I n t e r n a l D e v i c e
I P
Internal Device Selection
Disable
–
IP
–
GSM
–
IP & GSM
Select the desired type of internal device usage, IP and/or GSM (press [
∗
] to scroll choices).
Press [#] to continue
M u l t i m o d e
D i s a b l e d
Multi-Mode (email reporting)
Disabled =
no email reporting of events
4204 Sourced = up to four types of events reported (relay numbers 1-4 report as events 1-4
respectively)
2-4204 Sourced = up to eight types of events reported (first module
’
s relay numbers 1-4 report
as events 1-4 respectively; second module
’
s relay numbers 1-4 report as
events 5-8 respectively)
Enhanced Reports = Enables full panel status reporting via email and reporting to TC2 web
services. If used, RIS must be enabled in field *91; when enabled, address 25
is automatically assigned.
[#] to continue
Select the desired multi mode option (press [
∗
] to scroll choices).
This feature is available only after authorization for it is set via the web-based programming
tool on the AlarmNet Direct website.
Multi-mode emulates 4204 Relay Module outputs to send up to four (4204 sourced) or up to
eight (2-4204 sourced) reports of system events to the user via email (email address is
entered at the AlarmNet Direct website). Use the AlarmNet Direct website to customize
event titles, if desired. If enabled, a multi-mode address must be entered in the next prompt.
Use *79/*80 Menu modes to program each emulated relay output to trigger a desired system
event that, upon occurrence, will be sent to the user’s email address.
NOTES:
1. Multi-mode has not been evaluated by UL.
2. Multi-mode (email notification) is intended as a convenience for the user, and does not
replace Central Station reporting of critical events (alarms, troubles, etc.).
M u l t i m o d e A d d r
( 1 2 )
Multi-Mode Address
This prompt appears if Multi Mode is enabled.
12-15 =emulated 4204 Relay Module address.
25 = automatically assigned if Enhanced Reports selected
Select the desired address. If using “2-4204-sourced,” the address of the second module is
automatically assigned an address one higher than the first module’s address.
NOTE:
A 4204 Relay module address is required for multi-mode purposes, but an actual
4204 Relay module is not used at the selected address.
P r i m a r y C i t y I D
( ? ? )
Primary City ID
NOTE:
Account information is provided by the central station administrator.
01-99 (decimal) = 2-digit primary city code
P r i m a r y C S I D
( ? ? )
Primary CS ID
01-FE (HEX)
Enter the primary central station's system ID number,
P r i m a r y S u b I D
( ? ? ? ? )
Primary Subscriber ID
0001-9999 (decimal)
Enter the 4-digit customer account number.
R e m o t e A c c e s s Y / N
( N )
Remote Access
This feature is available only after authorization for it is set via the web-based
programming tool on the AlarmNet Direct website.
[Y] = use remote services
[N] = do not use remote services
[#] to continue
Remote Services allow the end user to access their security system from their
computer via the remote services (ex. Total Connect) website. Most system
functions can then be performed.
Menu Mode Programming
5-21
Summary of Contents for Ademco VISTA-21iPSIA
Page 26: ...Installation and Setup Guide 2 20 ...
Page 78: ...Installation and Setup Guide 6 8 ...
Page 84: ...Installation and Setup Guide 8 4 ...
Page 88: ...Installation and Setup Guide 9 4 ...
Page 89: ...Notes 9 5 ...