A
”
01 Zn List
1
If zone list was selected, this screen appears. Otherwise skip to the next prompt.
Enter the desired zone list number associated with this output number:
01-08 = zone list (Do not use pager zone list 09 in output definitions)
Enter the zone list event that will activate this output:
Enter Event
0 = restore; 1 = alarm;
Alarm 1
2 = fault; 3= trouble
NOTE:
For alarm, fault, and trouble, an event on ANY zone in the list activates the output,
but ALL zones in the list must be restored before the output is restored.
Press [
∗
] to continue and skip to the “Output Action” prompt.
“
B
”
01 Enter Zn type
Perimeter 03
If zone type was selected, this screen appears. Otherwise skip to the next prompt.
Enter the desired zone type for this output number.
CHOICES FOR ZONE TYPES:
00 = Not Used
05 = Trouble Day/Alarm Night 12 = Monitor Zone
01 = Ent/Exit #1
06 = 24 Hr Silent
14 = Carbon Monoxide
02 = Ent/Exit #2
07 = 24 Hr Audible
16 = Fire w/verification
03 = Perimeter
08 = 24 Hr Aux
23 = No Alarm Response
04 = Interior Follower
09 = Fire
24 = Silent Burglary
10 = Interior w/Delay
77 = Keyswitch Zone
81 = AAV Monitor Zone
90 = Configurable
CHOICES FOR
SYSTEM OPERATION:
20 = Arming–Stay
36 = At Bell Timeout***
52 = Kissoff
21 = Arming–Away
38 = Chime
54 = Fire Zone Reset
22 = Disarming
39 = Any Fire Alarm
58 = Duress
31 = End of Exit Time
40 = Bypassing
60 = AAV
32 = Start of Entry Time
41 = AC Power Failure
66 = Function Key†
33 = Any Burglary Alarm
42 = System Battery Low
67 = Bell Fail
43 = Comm. Failure
68 = Telco line cut
78 = Keyswitch Red LED
79 = Keyswitch Green LED
*** Or at Disarming, whichever occurs earlier.
† Use *57 Menu Mode to assign the function key (function “07”).
Note:
In normal operation mode:
Code + # + 7 + NN Key Entry
starts
Device NN.
Code + # + 8 + NN Key Entry
stops
Device NN.
Press [
∗
] to continue and skip to the “Output Action” prompt.
“
C
”
01 Enter Zn No.
12
If zone number was selected, this screen appears.
Enter the desired zone number associated with this output number.
Press [
∗
] to continue.
Enter the zone event that will activate this output.
01 Enter Event
0 = restore; 1 = alarm/fault/trouble
Restore 0
Press [
∗
] to continue to the “Output Action” prompt
01 Output Action
Close for 2 sec
1
Enter the desired device action as listed below.
0 = off
4 = Change Device State
1 = Close for 2 seconds
5 = Duration 1 (see data field *177)
2 = Stay Closed
6 = Duration 2 (see data field *177)
3 = Pulse 1 sec ON, 1 sec OFF
Press [
∗
] to continue.
Enter Output No.
R02 02
Enter the device output number (programmed in *79 Menu Mode) you want associated with
this output.
01-04 = output no.
17-18 = on-board triggers
Press [
∗
] to continue.
02 A E P TRIG
R02 1 1 3 ZL=00
A summary screen appears showing the programmed settings.
Press [
∗
] to return to output function number prompt.
Installation Instructions
5-8