ACUIX IP Rugged Housing and Dome Installation Guide
Document 800-02460 Rev A
17
08/08
Step 2: Set Switches on the Scan Assembly Circuit Board
About the SW5 and SW6 DIP Switch Settings
The scan assembly printed circuit board (PCB) has DIP switches SW5 and SW6 that
require setting as detailed in
so that the ACUIX IP dome works correctly. Switch
SW5 sets the protocol to IntelliBus and switch SW6 sets the baud rate to 38400 (positions
1 to 4) and No Parity (positions 5 and 6).
Setting DIP Switches SW5 and SW6
•
Set the DIP switches on the scan assembly printed circuit board as required for your
system configuration. Use
and
to help set it correctly.
.
Leave SW5-8
ON
. Setting the DIP switch SW5-8 to
OFF
enables a user to change the
address, protocol, baud rate and parity from the OSD menu (which is not recommended
with most installations).
Table 1-6
ACUIX IP DIP Switch Settings (SW5 and SW6)
Switch Position
1
2
3
4
5
6
7
8
SW5 - Set for IntelliBus Protocol
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
SW6 - Set Baud Rate to 38400 and No Parity
OFF
ON
ON
OFF
OFF
OFF
OFF
OFF