Precision Platform 4022 Scanner
Scanner Maintenance
i
N
OTE
:
Sensors may take an hour to stabilize before
calibration can be performed.
6.
To increase the head temperature, turn the trim heater knob
clockwise one number at a time. To decrease the temperature, turn
it counterclockwise.
Figure 9-13 shows the locations on the ECU for adjusting the head
temperatures.
Figure 9-13 ECU and Temperature Controls
9.9.4.4.
Sheet guide heaters
The sheet guide heaters are mounted on the sheet guides under the sensor
platform. They prevent condensation from forming on the sensor
10/18/07
p/n:
6510020208
9-50