Data Field Programming
4-3
Zone Sounds & Timing
FIELD
TITLE and DATA ENTRIES
EXPLANATION
*31
Single Alarm Sounding Per Zone
(per
armed period)
0 = no limit on alarm sounding per zone
1 = limit alarm sounding to once per arming
period for a given zone
Select whether a zone going into alarm should
sound more than once per armed period.
*32
Fire Alarm Sounder Timeout
0 = yes; fire sounder timeout after time
programmed in field
∗
33
1 = no fire sounder timeout; continue sounding
until manually turned off
Select whether fire alarm sounding expires after
sounder timeout or remains until manually turned
off.
*33
Siren Timeout
0 = No timeout
4 = 4 min
1 = 1 min
5 = 8 min
2 = 2 min
6 = 16 min
3 = 3 min
This field determines whether the external
sounder will shut off after time allotted, or
continue until manually turned off.
*34
Exit Delay
00 - 96 = 0 - 96 seconds
97 = 120 seconds
The system waits the time entered before arming
entry/exit zones. If the entry/exit door is left open
after this time expires, an alarm will occur or the
zone will be auto-bypassed, depending on the
selection in field *88. Common area zones use
same delay as partition 1.
*35
Entry Delay 1
00 - 96 = 0 - 96 seconds
97 = 120 seconds
98 = 180 seconds
99 = 240 seconds
Upon entering, the system must be disarmed
before the time entered expires, otherwise it
sounds an alarm. Common area zones use same
delay as partition 1.
*36
Entry Delay 2
See *35 above for entries.
See *35 for explanation.
*37
Audible Exit Warning
0 = no; 1 = yes
Warning sound consists of slow continuous beeps
until last 10 seconds, then it changes to fast beeps.
Sound ends when exit time expires.