Zone Sounds & Timing (
∗∗∗∗
31
–
∗∗∗∗
39)
*31
Single Alarm Sounding Per Zone
(per armed period)
0 = no limit on alarm sounding per zone
1 = limit alarm sounding at the bell output to once per
arming period for a given zone
V21iPSIA:
If
“
0
”
selected,
“
alarm sounding per zone
”
will be the same as the
“
number of reports in armed
period
”
set in field *93 (1 if one report, 2 if 2 reports,
unlimited for zones in zone list 7).
*32
Fire Alarm Sounder Timeout
0 = yes; sounder timeout after time selected in field
∗
33
1 = no timeout; sounds until manually turned off
This control complies with NFPA requirements for
temporal pulse sounding of fire notification appliances.
Temporal pulse sounding for a fire alarm consists of the
following:
3 pulses – pause – 3 pulses – pause – 3 pulses.
UL fire alarm installations: must be
1
.
*33
Alarm Sounder Timeout
0 = No timeout; 1 = 4 min; 2 = 8 min; 3 = 12 min; 4 = 16 min
This field determines whether the external sounder will
shut off after time allotted, or continue until manually
turned off.
UL Installations: For residential fire alarm installation,
must be set for a minimum of 4 min (option
1
); for UL
Commercial Burglary installations, must be minimum
of 16 min (option
4
).
*34
Exit Delay
00 - 96 = 0 - 96 seconds; 97 = 120 seconds
V21iPSIA:
45 - 96 = 45 - 96 secs; 97 = 120 secs
NOTE: Entries less than 45 will result in a 45-sec delay.
The system waits the time entered before arming
entry/exit zones. If the entry/exit door is left open after
this time expires, an alarm will occur. Common zones
use same delay as partition 1.
UL installations: For UL Commercial Burglar Alarm
and UL Residential Burglar Alarm installations with
line security, total exit time must not exceed 60
seconds.
SIA Guidelines: minimum exit delay is 45 seconds
*35
Entry Delay 1 (*35), Entry Delay 2 (*36)
*36
00 - 96 = 0 - 96 seconds; 97 = 120 secs; 98 = 180
secs; 99 = 240 secs
V21iPSIA:
30-96 = 30 - 96 secs;
97 = 120 secs; 98 = 180 secs; 99 = 240 secs
NOTE: Entries less than 30 will result in a 30-sec delay.
Upon entering, the system must be disarmed before the
time entered expires, otherwise it sounds an alarm.
Common zones use same delay as partition 1.
UL Installations: For UL Residential Burglary Alarm
installations, must be set for a maximum of 30 seconds;
entry delay plus dial delay should not exceed 1 min. For
UL Commercial Burglar Alarm, total entry delay may
not exceed 45 seconds.
SIA Guidelines: minimum entry delay is 30 seconds
*37
Audible Exit Warning
0 = no; 1 = yes
Warning sound consists of slow continuous beeps until
the last 10 seconds, and then it changes to fast beeps.
Sound ends when exit time expires.
SIA Guidelines: must be enabled (enter
1
)
V21iPSIA:
Feature always enabled; field does not exist.
*38
Confirmation Of Arming Ding
0 = no ding; 1 = confirmation ding after arming system
2 = ding after arming from RF button or RF keypad only
(except 5827/5827BD)
Confirmation of arming is 1/2-sec external sounder “ding.”
If
1
selected, ding occurs when closing report is sent if
open/close reporting is enabled, or at the end of Exit
Delay. If
2
selected, ding occurs upon reception of the
wireless arming command.
UL Installations: must be
1
for UL Commercial Burglar
Alarm installations.
*39
Power-Up In Previous State
0 = always power-up in a disarmed state
1 = assume the system status prior to power down
When the system powers up armed, an alarm will occur
1 minute after arming if a zone is faulted.
Note that if the previous state was armed Away or Stay,
the system ignores sensor changes for 1 minute, which
allows sensors such as PIRs to stabilize.
UL Installations: must be
1
(power-up in previous state)
SIA
Guidelines
: must be
1
V21iPSIA:
Feature must be enabled.
Dialer Programming (
∗∗∗∗
40
–
∗∗∗∗
50)
*40
PABX Access Code or Call Waiting Disable
Enter up to 6 digits if PABX is needed to access an
outside line. Do not fill unused spaces. 0
–
9, # + 11 for
‘
∗
’
,
# + 12 for
‘
#
’
, # + 13 for a pause (2 seconds)
To clear entries from field, press
∗
40
∗
. If fewer than 6
digits need to be entered, exit by pressing [
∗
].
Call Waiting:
If the subscriber’s phone service has
“call waiting” (and is not using PABX), enter “*70” (“# +
11”) plus “# + 13” (pause) as the PABX entry to disable
“call waiting” during control panel calls. If the
subscriber does not have “call waiting” and is not using
PABX, make no entry in this field.
NOTES:
1. The call waiting disable feature cannot be
used on a PABX line. 2. Using Call Waiting Disable on
a non-call waiting line will prevent successful
communication to the central station.
V21iPSIA:
If call waiting is used, enter call waiting disable digits
as described above, and also set Call Waiting Disable option in
field *91.
*41
Primary (*41) and Secondary (*42) Phone No.
*42
Enter up to 20 digits. 0
–
9, # + 11 =
‘
∗
’
, # + 12 =
‘
#
’
,
# + 13 = pause (2 secs)
If entering fewer than 20 digits, exit by pressing [
∗
] +
next field number. To clear entries, press
∗
41
∗
or *42*
respectively. Do not fill unused spaces.
NOTE:
Backup reporting (see field *49) is automatic
only if there is a secondary phone number (field
∗
42).
Installation and Setup Guide
4-2
Summary of Contents for Ademco VISTA-21iPSIA
Page 26: ...Installation and Setup Guide 2 20 ...
Page 78: ...Installation and Setup Guide 6 8 ...
Page 84: ...Installation and Setup Guide 8 4 ...
Page 88: ...Installation and Setup Guide 9 4 ...
Page 89: ...Notes 9 5 ...