Installation Instructions
Basic Guidelines
Installation Instructions
Basic Guidelines
Follow these instructions to the letter to ensure that the equipment will
function properly. Failure to respect these guidelines will release
Honeywell Analytics from any responsibility in the event of improper
functioning:
•
Make sure to locate all transmitters in areas easily accessible for
service.
•
Avoid locations where instruments are subject to vibrations
•
Avoid locating transmitters near sources of electromagnetic
interference
•
Avoid locating transmitters in areas subject to significant
temperature swings
•
Transmitters should be installed 1.5 m (5 ft.) above the floor for CO
transmitters to prevent signal interference by vehicles ( NO
2
transmitters should be installed 30 cm [1 ft] from the ceiling.)
•
Install transmitters in upright position (to ensure ease of use and
access to programming pushbuttons).
•
Place transmitters so that they are facing the center of the area
•
Do not install a transmitter facing a parking space; the vehicle will
sever the communication link. If possible, install the transmitter
perpendicular to the space.
•
Avoid installing the transmitters on or near metal (transformers,
pipes, etc.)
•
Do not install transmitters on ceilings
•
Do not install transmitters in ceiling or wall wells (placement in
these areas may impede signal transmission)
Summary of Contents for 301W
Page 2: ......
Page 3: ...Wireless Gas Monitoring Device 301W Installation and User Manual ERP 511398 5 07 ...
Page 4: ......
Page 6: ......
Page 8: ......
Page 10: ......
Page 22: ......
Page 34: ......
Page 38: ......
Page 44: ......
Page 45: ...Dispositif de détection de gaz sans fils 301W Manuel de l utilisateur ERP 511398 5 07 ...
Page 46: ......
Page 48: ......
Page 50: ......
Page 52: ......
Page 64: ......
Page 72: ......
Page 86: ......