Model 6820 / 6820-EVS Installation Manual
LS10144-001SK-E
4-1
Section 4
Control Panel Installation
4.1
Mounting the Control Panel Cabinet
The 6820 cabinet can be surface or flush-mounted. Cabinet base dimensions are 14.5" W x 24.75" H. There
should be 1.5" to 1.75" of cabinet extruding from the wall, this should be measured from either the top edge or
bottom edge to the exterior side of the sheet rock. Do NOT flush mount in a wall designated as a fire break.
The 6820EVS cabinet can be surface or flush mounted. Cabinet overall dimensions are 21.592" W x 28.12" H. If
you flush mount the cabinet, the backbox dimensions are 20"W x 26.5"H x 4.1"D There should be 1.5" to 1.75"
of cabinet extruding from the wall, this should be measured from either the top edge or bottom edge to the
exterior side of the sheet rock. Do NOT flush mount in a wall designated as a fire break.
Figure 4-1 FACP Cabinet Base
4.1.1
Preventing Water Damage
Water damage to the fire system can be caused by moisture entering the cabinet through the conduits. Conduits
that are installed to enter the top of the cabinet are most likely to cause water problems. Installers should take
reasonable precautions to prevent water from entering the cabinet. Water damage is not covered under warranty.
4.1.2
Removing the 6820 / 6820EVS Assembly from the Housing
If it should ever be necessary to remove the control panel assembly from the cabinet for repair, do so by
unscrewing the nuts that connect the control panel assembly to the cabinet. Do not attempt to disassemble the
circuit boards. See Section 3.7 for location of the nuts.
6820
6820EVS
14.50"
20"
26.5"
24.75"