20 Installation Instructions ACC 50
3.2 Line
lengths/types
For connecting external components, please use the following line types. Also pay attention to the
maximum line length.
Door monitoring contact
40m
J-Y(St)Y 2x2x0,6
Door strike key
40m
J-Y(St)Y 2x0,6
Alarm relay output
40m
J-Y(St)Y 2x0,6
Timer
40m
J-Y(St)Y 2x0,6
Printer
5m
LifYCY 5x2x0,6
2
Voltage supply
Calculation
H03VV-F 2x1.5mm
3.3
Fixation of ACC 50
The fixing boreholes of the ACC 50 are designed so that for installation either a flush-mounted box or
cavity wall installation box (60mm) can be used. The device can also be installed directly above an
empty pipe output (see drawing next page), taking into consideration that the reserve cable is either in
the installation box or in the junction socket.