4-27
CHAPTER 4 - INSTAllATION INSTRUCTIONS
MAN0448_Issue 13_01-2010
5704 Control System
005704-M-5001 A03249
Notes: 1. Where the sensor is earthed locally, either to the stud or through
the sensor casing or mounting, to avoid earth loops the screen
sheath should only be connected at one end, i.e. the sensor
or at the relay/interface card.
2. The above diagram shows the sensor connections for
Channel 1. Channels 2, 3 and 4 connections are similar and
their pin connection numbers are shown below:
Channel
Transmitter Connection
S
01
Quad Relay
1
15
17
Interface Connections
2
16
18
3
21
23
4
22
24
Four Wire Isolated Signal Input, Transmitter Connection for
Opus/lifeline II
S
01
Screened
Cable
Quad Relay Interface Card
05704-A-0121
15
17
Cabinet
Protective
Earth
+24V*
0V*
Opus/Lifeline II Transmitter
* 24V supply may be obtained
from either the cabinet or a
separate field supply
Arrows Indicate
Direction of Loop
Current Flow
5
6
Screen to
cable gland
1
3
J4
J5