LXL-1010 Installation and Setup Guide
5–2
PROMPT
VALID ENTRIES
EXPLANATION
10 Zone Type
Perimeter 03
Zone Type (ZT)
00-24, 90, 91 = zone type (see
table at right)
Each zone must be assigned to a zone type, which defines the way in
which the system responds to faults in that zone.
Enter the Zone Type code from the list below:
Note:
If 00 is entered,
Delete Zone ?
will be displayed.
00 = Not used
07 = 24-Hr Audible
20 = Arm–STAY*
01 = Entry/exit #1
08 = 24-Hr Aux
21 = Arm–AWAY*
02 = Entry/exit #2
09 = Fire
22 = Disarm*
03 = Perimeter
10 = Interior w/Delay 23 = No Alarm Resp*
04 = Interior Follower
12 = Monitor Zone
24 = Silent Burglary
05 = Trouble Day/Alarm Night 14 = Carbon Monoxide
06 = 24-Hr Silent
81 = AAV Monitor Zone
*5800 button-type transmitters only
90-91 = Configurable
10 Report Code
1st 01 2nd 00 10
Report Code (RC)
First Digit:
00 to disable
Second Digit: same as above
[
∗
] to continue
Enter the report code for this zone, which consists of 2 hexadecimal digits,
each in turn consisting of 2 numerical digits. For example, for a report code
of “10,” enter 01 and 00.
For Contact ID
®
, entering any non-zero entry as the first digit enables the
report code for this zone. Refer to the
System Communication
section for
information about report codes and formats.
10 INPUT TYPE
RF TRANS
3
Input Device type (In)
3 = RF (supervised RF
transmitter,
4 = UR (unsupervised RF
transmitter)
5 = Button type RF
transmitter
(unsupervised).
[
∗
] to continue
All of the RF transmitters have one or more unique factory-assigned
input (loop) ID codes. Each of the inputs requires its own
programming zone
(e.g., a 5804's four inputs require four
programming zones).
RF Transmitters can be enrolled as one of the following types:
Type Description
“RF”
Sends periodic check-in signals, as well as
(Supervised RF)
fault, restore, and low-battery signals. The
transmitter must stay within receiver's range.
“UR”
Sends all the signals that the “RF” type
(Unsupervised RF)
does, but the control does not supervise the
check-in signals. The transmitter may therefore
be carried off-premises.
“BR”
(Unsupervised Sends only fault signals. It will not send a
Button RF)
low-battery signal until it is activated. The
transmitter may be carried off-premises.
10 INPUT S/N: L
A 0 2 2 - 4 0 6 4 1
Serial number Entry
and Loop Number Entry
see explanation
[
∗
] to continue
a. Transmit two open/close sequences. If using a button-type
transmitter, press and release the button twice, but wait about 4
seconds before pressing the button the second time.
OR
b. Manually enter the 7-digit serial number printed on the label of
the transmitter. Then press the [Q] key – the cursor will move to
the “L” position. You can edit the loop number, if necessary. When
the loop number is acceptable, press [Q].
c. Press key [C] to copy the serial number previously enrolled (used
when programming a transmitter with several input loops).
10 INPUT S/N L
A 0 2 2 - 4 0 6 4 ?
Loop Number Change
[
∗
] to continue
NOTE:
If the [C] key is used to copy the previously enrolled serial
number, the cursor will move to the Loop column (L) with the
previous serial number displayed, and display a highlighted question
mark for the loop number.
Enter the loop number and press [
✱
]. The system will now check for
a duplicate serial/loop number combination.
10 INPUT S/N L
A 0 2 2 - 4 0 6 4 1
Enroll Summary
[
∗
] to continue
If the serial/loop number combination is not a duplicate in the
system, a display showing the serial number and loop number entry
will appear.
www.PDF-Zoo.com
firealarmresources.com
Summary of Contents for ADEMCO LYNX XL Series
Page 8: ...LXL 1010 Installation and Setup Guide 1 4 www PDF Zoo com firealarmresources com ...
Page 18: ...LXL 1010 Installation and Setup Guide 2 10 www PDF Zoo com firealarmresources com ...
Page 44: ...LXL 1010 Installation and Setup Guide 6 2 www PDF Zoo com firealarmresources com ...
Page 50: ...LXL 1010 Installation and Setup Guide 8 2 www PDF Zoo com firealarmresources com ...
Page 60: ...LXL 1010 Installation and Setup Guide 11 4 www PDF Zoo com firealarmresources com ...
Page 66: ...LXL 1010 Installation and Setup Guide 12 6 www PDF Zoo com firealarmresources com ...
Page 70: ...LXL 1010 Installation and Setup Guide 13 4 www PDF Zoo com firealarmresources com ...
Page 74: ...LXL 1010 Installation and Setup Guide 14 4 www PDF Zoo com firealarmresources com ...