Model 6820 / 6820-EVS Installation Manual
LS10144-001SK-E
10-13
systems). Auto Display Event activates after two minutes of annunciator inactivity.
Figure 10-7 Highest Priority Event Display
Figure 10-8 Event Display after Two Minutes Sitting idle
Table 10-2: Operation Mode Behavior
Operation
Mode
Occurs
When
System Behavior
In This Mode You Can
Normal
No alarm or
trouble
condition
exists and
menus are not
in use.
SYSTEM POWER LED is on.
The All Systems Normal display indicates that
the system is in normal mode.
The current date and time display on the last
line of the LCD.
Enter the appropriate code to activate the User or
Installer Menu, or rotate the key to activate the User
Menu.
Alarm
A smoke
detector goes
into alarm or a
pull station is
activated. EVS
LOC or point
alarm
CO Detector
goes into
Alarm.
If more than 3
categories are
active at a
single time.
The communicator seizes control of the phone
line and calls the central station.
The on-board annunciator sounds a loud,
steady beep (any notification devices attached
to the system will also sound).
GENERAL ALARM LED flashes.
The LCD displays a screen similar to this one.
Press the down arrow to view the alarm. A screen
similar to this one displays.
Press SILENCE and enter an access code (or
activate the key) to silence the annunciator (and any
notification devices attached to the system).
When the alarm condition clears, press RESET and
enter a code (or activate the key) to restore the panel
to normal.
site
panel#
module#