Model 6820 / 6820-EVS Installation Manual
LS10144-001SK-E
4-21
4.7.2
6860 Connection to the Panel
Connect the 6860 to the panel as shown in Figure 4-28.
Figure 4-28 Model 6860 Connection to the Panel
4.8
5815XL Installation
The 5815XL SLC expander lets you add 127 SD addressable devices The maximum number of SLC SD devices
per panel is 635. The number of 5815XL’s is limited by the maximum number of SBUS devices.
Note: 5815XL will only support SD SLC devices.
To install the 5815XL:
1.
Make sure power is off at the panel.
2.
Mount the 5815XL in the 6820 cabinet, the 5895XL cabinet, or the 5815RMK remote mounting kit. Use the
standoffs located under the control panel board assembly and secure with screws provided with the 5815XL.
For additional information, also see
Model 5895XL Installation Instructions
(P/N 151142) or
5815RMK
Remote Mounting Kit Installation Instructions
(P/N 151391).
3.
Connect the 5815XL to the control panel. (See Section 4.8.1.)
4.
Use on-board DIP switches to select an SBUS ID#. (See Section 4.13.1).
5.
The new 5815XL module must be added to the system through programming. JumpStart will add the mod-
ule automatically (see Section 8.1). You can also add it manually (see Section 9.2.2). Select a name, if
desired (see Section 9.3.1.1).
6.
You are now ready to connect SLC devices to the 5815XL (see Section 9.5.1).
Supervised
Power Limited