background image

LYNXR-ISIA Installation and Setup Guide

 

  

- 67 - 

Programming Default Tables 

56 ZONE ASSIGNMENT/ALARM REPORT CODES FOR TABLES 3 & 4 

Zone No.  Zone Type  Alarm Code 

Input Type  

Loop Number 

Zone Descriptor 

1,0 

3 (RF) 

47, 04 (FRONT DOOR) 

1,0 

3 (RF) 

33, 04 (BACK DOOR) 

1,0 

3 (RF) 

80 (WINDOW) 

1,0 

3 (RF) 

80 (WINDOW) 

1,0 

3 (RF) 

80 (WINDOW) 

1,0 

3 (RF) 

80 (WINDOW) 

10 

1,0 

3 (RF) 

56 (MOTION DETECTOR) 

1,0 

3 (RF) 

22, 02 (SMOKE DETECTOR) 

26 21  1,0 5 

(BR) 

 

27 22  1,0 5 

(BR) 

 

28 23  0,0 5 

(BR) 

 

29 23  0,0 5 

(BR) 

 

30 21  1,0 5 

(BR) 

 

31 22  1,0 5 

(BR) 

 

32 23  0,0 5 

(BR) 

 

33 23  0,0 5 

(BR) 

 

92 ---  ---  --- 

--- 

 

99 6  1,0  --- 

--- 

 

NOTE: Zone 2 to 41 are RF zones; Zone 92 is Duress; Zone 99 is keypad panic 

 

 

80 DEFAULT TABLE: APPLIES TO DEFAULT TABLE 4 (devices 2-7 have no default values) 

  

 

Start

   

Stop 

 

Device Number 

 

Action 

 

Event 

 

Zone List 

Zone Type 

System Operation 

Restore of  

Zone List 

Zone type  

System operation 

1 2 

1  

2   

8** 2 

 

  33 

  36 

** 

NOTE: 

If using an X10 Powerhouse Security SH10A siren as device 8, you must change the device action default to “3” if using default  

table  4. 

 
 

80 DEFAULT TABLE: APPLIES TO DEFAULT TABLE 1 and 2 (devices 1-7 have no default values) 

  

 

Start

   

Stop 

 

Device Number 

 

Action 

 

Event 

 

Zone List 

Zone Type 

System Operation 

Restore of  

Zone List 

Zone type  

System operation 

8** 2 

 

  33 

  36 

 
 

81 ZONE LIST FOR OUTPUT DEVICES DEFAULT TABLE: Applies To Default Table 1 - 4. 

Zone List 1 28, 32 
Zone List 2 29, 33 
Zone List 3 2, 3 

Summary of Contents for ADEMCO LYNXR-ISIA

Page 1: ...rity Systems Installation and Setup Guide AWAY OFF STAY AUX LIGHTS ON RECORD LIGHTS OFF STATUS TEST VOLUME CODE NO DELAY BYPASS PLAY CHIME FUNCTION DELETE ESCAPE ADD SELECT ARMED READY 4 5 6 7 8 9 0 1 2 3 K14114 2 1 07 Rev A ...

Page 2: ...the hallway outside may not wake up the sleeper if the door is closed Install a smoke detector inside bedrooms where electrical appliances such as portable heaters air conditioners or humidifiers are used Install a smoke detector at both ends of a hallway if the hallway is more than 40 feet 12 meters long Install smoke detectors in any room where an alarm control is located or in any room where al...

Page 3: ...6 81 ZONE LIST MENU MODE 39 83 ENHANCED SEQUENTIAL MODE 41 84 ASSIGN ZONE VOICE DESCRIPTORS 44 85 RECORD CUSTOM VOICE DESCRIPTORS 46 VOICE PROMPT PROGRAMMING 47 REMOTE PROGRAMMING CONTROL DOWNLOADING 51 SYSTEM OPERATION 53 TESTING THE SYSTEM 59 SYSTEM COMMUNICATION 60 TROUBLESHOOTING GUIDE 62 PROGRAMMING DEFAULT TABLES 65 REGULATORY AGENCY STATEMENTS 68 SPECIFICATIONS 69 CONTACTING TECHNICAL SUPPO...

Page 4: ... 30mA max Bell output 120mA max Steady output for burglary panic Temporal pulse output for fire alarms Long Range Radio Audio alarm verification PROGRAMMING Options stored in EEROM Can be uploaded downloaded or controlled via IBM compatible computer using Compass downloader software and specified HAYES modem Voice Prompt programming mode COMMUNICATION Ademco Low Speed Sescoa Radionics Ademco Expre...

Page 5: ...e back plate to a sturdy wall feeding the field wiring through the appropriate openings in the back plate 5 After wiring connections are made carefully reconnect the ribbon cable to the front assembly PC board connector properly aligning the red wire 6 Snap the front assembly to the back plate so it is secured by the locking tabs LOCKING TABS LOCKING TABS LOCKING TABS RED WIRE MARKING DISCONNECT T...

Page 6: ...ALL OUTPUT CIRCUITS ARE POWER LIMITED PREMISES TELEPHONE 1 2 3 4 8 6 5 11 7 10 12 15 16 13 14 PHONE FUTURE USE FUTURE USE SOUNDERS PLCD AC EARTH GROUND EARTH GROUND INCOMING TELEPHONE LINE RING TIP RING TIP PIEZO 6 14VDC 120mA max e g WAVE2EX 6 14VDC 30mA max DATA OUT SYNC IN POWERLINE CARRIER DEVICES RJ11 8 POS JACK AC AC SYNC COM DATA 9 BELL 09003 009 V0 NOTE USE ONLY THE K10145X10 TRANSFORMERS ...

Page 7: ...res to RJ31X terminals 1 grey and 8 brown respectively e Wire the flying leads of a Direct Connect Cord to the control s phone terminals as shown in the diagram or plug into the 8 position jack f Plug the Direct Connect Cord into the RJ31X jack RJ31X 1 2 3 4 5 6 7 8 RING TIP INCOMING PHONE LINE TO PREMISES PHONES TIP RING TIP RING BROWN GREY RED GREEN INCOMING PHONE LINE TO PREMISES PHONES GREEN R...

Page 8: ...the Installation Instructions for device that you are installing for additional information The wire run between the LYNXR ISIA and the Communications Device must not exceed ten 10 feet U U U UL L L L The 7845ENT and 7845CV2 have been evaluated by UL for Household Burglary installations The communications modules have not been evaluated for Household Fire installations AlarmNet 7845i L Communicati...

Page 9: ...anet LAN via the appropriate Ethernet connection if applicable 7845GSM 7845i GSM LYNX SUPER HIGH CAPACITY BATTERY OPTIONAL REQUIRED FOR 24 HR BACKUP 7845i GSM 010 V0 GND Z3 OR DATA OUT Z1 Z2 OR DATA IN ECP VOLTAGE INPUT RED BLK GRN YEL RED BLK GRN YEL 4 5 6 3 5 4 4 WIRE CABLE N4632 4 1 2 TB1 LRR IP COMMUNICATIONS PORT LYNXR I CONTROL PANEL NC 12 VDC GND DATA IN DATA OUT LYNX STANDARD CAPACITY BATT...

Page 10: ...FLT DATA OUT P1 BAT LYNXR I CONTROL PANEL RED NC BLK GRN YEL RED BLK GRN YEL 12 VDC GND DATA IN DATA OUT 4 WIRE CABLE N4632 4 LYNX STANDARD CAPACITY BATTERY Connecting AlarmNet 7845CV2 Configuring Long Range Radio and Internet Communication Devices 1 Enable the communications device in programming field 55 and configure alarm reporting and module supervision in programming field 77 2 Program the d...

Page 11: ...y message is displayed and a report is sent to the central station In addition the system will beep once every 45 seconds to audibly indicate a low battery condition press any key to stop the beeping AC Power and Rechargeable Backup Battery Connecting AC Power and backup battery 1 Connect wires from the K10145X10 AC Transformer to terminals 15 and 16 as shown in the wiring diagram 2 Remove battery...

Page 12: ...ect the battery pack connector from the receptacle on the terminal block PC board 3 Remove the battery pack from the back plate 4 If required replace the tape that secures the battery pack 5 Install a replacement battery pack P N LYNXRCHKIT SC LYNXRCHKIT HC or LYNXRCHKIT SHA into the back plate 6 Install the battery retainer 7 Connect the battery connector to the receptacle on the terminal block P...

Page 13: ...for some transmitters keypads that may be carried off premises 5804 5804BD 5804BDV and 5804E each transmitter is supervised by a check in signal that is sent to the receiver at 70 90 minute intervals If at least one check in is not received from each supervised transmitter within a 12 hour period the missing transmitter number s and FAULT will be displayed The supervision for a particular transmit...

Page 14: ...ave a two second delay on the special function keys or two button panic pairs built in keypad s two button panic pairs Go No Go Test Mode 5804E encrypted High Security devices must be activated while the system is in Go No Go Test Mode Refer to the transmitter s installation instructions for complete details The system will confirm enrollment of the encrypted device by beeping two times The Go No ...

Page 15: ...ellow AR ME D RE AD Y MESSAGE MIC Notes 1 Loop 4 must be enrolled on the 5801 5804 5804BD 5804BDV and 5804E transmitters whether or not the loop is used 2 5804E encrypted High Security devices must be activated while the system is in Go No Go Test Mode Refer to the transmitter s installation instructions for complete details The system will confirm enrollment of the encrypted device by beeping two...

Page 16: ...amming Mode 1 Press both the and keys at the same time within 50 seconds after power is applied to the Control or from exiting Programming mode OR 2 After power up enter the Installer Code 4112 800 to enter Expert Programming mode This method disabled if Program mode is exited using 98 OR enter Installer Code 4112 888 to enter Voice Prompt Programming mode If a different Installer Code has been pr...

Page 17: ...e selected 96 resets all subscriber account numbers and CSID in preparation for an initial download Exiting Program Mode 98 inhibits re entry into the Expert or Voice Prompt Programming modes using the Installer Code 99 allows re entry into the Expert Program mode using Installer Code 4112 800 or into the Voice Prompt Programming mode using Installer Code 4112 888 Note After exiting program mode o...

Page 18: ...NO DELAY mode Type 04 Interior Follower 5890 5890PI 01000 019 V1 Zone type 04 is usually assigned to a zone covering an entry area i e foyer lobby or hallway that one must pass upon entry after faulting the entry exit zone to reach the keypad It provides an instant alarm if the entry exit zone is not violated first and protects an area in the event an intruder has hidden on the premises before the...

Page 19: ...ter 30 seconds a fire alarm is provided If any other fire zone is faulted during the 30 second delay window a fire alarm is immediately provided for that zone An alarm for original fire zone will also be provided if that zone is still faulted afterward If there are no fire alarms after the 30 second delay expires the system will open a 60 second window If any fire zone is faulted during that windo...

Page 20: ...led security code is not required to arm the system The user simply presses and holds down the AWAY or STAY key to arm 22 Keypad Backlight Timeout 0 no timeout always backlight keys 1 turn backlighting off after inactivity This option allows the choice of either always backlighting the keypad or turning the backlighting off after 10 seconds of keypad inactivity 23 Forced Bypass 0 no forced bypass ...

Page 21: ...Entered Value Delay in Seconds 45 96 45 96 97 120 The system will wait the time entered before sounding an alarm if the exit door is left open after the system has been armed UL installations must be set for a maximum of 60 seconds Note The control validates the data entered in this field If the selection is not valid the control will emit a single long beep indicating that the selection has been ...

Page 22: ...an alarm in the system if one or both of the 2 cross zones is bypassed If one of the 2 cross zones faults and remains faulted after the cross zone time interval the second cross zone can go into alarm immediately even after the cross zone time This is to detect scenarios involving multiple break ins of a premises UL This option is not for use in UL installations DIALER PROGRAMMING 40 50 Fields 40 ...

Page 23: ...he telephone message can be terminated acknowledged by pressing any key on the telephone keypad Pressing any key on the local LYNXR ISIA keypad will terminate acknowledge both the follow me and the local reminder announcements Note The follow me reminder announcement will be terminated if any other event requires the system to dial out or if an audible alarm has occurred 47 Phone System Select Cen...

Page 24: ... Report Format Options 6 9 send reports to the primary phone number in a format defined in Field 48 and send reports to a pager which has its phone number entered as the secondary phone number in Field 42 The pager report is a 7 digit code with optional 16 digit prefix in the following format AAAAAAAAAAAAAAAA EEE 0NNN where AAA Optional 16 digits for PIN number etc See Field 88 for full descriptio...

Page 25: ... Enabled 4 Enabled Disabled Disabled 5 Enabled Disabled Enabled 6 Enabled Enabled Disabled 7 Enabled Enabled Enabled Note The control validates the data entered in this field If the selection is not valid the control will emit a single long beep indicating that the selection has been rejected The control replaces the selection with the default value 7 which is displayed on the keypad and advances ...

Page 26: ...t report With ADEMCO Contact ID Reporting Enter a digit in the first box to enable the zone to report Use a different digit for each zone until you have used up available digits If the number of zones exceeds the number of available digits begin with digit 1 again This is an enabling code only and is not the actual code sent to the central station office Entries in the second boxes will be ignored...

Page 27: ...ode See notes above Sent when a system low battery condition is restored to normal 75 RF Transmitter Low Batt Restore Code See notes above Sent when a transmitter that previously sent in a low battery message has sent a message indicating it no longer has a low battery condition 76 Test Restore Report Code See notes above Sent when the test mode is exited A restore code entered here will cause a r...

Page 28: ...Priority 1st Entry delay before switching Central Station reporting path 0 Redundant reporting on dialer and LRR IP communications device 7 105 seconds 8 120 seconds 9 135 seconds 10 150 seconds 1 15 seconds 11 165 seconds 2 30 seconds 12 180 seconds 3 45 seconds 13 195 seconds 4 60 seconds 14 210 seconds 5 75 seconds 15 225 seconds 6 90 seconds 2nd Entry 0 Primary Dialer Preferred Channel 1 LRR I...

Page 29: ...ction is made 91 Audio Alarm Verification AAV Remote Phone Control 0 none 1 AAV and remote phone control 2 remote phone control only 4 AAV only Notes 1 For UL installations Audio Alarm Verification cannot be used Audio Alarm Verification will only function when Contact ID is selected 2 AAV and Remote Phone Control features can only be used if the central station or remote phone supports DTMF comma...

Page 30: ...he 56 Enhanced Zone Programming Mode section for procedure 80 DEVICE PROGRAMMING MENU MODE Interactive menu mode for programming Powerline Carrier Devices Refer to the 80 Device Programming Menu Mode section for detailed procedure 81 ZONE LISTS MENU MODE Interactive menu mode for programming zone lists for Powerline Carrier Devices Refer to the 81 Zone List Menu Mode section for detailed procedure...

Page 31: ...u must refer to these instructions or to the Program Form while programming the system because the keypad display does not show prompt titles Instead prompts are indicated by a number letter combination The prompts for 56 are as follows A 02 Zone Number for entering the zone number b Zone Type for entering zone type C Report Code for entering the zone s report code d Input Type for entering the tr...

Page 32: ... Entry Exit 1 10 Interior w Delay 02 Entry Exit 2 16 Fire with verification 03 Perimeter 20 Arm Stay 04 Interior Follower 21 Arm Away 05 Trouble Day Alarm Night 22 Disarm 06 24 Hr Silent 23 No Alarm Response 07 24 Hr Audible 24 Silent Burglary 08 24 Hr Aux Notes 1 ZT9 and ZT16 can not be assigned to Zone 01 hard wire zone 2 ZT16 is not for use with manually actuated devices including fire keypad o...

Page 33: ...l other device types four 4 transmissions are required fault restore and fault restore A single beep will sound after the second transmission confirming that the loop and serial number have been captured Following the fourth transmission the system will confirm that the loop number and serial number have been learned and announce the Voice Descriptor for the zone if it is programmed followed by tw...

Page 34: ...using the 83 Enhanced Sequential Mode Manual entry Enter 1 to advance to Serial number prompt 1b Copy the previous serial number Enter 2 to copy the previous serial number entered Return to Prompt E Enter to return to Loop Number prompt E Enter transmitter later Enter 0 or if you wish to enter the transmitter later using the 83 Enhanced Sequential Mode described later in this manual Notes 1 The pa...

Page 35: ...r 3 descriptor 3 will be announced 8 accept word and advance to next zone prompt A entire zone descriptor will be announced Press any other key to repeat the selected word see 84 Assign Zone Voice Descriptors section for vocabulary index Use the 6 or 8 key to advance as described To change the entered index number before pressing 6 or 8 simply press desired 2 digit vocabulary index number If descr...

Page 36: ...ccur to a zone or group of zones zone list in order to activate the device These conditions apply only when a zone list is used The different choices for EVENT are listed below and in the Programming Powerline Carrier Devices paragraph that follows ALARM Device activates upon any alarm in an assigned zone in the zone list FAULT Device activates upon any opening or short in an assigned zone in the ...

Page 37: ...ice to de activate During normal system operation any devices may be manually started by keypad entry of Code 4 n or manually stopped by keypad entry of Code 7 n where n the device number to be controlled Code is required for devices 7 and 8 For devices 1 6 code is not required See User Manual for more information Programming Powerline Carrier Devices While in program mode press 80 to enter Output...

Page 38: ...one list not used for this device continue return to previous prompt If a zone list will be used to start the device action enter the zone list number at this prompt E zt Start zone type 01 58 zone type to start this device action select only those that are applicable 00 zone type not used for this device continue return to previous prompt If a zone type or system operation will be used to start t...

Page 39: ...ist can be assigned to more than one Powerline Carrier Device The prompts for 81 are as follows 81 Zone List Programming Main Menu prompt A 01 Zone List Number for entering the zone list number to be programmed b Zone Entry to List for entering zones to the assigned zone list C Delete Entire List for deleting the entire zone list and its contents d Delete Specific Zones From List Selects whether t...

Page 40: ...sts are used b zz Zone entry to list 01 41 95 96 99 zone numbers to add to zone list accept zone number and enter the next zone number 00 accept zone number s and continue to next prompt Enter each zone number to add to the zone list by first entering the zone number then the key for example 01 02 03 The system will announce the Voice Descriptor for the selected zone if it is programmed After all ...

Page 41: ...ries The right most column provides a further explanation of the entries Notes 1 Entry of a number other than one specified will give unpredictable results 2 In Enhanced Sequential Mode 4 button type keys will always be enrolled simultaneously They will be stopped at the 4 button boundaries of 26 30 34 and 38 provided the zone is free of a serial number If the first zone of the key has a serial nu...

Page 42: ...for this transmitter has already been entered however it may still be confirmed viewed or deleted If the transmitter s serial number has not been previously entered you may enter the enroll serial number mode 1A by entering 1 or copy the last serial number that was entered by entering 2 If the transmitter s serial number has been previously entered you may view the present serial number by enterin...

Page 43: ...e the Voice Descriptor if it is programmed followed by three beeps and return to Prompt 1A and LC will be displayed No additional transmissions are needed for confirmation Manual Entry Enter the 7 digit serial number printed on the transmitter If you enter an incorrect digit press the key to backup to prompt 1A and start over When all 7 digits are entered press the key If less than 7 digits are en...

Page 44: ... digit vocabulary index number of first descriptor word for this zone 6 accept word and advance to descriptor 2 descriptor 2 will be announced 8 accept word and advance to prompt A for next zone Press any other key to repeat the selected word Enter the first word of the descriptor for the selected zone Use the 6 or 8 key to advance as described To change the entered index number before pressing 6 ...

Page 45: ...SIDE 67 SILENT POLICE 68 SIX 69 SLIDING 22 SMOKE 23 SOUTH 24 STORAGE 85 SYSTEM T 25 THIRD FLOOR 75 THREE 76 TRANSMITTER 77 TWO U 78 UPSTAIRS 26 UTILITY 79 UTILITY ROOM W 27 WEST 80 WINDOW Y 28 YARD Z 81 ZERO 86 ZONES 29 1ST 30 2ND 31 3RD 70 Custom Word 1 71 Custom Word 2 72 Custom Word 3 73 Custom Word 4 74 Custom Word 5 99 Blank for erasing a previously programmed word SYSTEM WORDS AC LOSS ARMED ...

Page 46: ...de upon which this prompt blinks indicating the mode is inactive A 7d Custom descriptor number Enter 7 d Where d 0 4 each representing custom word 70 71 72 73 or 74 respectively Any existing word will be announced Press to start recorder Begin speaking immediately after the third beep Speak the desired word clearly near the microphone Recording stops after 1 5 seconds 6 accept word and ready to re...

Page 47: ... If an irrelevant command is entered LYNXR ISIA will generate a long rejection beep and repeat the previous voice prompt 3 Phone numbers and account numbers can be left blank by pressing the ADD AWAY key without entering any data 4 LYNXR ISIA automatically saves phone and account number data once all available digits are entered ENTERING VOICE PROMPT PROGRAMMING 1 Power up the control and enter th...

Page 48: ... Door Press SELECT Select delay door location See 1 Press SELECT Activate transmitter twice Press ADD System announces descriptors for the programmed sensor 1 Delay Door Location Front Basement Back Sliding Side Hall Garage Kitchen Patio To add a Window Motion Detector or Fire Detection Sensor Select Add Sensors Press SELECT Select sensor type See 2 Press SELECT Select sensor location See 3 Press ...

Page 49: ...CT Activate transmitter twice Press ADD System announces the key number LYNXR ISIA automatically saves phone and account number data once all available digits are entered To Add First Central Station Phone Number Select First Central Station Phone Number Press SELECT Enter first central station phone number up to 20 digits Press ADD Enter first central station account number up to 4 digits Press A...

Page 50: ...t Number Press SELECT Enter second central station account number up to 4 or 10 digits Press ADD Refer to the LYNXR ISIA Programming Default Tables to view the complete set of Template default table selections To Program a Template Default Table Select Templates Press SELECT Select template See 6 Press SELECT 6 Template selections Template 1 Template 2 Template 3 Template 4 To Enter Expert Program...

Page 51: ...stem compromising information Equipment required to download to a system at the premises An IBM PC compatible computer and appropriate interconnecting cables Either a HAYES brand SMARTMODEM 1200 Level 1 2 or higher external or Level 1 1 or higher with 4 position DIP switch internal style a HAYES brand Optima 336 external a HAYES brand Optima 24 Plus FAX96 or an Ademco CIA Modem Compass Downloader ...

Page 52: ...ypad will become inactive and will display CC 2 The keypad will become active after the download communication is terminated 3 The detailed operation of the download functions is covered in the installation instructions for the Compass Downloader for Windows Remote Programming Advisory Notes Keypad entries are ignored during the time interval stated above A copy of the program downloaded may be pr...

Page 53: ...urity codes permit access to the system for arming disarming etc The Installer Code can disarm the system only if it was used to arm it In addition the Installer Code cannot disarm the system if it was armed by pressing and holding a Quick Arm button The Babysitter Code User Code No 7 can disarm the system only if it was used to arm it In addition the Babysitter Code cannot disarm the system if it...

Page 54: ...ary messages To arm in STAY mode STAY or installer code 3 To restart exit delay STAY applies only if system is armed in Stay mode To arm in AWAY mode AWAY or installer code 2 To arm with NO DELAY AWAY or STAY NO DELAY To arm if Quick Arm is programmed AWAY or STAY hold down for at least 2 seconds To disarm the system and silence alarms OFF Note During Entry Delay or when an Alarm Condition exists ...

Page 55: ...NTER CODE every three 3 seconds for the next eight 8 seconds During this period the panel will wait for a valid User Code to be entered If a valid User Code is not entered or the eight 8 second period expires a modem tone will be generated for remote programming Compass Downloading If a valid User Code has been entered the control will announce the current system status and or beeping sounds Keypa...

Page 56: ...y entering one of the valid AVM commands shown in the table below The session may be extended 5 minutes without changing the operating mode by pressing the 7 key on the touch tone phone Selecting another operating mode also resets the session an additional 5 minutes During the last minute of the 5 minute session the LYNXR ISIA generates two beeps every 30 seconds to alert the Central Station opera...

Page 57: ... or the local LYNXR ISIA keypad will terminate acknowledge the message The system will dial the secondary phone number a maximum of eight times The Follow Me alarm functions may be triggered by a variety of events depending upon the selections made during programming in field 49 Note The follow me system announcement will be terminated if any other event requires the system to dial out or if an au...

Page 58: ...en bypassed CHIME Chime feature is activate FAULT A malfunction is discovered in the system or an open is detected in a fire zone or a fault in a day night burglary zone is discovered during a disarmed period Accompanied by a display of the zone number in trouble FIRE A fire alarm or fire fault is present Accompanied by a display of the zone that is in alarm LOW BAT Low battery condition in a wire...

Page 59: ... Notify them in advance that tests will be in progress 1 Arm the system and fault one or more zones After 15 seconds if optional burglary abort is selected silence alarm sounder s by entering the code and pressing OFF Check entry exit delay zones 2 Check the keypad initiated alarms that are in the system by pressing the Panic key pairs If the system has been programmed for audible emergency the ke...

Page 60: ...the three sets of handshake kissoff frequencies that the panel supports and the different formats that can be sent for each FORMAT HANDSHAKE TRANSMITS DATA KISSOFF TRANSMIT TIME Low Speed 1400Hz 1900Hz 10PPS 1400Hz Under 15 seconds 3 1 Standard report 4 1 4 2 Sescoa Radionics 2300Hz 1900Hz 20PPS 2300Hz Under 10 seconds 3 1 Standard report 4 1 4 2 Express 1400 2300Hz DTMF 10 cps 1400Hz Under 3 seco...

Page 61: ... Walk Test etc contain zeroes in the ZZZ location CONTACT ID EVENT CODES Code Definition 110 Fire Alarm 121 Duress 122 Alarm 24 hour Silent 123 Alarm 24 hour Audible 131 Alarm Perimeter 132 Alarm Interior 134 Alarm Entry Exit 135 Alarm Day Night 146 Silent Burglary 150 Alarm 24 Hour Auxiliary 301 AC Power 302 Low System Battery Battery Test Fail 344 RF Jam Detected 353 ECP Communication Supervisio...

Page 62: ...IP module communication failure displayed on RF Keypad only CA appears if an exit or interior zone contained a fault during closing at the time the Exit Delay ended e g exit door left open but the system was disarmed during the Entry Delay time The alarm sounder and keypad sound continuously but stop when the system is disarmed No message will be transmitted to the central station CC Modem Comm sy...

Page 63: ...keypad 4a System is in Test mode 4b A transmitter low battery has occurred and is displayed 4c A supervision fault has occurred 4d System low battery 4a Enter Code OFF to exit Test mode 4b Enter Code OFF and replace the battery 4c Check the transmitter indicated Restore communication to the receiver to cancel the condition 4d Replace system battery 5 There is no response to a transmitter in normal...

Page 64: ... light not on Open or faulted zone s Check for faulted zones and make intact or use Bypass arming if desired 4 System doesn t respond to keystrokes on keypad 4a CC displayed 4b d1 displayed 4a System is in communication with downloader at central station 4b System has just been powered and is in its one minute initialization 4a Wait until download session is finished 4b Wait for initialization to ...

Page 65: ...window 2 2 2 2 51 Periodic test report 0 3 0 0 52 First test report offset 2 2 2 2 53 Sescoa radionics select 0 0 0 0 54 Lack of usage notification 0 0 0 0 55 Enable Disable ECP interface 0 0 0 0 56 Enhanced zone programming See 56 table See 56 table See 56 table See 56 table 57 False alarm options 7 7 7 7 58 RF jam detection 0 0 0 0 59 Exit error report code 1 1 1 1 60 Trouble report code 1 0 1 0...

Page 66: ... Descriptor 2 1 1 0 3 RF 2 47 04 FRONT DOOR 3 1 1 0 3 RF 2 33 04 BACK DOOR 4 3 1 0 3 RF 2 80 WINDOW 5 10 1 0 3 RF 1 56 MOTION DETECTOR 26 21 1 0 5 BR 3 27 22 1 0 5 BR 2 28 20 1 0 5 BR 4 29 23 0 0 5 BR 1 30 21 1 0 5 BR 3 31 22 1 0 5 BR 2 32 20 1 0 5 BR 4 33 23 0 0 5 BR 1 92 99 6 1 0 NOTE Zone 2 to 41 are RF zones Zone 92 is Duress Zone 99 is keypad panic 56 ZONE ASSIGNMENT ALARM REPORT CODES FOR TA...

Page 67: ...OTE Zone 2 to 41 are RF zones Zone 92 is Duress Zone 99 is keypad panic 80 DEFAULT TABLE APPLIES TO DEFAULT TABLE 4 devices 2 7 have no default values Start Stop Device Number Action Event Zone List Zone Type System Operation Restore of Zone List Zone type System operation 1 2 2 1 2 8 2 33 36 NOTE If using an X10 Powerhouse Security SH10A siren as device 8 you must change the device action default...

Page 68: ...ve the radio or television receiver away from the receiver control Move the antenna leads away from any wire runs to the receiver control Plug the receiver control into a different outlet so that it and the radio or television receiver are on different branch circuits If necessary the user should consult the dealer or an experienced radio television technician for additional suggestions The user o...

Page 69: ...ell 6 14VDC 120mA max e g ADEMCO s WAVE2EX 3 Communication FORMATS SUPPORTED ADEMCO Express 10 characters sec DTMF TouchTone Data Tones 1400 2300Hz ACK 1400Hz KISSOFF ADEMCO Contact ID Reporting 10 characters sec DTMF TouchTone Data Tones 1400 2300Hz ACK 1400Hz KISSOFF ADEMCO Low Speed 10 pulses sec 1900Hz Data Tone 1400Hz ACK KISSOFF Radionics SESCOA 20 pulses sec 1800Hz Data Tone 2300Hz ACK KISS...

Page 70: ...t and the version level if known along with any documentation that came with the product Note your ADEMCO customer number and or company name Having this information handy will make it easier for us to serve you quickly and effectively You may contact Technical Support via Toll Free Fax Please include your return fax number You will receive a reply within 24 hours Technical Support 1 800 645 7492 ...

Page 71: ...LYNXR ISIA Installation and Setup Guide 71 Notes ...

Page 72: ...LYNXR ISIA Installation and Setup Guide 72 Notes ...

Page 73: ...LYNXR ISIA Installation and Setup Guide 73 Notes ...

Page 74: ...n custom voice descriptors 46 Assign zone voice descriptors 44 65 Audio alarm verification AAV remote phone control 29 Audio alarm verification Two way voice feature 56 Aux function 55 Aux function 1 button paging 28 65 Aux key 29 Away mode 54 B Babysitter code 53 Back plate 5 Backlighting 20 Backup battery 11 Backup reporting 22 Battery life 14 Bell 69 BR 13 32 Burglary zones 21 Busy standby 62 B...

Page 75: ...de 20 53 65 Interactive Mode 17 Interior w Delay 19 Interior Follower 18 K Keypad backlight timeout 20 65 Keypad functions 54 55 Keys 13 Kissoff frequency 60 L Lack of usage notification 25 Long range radio 28 Loop and serial number 33 Loop number 33 66 Low battery report code 26 65 Low battery restore report code 27 65 Low speed 60 LYNX DM 5 LYNXRCHKIT HC 12 LYNXRCHKIT SC 12 M Macro function 28 M...

Page 76: ...fications 69 Split dual reporting 24 65 Start by event 36 Start by zone type 36 Start event type 38 Start zone list 38 Start zone type 38 Station initiated remote programming 51 Stay mode 54 Stop recording 54 Stop zone list 38 Stop zone type 38 Supervised fire 19 Supervised RF 13 32 Swinger shutdown 29 System battery 63 System communication 60 System features 4 System operation 36 37 53 67 System ...

Page 77: ...d by those beams They cannot detect motion or intrusion that takes place behind walls ceilings floors closed doors glass partitions glass doors or windows Mechanical tampering masking painting or spraying of any material on the mirrors windows or any part of the optical system can reduce their detection ability Passive Infrared Detectors sense changes in temperature however as the ambient temperat...

Page 78: ...exceed a 60 seconds for a system with standard line security or encrypted line security b 120 seconds for a system without standard line security or encrypted line security or c 120 seconds for a system that does not transmit an alarm signal to a remote monitoring location SIA Quick Reference Guide 1 31 Single Alarm Sounding per Zone If 0 selected alarm sounding per zone will be the same as the nu...

Page 79: ...LE SHUNT REMOVE TO DISABLE THE LYNXR ISIA CONTROL IS COMPATIBLE WITH THE FOLLOWING INTEGRAL RECHARGEABLE BATTERY PACKS EXTERNAL SOUNDERS AND POWERLINE CARRIER DEVICES HAVE NOT BEEN EVALUATED BY UL FUTURE USE FUTURE USE SOUNDERS PLCD AC GND REPLACE EVERY FOUR YEARS P N LYNXRCHKIT SC P N LYNXRCHKIT HC P N LYNXRCHKIT SHA STANDARD HIGH CAPACITY BATTERY CONNECTOR ALARMNET LRR IP COMMUNICATIONS PORT SUP...

Page 80: ...ION ON THE FACE HEREOF IN NO CASE SHALL SELLER BE LIABLE TO ANYONE FOR ANY CONSEQUENTIAL OR INCIDENTAL DAMAGES FOR BREACH OF THIS OR ANY OTHER WARRANTY EXPRESS OR IMPLIED OR UPON ANY OTHER BASIS OF LIABILITY WHATSOEVER EVEN IF THE LOSS OR DAMAGE IS CAUSED BY THE SELLER S OWN NEGLIGENCE OR FAULT Seller does not represent that the products it sells may not be compromised or circumvented that the pro...

Reviews: