customer.honeywell.com

Table 5. Echelon Generic Cable Specification For Belden 85102 Equivalent, Stranded Twisted Pair 16 AWG (1.5 mm

2

).

Cable Termination

The FTT network segment requires termination for proper 
data transmission performance. Use a 209541B FTT 
termination module. Free topology (singly terminated) 
segments use the yellow and brown wires. Daisy-chain 
(doubly terminated) segments use the orange and brown 
wires. See Fig. 4.

Fig. 4. 209541B FTT termination module

.

Free Topology (Single Termination) 
Network Segment

In a free topology segment (singly terminated) only one 
termination is required and the termination can be placed 
anywhere on the free topology segment. See Fig. 1 and 5.

Fig. 5. Physical connection of module 

for a single termination network

.

Daisy-Chain (Double Termination) 
Network Segment

In a daisy-chain free topology segment (doubly terminated) 
two terminations are required, one at each end of the FTT 
daisy-chained network segment. See Fig. 6 and 7.

Fig. 6. FTT termination module wiring for 

double termination network topology

.

Fig. 7.  Physical connection of modules 

for a double termination network

.

L

ON

W

ORKS

®, Neuron®, L

ON

M

ARK

® and L

ON

M

ARK

® logo are 

registered trademarks of Echelon® Corporation.

Minimum

Typical

Maximum

Units

Condition

DC Resistance, each conductor

14.0

14.7

15.5

Ohms/km

20°C per ASTM D 4566

DC Resistance Unbalance

20°C per ASTM D 4566

Mutual Capacitance

per ASTM D 4566

Characteristic Impedance

92

100

108

Ohms

64 khz to 1 Mhz, per ASTM D 4566

Attenuation

20 khz

1.3

Db/km

20°C per ASTM D 4566

64 khz

1.9

78 khz

2.2

156 khz

3.0

256 khz

4.8

512 khz

8.1

772 khz

11.3

1000 khz

13.7

Propagation Delay

5.6

Nsec/m

78 khz

M12198

YELLOW

ORANGE

BROWN

M12200

YELLOW

ORANGE

L

ONWORKS

-BUS

BROWN

TERMINATION

MODULE

TERMINATION

MODULE

DEVICE

DEVICE

DEVICE

(DAISY CHAINED)

(DAISY CHAINED)

DEVICE

DEVICE

M12199

M12201

ORANGE

YELLOW

L

ONWORKS

-BUS

BROWN

ORANGE

YELLOW

L

ONWORKS

-BUS

BROWN

Summary of Contents for 3252

Page 1: ... topology architecture allows the user to wire the control devices with virtually no topology restrictions Unlike bus wiring designs the FTT system uses a free topology wiring scheme that supports T tap star loop mixed and or daisy chain see Fig 1 This design has many advantages First the installer is free to select the method of wiring that best suits the installation reducing the need for advanc...

Page 2: ...rk traffic may benefit from the use of a Q7751A router which forwards packets only when necessary Routers are not allowed within loops Fig 2 Repeaters and router in a FTT network Fig 3 Physical layer repeater Q7740A 2 Way or Q7750B 4 Way NETWORK CABLING AND CONNECTIONS This section provides information about cabling and FTT network connections IMPORTANT For network terminal connections twist the w...

Page 3: ... twisted pair 49 67 22 34 mm2 106 4600 feet 1400 m TIA568A Category 5 24 AWG twisted pair solid or stranded plenum or non plenum 46 58 24 27 mm2 168 3000 feet 900 m Wire Cable type Unshielded Maximum Length for Segment s Node to Node FTT Network Bus Honeywell Cable 1125 stranded non plenum 1640 feet 500 m 1640 feet 500 m Belden 85102 stranded non plenum 1640 feet 500 m 1640 feet 500 m Belden 8471 ...

Page 4: ...t See Fig 1 and 5 Fig 5 Physical connection of module for a single termination network Daisy Chain Double Termination Network Segment In a daisy chain free topology segment doubly terminated two terminations are required one at each end of the FTT daisy chained network segment See Fig 6 and 7 Fig 6 FTT termination module wiring for double termination network topology Fig 7 Physical connection of m...