*80 Menu Mode: Defining Output Functions
Use this mode to program output function definitions (up to 12 functions) that provide automated
control of any of the output devices, based on events occurring on individual zones or zones with
certain zone types. Each output definition is identified by an output function number, and includes
the following components:
Output Definition Components
Component Description
Output Function No.
A reference number that defines an output’s characteristics.
Activated By
Determines whether the initiating event occurs on a zone, a zone list, or a zone type.
Event
Event that triggers the output action. Can be an event occurring on a specific zone
number or a zone list, or a specific zone type.
Output Action
Defines the action of the relay when the defined event occurs. Can close for 2 seconds,
stay closed until reset, continuously pulse (1-second close-open-close-open, etc.), toggle
the device state, or activate for a defined duration (set in data field *177).
Output No.
Assigns this function to a specific output number (defined in *79 Menu Mode). This is
the output number that will perform this function upon the triggering event. Note that
each defined function is associated with only one output number. This means that if
more than one output device needs to perform this particular function, you need to
define another output function number with the same attributes, but assign the
appropriate output number. (i.e. output devices can be assigned more than one function
number, but each function number can only be assigned a single output number.
For example,
if you want to pulse a strobe light upon fire alarms on zone 4 using a relay mapped to
output number 2 (as programmed in *79 Menu Mode), program the following in *80 Menu Mode:
Prompt Entry
Output Funct. # = 01 (assuming this is the first output function)
Activated By:
= 3 (zone number)
Enter Zn No.
= 04 (requires 2-digit zone numbers)
Output Action
= 3 (continuous pulse)
Output Number = 02 (device mapped in *79 Menu Mode)
Start Output Definition mode by pressing
✱
80 while in Data Programming mode.
∗∗∗∗
80 Menu Mode
PROMPT
VALID ENTRIES and EXPLANATION
Output Funct. #
(00 = Quit)
01
Enter the output function number to be defined
01-12 = output function number
[
∗
] to continue; 00 = exit
01 A E Trig
?00 0 0 – ZL=00
This screen displays a summary of the current output programming
A = Output Action; E = Triggering event; Trig = Trigger type
Question mark indicates the device shown has not been mapped. Use *79 Menu mode to
map the device.
[
∗
] to continue
01 Activated By:
Zone List
Select where the initiating event for this output definition is to occur.
0 = delete (deletes the output function and any previous programming)
Delete?
To delete this output definition, press 1.
0 = NO, 1 = YES
If you do not want to delete this output,. press 0.
1 = zone list (go to “A” prompt); 2 = zone type (go to “B” prompt); 3 = zone number (go to “C”
prompt)
[
∗
] to continue
5-7