Type 05
Trouble by Day/
Alarm by Night
•
Assign to a zone that contains a foil-protected door or window (such as in a store), or to a zone
covering a sensitive area such as a stock room, drug supply room, etc.
•
Can also be used on a sensor or contact in an area where immediate notification of an entry is
desired.
•
Provides an instant alarm if faulted when armed in the Away, Stay, Night-Stay, Instant or
Maximum (night) modes.
•
During the disarmed state (day), the system will provide a latched trouble sounding from the
keypad (and a central station report, if desired).
Type 06
24-hr Silent Alarm
•
Usually assigned to a zone containing an emergency button.
•
Sends a report to the central station but provides no keypad display or sounding.
Type 07
24-hour Audible
Alarm
•
Assign to a zone that has an emergency button.
•
Sends a report to the central station, and provides an alarm sound at the keypad, and an
audible external alarm.
Type 08
24-hour
Auxiliary Alarm
•
Assign to a zone containing an emergency button, or to a zone containing monitoring devices
such as water or temperature sensors.
•
Sends a report to the central station and provides an alarm sound at the keypad. (No bell
output is provided.)
Type 09
Supervised Fire
•
Provides a fire alarm on short circuit and a trouble condition on open circuit.
•
A fire alarm produces a pulsing bell output and keypad sounding that complies with NFPA
requirements for temporal pulse sounding of fire notification appliances. Fire alarm t
emporal
pulse sounding is as follows: 3 pulses–pause–3 pulses–pause–3 pulses–pause. . . ,
repeated.
•
This zone type is always active and cannot be bypassed.
Type 10
Interior w/Delay
•
Provides entry delay (using the programmed entry time), if tripped when the panel is armed in
the Away mode.
•
Entry Delay 1 begins whenever sensors in this zone are violated, regardless of whether or not
an entry/exit delay zone was tripped first.
•
Bypassed when the panel is armed in the Stay or Instant modes; if armed in Night-Stay mode,
zones assigned to zone list 05 (night-stay zone list) are not bypassed when system armed in
Night-Stay mode.
Type 12
Monitor Zone
•
Works as a dynamic monitor of a zone fault/trouble (not alarm). In the case of a short/open, the
message, "*ALARM*-24 Hr. Non-Burg. -#XXX " (where XXX is the zone number) will be sent
to the Central Station. The system keypad will display a “check” message indicating the
appropriate zone (but keypad beeping does not occur). Upon restoral of the zone, the message,
"*RESTORE*-24 Hr. Non-Burg. -#XXX
" will be sent to the Central Station.
•
The “check” message will automatically disappear from the keypad dynamically, when the
zone restores; a user code + off sequence is not needed to reset the zone.
•
Faults of this zone type are independent of the system, and can exist at the time of arming
without interference.
•
Since this is a “trouble” zone type, do not use this zone type with relays set to activate upon
“alarm.”
Type 14
24 Hour Carbon
Monoxide
Monitor
•
Assigned to any zone with a carbon monoxide detector.
•
A carbon monoxide alarm produces keypad and detector sounding (does not affect bell output)
•
Always active and cannot be bypassed.
Type 16
Fire
w/Verification
•
Provides a fire alarm when zone is shorted, but only after the alarm is verified to help
eliminate false alarms due to electrical or physical transients.
•
System verifies alarm by resetting smoke detectors after short is detected (removes power 7
seconds for zone 1; 3 seconds for trigger output). A subsequent short circuit within 90 seconds
triggers fire alarm, otherwise the first alarm is ignored.
•
Provides a trouble response when zone is open.
Type 20
Arm-Stay (BR
only)
•
Arms the system in Stay mode when the zone is activated.
•
Pushbutton units send the user number to the central station when arming or disarming.
•
User number for button must be assigned.
Type 21
Arm-Away (BR
only)
•
Arms the system in Away mode when the zone is activated.
•
Pushbutton units send the user number to the central station when arming or disarming.
•
User number for button must be assigned.
Type 22
Disarm (BR only)
•
Disarms the system when the zone is activated.
•
User number for button must be assigned.
Programming Overview
3-23
Summary of Contents for Ademco VISTA-21iPSIA
Page 26: ...Installation and Setup Guide 2 20 ...
Page 78: ...Installation and Setup Guide 6 8 ...
Page 84: ...Installation and Setup Guide 8 4 ...
Page 88: ...Installation and Setup Guide 9 4 ...
Page 89: ...Notes 9 5 ...