WASH INDICATION THRESHOLD PRESENT ON POWER SUPPLIES MANUFACTURED WITH DATE CODE 9430 AND EARLIER 5 ONE CELL UNIT SIMILAR BUT WITH JUST ONE CELL 6 P1 P2 TERMINALS ON 120V MODELS ONLY POWER CONNECTIONS ON 240V MODELS ARE TO QUICK CONNECTS ON POWER SUPPLY TRANSFORMER BROWN...

Page 4: ... INTERLOCK SWITCH 2 SHORTING BAR 3 AIRFLOW SWITCH DISABLE JUMPER 4 W8600E REMOTE PERFORMANCE INDICIATOR DRIVER 5 TOP TERMINAL ON TRANSFORMER 6 INPUT POWER PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED 7 NEON LIGHT M15098 2 7 BLACK RED TEST BUTTON CONTACT BOARD RED IONIZER BLACK COLLECTOR BLACK 4 BLACK BLACK BROWN BLACK BLACK WHITE GREEN 3 6 1 5 E5 E6 J5 J1 J1 J2 GREEN YELLOW RED BLU...

Page 5: ...OPERATION CAN BE CHECKED SEPARATELY SEE W8600E INSTRUCTIONS 2 3 M5609E FOLLOW THE STEPS IN ORDER DO NOT SKIP AROUND EACH TIME YOU ISOLATE AND FIX A PROBLEM GO BACK TO START REPEAT ALL THE STEPS UNTIL THE AIR CLEANER CHECKS OUT OK 1 2 3 1 THIS STEP EXPOSES DANGEROUSLY HIGH VOLTAGE ONLY A QUALIFIED SERVICE TECHNICIAN SHOULD ATTEMPT THIS STEP WARNING CHECK NEON LIGHT TURN OFF AIR CLEANER AND REMOVE C...

Page 6: ... ozone generated by the air cleaner can be reduced in one of two ways 1 Install an activated carbon filter downstream from the air cleaner Make sure particles from the air filter cannot fall into the air cleaner WARNING ELECTRIC SHOCK HAZARD CAN CAUSE PERSONAL INJURY Only a trained service technician should perform the following procedure 2 This will reduce ozone production about 20 to 25 percent ...

Page 7: ...l not apply if it is shown by Honeywell that the defect or malfunction was caused by damage that occurred while the product was in the possession of a consumer Honeywell sole responsibility shall be to repair or replace the product within the terms stated above HONEYWELL SHALL NOT BE LIABLE FOR ANY LOSS OR DAMAGE OF ANY KIND INCLUDING ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES RESULTING DIRECTLY OR I...

Page 8: ...TRONIC AIR CLEANER Home and Building Control Honeywell Limited Honeywell Limitée 155 Gordon Baker Road North York Ontario M2H 3N7 69 1136 1 J H Rev 11 97 Home and Building Control Honeywell Inc Honeywell Plaza P O Box 524 Minneapolis MN 55408 0524 Printed in Mexico ...

Reviews: