LS10144-001SK-E
Programming
9-16
10. Repeat steps 1 through 9 for all circuits.
Table 9-5: Menu choices for Internal/External Power Module
Choices
Type Selections
Function
Selections for
each Type
Comments
Enter Point
Select Type
UNUSED
B NOTIF
NOTIF Output
Control Circuit
A NOTIF
AUX_PWR
CONSTANT
Constant auxiliary power.
AUX RESET
Resettable auxiliary power.
AUX DOOR
Door holder auxiliary power.
Aux SYNC
Aux Power for System Sensor
B SWITCH
MANUAL PULL
Refer to comments column of
Table 9-3 for description of these options.
Latch or Non-latching feature only appears for
WATERFLOW, FIRE SUPERVISORY, FIRE
TAMPER, ZONE AUX1, ZONE AUX2, SYSTEM
AUX1, SYSTEM AUX2, EVS INPUT, EVS TAMPER,
and EVS SUPERVISORY.
WATERFLOW
FIRE SUPERVISORY
FIRE TAMPER
FIRE DRILL
SILENCE
RESET
P.A.S. ACK
ZONE AUX1
ZONE AUX2
SYSTEM AUX1
SYSTEM AUX2
MANUAL RELEASE
INTERLOCK
STATUS POINT
EVS INPUT
User also has EVS Event Number 1-8 option for
EVS INPUT. Only available when an EVS-VCM is
installed in the system.
EVS TAMPER
EVS SUPERVISORY
A SWITCH
Same as B SWITCH
B DETECT
2-WIRE SMOKE
Used for Class B, 2-wire detectors.
4-WIRE SMOKE
Used for Class B, 4-wire detectors.
CO 4-WIRE DET
Used for Class B, 4-wire CO detectors.
CO 4-WIRE SUP DET
Latching or Non-latching used for Class B, 4-wire
CO Supervisory detectors
A DETECT
2-WIRE SMOKE
Used for Class A, 2-wire detectors.
4-WIRE SMOKE
Used for Class A, 4-wire detectors.
CO 4-WIRE DET
Used for Class A, 4-wire CO detectors.
CO 4-WIRE SUP DET
Latching or Non-latching used for Class A, 4-wire
CO Supervisory detectors