Model 6820 / 6820-EVS Installation Manual
LS10144-001SK-E
12-13
12.2 SIA / Panels PI Modifier Reporting:
Events are sent to the central station as a variable length string:
The event format is:
EEZZZZ
Where:
EE Event code (2 characters)
ZZZZ Event parameter (up to four digits – not zero filled)
1.
The account number is sent using an account block that is separate from the event block
2.
Multiple events can be sent within a single event block. Events are separated by a “/” character.
3.
Event parameter can be either a zone, point or module number.
Zone-based AUX1 switch en-
abled
pi Exp. ID UU
Point #
UUNNXXPPPP
3
571
Exp. ID
Point #
Zone-based AUX1 switch trouble
pi Exp. ID UT
Point #
UTNNXXPPPP
1
373
Exp. ID
Point #
Zone-based AUX1 switch trouble
restore
pi Exp. ID UJ
Point #
UJNNXXPPPP
3
373
Exp. ID
Point #
Zone-based AUX2 switch alarm
pi Exp. ID UA
Point #
UANNXXPPPP
1
140
Exp. ID
Point #
Zone-based AUX2 switch alarm
restore
pi Exp. ID UH
Point #
UHNNXXPPPP
3
140
Exp. ID
Point #
Zone-based AUX2 switch dis-
abled
pi Exp. ID UB
Point #
UBNNXXPPPP
1
571
Exp. ID
Point #
Zone-based AUX2 switch en-
abled
pi Exp. ID UU
Point #
UUNNXXPPPP
3
571
Exp. ID
Point #
Zone-based AUX2 switch trouble
pi Exp. ID UT
Point #
UTNNXXPPPP
1
373
Exp. ID
Point #
Zone-based AUX2 switch trouble
restore
pi Exp. ID UJ
Point #
UJNNXXPPPP
3
373
Exp. ID
Point #
System-based Wireless Gateway
Trouble
pi Exp. ID UT
Point #
UTNNXXPPPP
1
373
Exp. ID
Point #
System-based Wireless Gateway
Trouble - restore
pi Exp. ID UJ
Point #
UJNNXXPPPP
3
373
Exp. ID
Point #
Wireless Gateway Trouble
pi Exp. ID UT
Point #
UTNNXXPPPP
1
373
Exp. ID
Point #
Wireless Gateway Trouble re-
store
pi Exp. ID UJ
Point #
UJNNXXPPPP
3
373
Exp. ID
Point #
Table 12-2: Reporting Formats Table
SIA Reporting Format
Contact ID Reporting Format
SIA pi Modifier
SIA
Event Description
Module
ID # (If
Any)
SIA
Event
Codes
Parameter Fixed Length
Format NN -
panel ID
XX- SBUS ID
ZZZ- Zone #
PPPP- Point #
GGG- Group #
E- Emergency #
RRRR-Receiver #
Qualifier
Event
Code
Group #