background image

S E C T I O N   1  

Features and Installation Highlights 

• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •

 

This manual describes the installation of both the VISTA-48A and VISTA-48E. These units 
are identical except where noted. 
 

Capabilities 

  Supports 3 partitions, which can protect three independent areas, as if each area had its own 

control. 

  Common area option allows either of the other two partitions to arm, while leaving a common 

area (ex. lobby or foyer) disarmed for access into the remaining disarmed partition. 

  Supports up to 48 protection zones plus 16 keyfob zones (zones 49-64) for total of 64 zones: 

  -- 8 basic wired zones (zones 1-8) with optional zone-doubling/double-balanced zone feature 
  -- Up to 40 additional wired zones (zones 9-48) using up to 5 8-zone 4219/4229 modules (each 4-

zone 6164 in which zones [EOLR or double-balanced] are used consumes one 4229 location) 

  -- Supports up to 40 wireless transmitter zones (5800 series; zones 9-48); additional wireless 

zones are available if less than 16 keyfob zones are used. 

  -- Supports up to 4 installer-configurable zone types 

 

  Up to 48 Security Codes, each with separate authority levels and partition access 

  Provides supervision of auxiliary power and supervision of trigger power via the Trigger-G 

module (supplied). 

 

  Downloading via an IBM compatible computer, Compass downloading software, and an 

ADEMCO CIA/CIA-EU modem. 

 

Functions 

  Single-button arming feature: Can use dedicated keys to arm the system AWAY or STAY 

  Up to 32 Schedules, to control output devices, to determine when users have access, and/or to auto-

arm/disarm (or allow disarm) the system 

  Up to 4 Keypad macros, which can be activated by wired/wireless keypads  

  Paging feature allows certain system conditions to be reported to up to 2 pager phone numbers; can 

use a dedicated key on keypads to send a signal to a pager 

  User programmable telephone number for audio “beeps” reporting of alarms to the user (follow-me 

feature). 

  Built-in Telephone Line Monitoring option can monitor the telephone line voltage and can cause a 

local display, or a display and trouble/alarm sound. 

  Event Logging records up to 254 selected events in a history log; control and readout from the log is 

done via Ademco Compass Downloader software or using an installer/master code at an alpha 
display keypad for local display. 

  Installer-customized zone descriptors for all zones (useful only when using alpha display keypads). 

  Optional siren supervision detects external sounder wiring short or open; causes a trouble 

condition, keypad display, and sends a report to the central monitoring station, if enabled. 

  Optional RF jam detection for wireless systems detects a condition that may impede proper RF 

reception (i.e., jamming or other RF interference); causes keypad display, sends a report to the 
central monitoring station (if trouble reporting is enabled), and can optionally send a tamper alarm 
if detected during the armed mode. 

  Individual user code selection for open/close reporting to central monitoring station (set when 

adding a user code, attribute 6). 

 

 

1-1 

Summary of Contents for ADEMCO VISTA-48A

Page 1: ...ADEMCO VISTA 48A ADEMCO VISTA 48E Security Systems Installation and Setup Guide K0749 1EN 11 04 Rev A ...

Page 2: ...nstalling the Transmitters 2 9 Installing a Keyswitch 2 10 Connecting Relay Modules 2 11 Powerline Carrier Devices 2 12 Trigger Module and On Board Triggers 2 13 Phone Line Connections 2 14 Alternative Communications Media ACM Connections 2 14 Programming Overview 3 1 About Programming 3 1 Zones and Partitions 3 1 Keypads 3 2 Wireless Receiver Transmitters and Wireless Keys keyfobs 3 2 Pager Progr...

Page 3: ...82 Menu Mode 5 15 Configurable Zone Type Programming 83 Menu Mode 5 16 Programming Installer and User Schedules 5 18 System Communication and Operation 6 1 Panel Communication with Central Station 6 1 Report Code Formats 6 1 Robofon 8 Format 6 3 ADEMCO Contact ID 6 4 Security Codes 6 5 Keypad Functions 6 6 Panic Keys 6 6 Follow Me Feature 6 7 Setting Adjusting the Real Time Clock 6 7 Various Syste...

Page 4: ......

Page 5: ...stem AWAY or STAY Up to 32 Schedules to control output devices to determine when users have access and or to auto arm disarm or allow disarm the system Up to 4 Keypad macros which can be activated by wired wireless keypads Paging feature allows certain system conditions to be reported to up to 2 pager phone numbers can use a dedicated key on keypads to send a signal to a pager User programmable te...

Page 6: ... Plug in 230VAC power pack XF1 Model No 60844CK Ap11 V 99090 E148 36 VISTA 48E 220VAC wired in transformer 16 5VAC 25VA Important Installation Highlights Installer Please Read This system uses addressable keypads and Zone Expander Modules see table of addresses in Programming Overview section Keypads must be set for addresses 16 23 first keypad is address 16 which is different from previous contro...

Page 7: ...closed and secured without a lock by using 2 screws in the cover s edge CABINET DOOR BOTTOM LOCKED UNLOCKED cab_lock_snap 001 V0 ADEMCO ADEMCO PUSH SNAP TAB SNAP TAB PUSH ON LOCK UNTIL IT IS SEATED SECURELY STEP 2 STEP 1 CHECK POSITION Figure 1 Installing the Cabinet Lock Mounting the PC Board Alone no RF Receiver 1 Hang two short mounting clips provided on the raised cabinet tabs see Detail B in ...

Page 8: ...d terminals and tighten the screws Notes Do not mount the cabinet on or near metal objects This will decrease RF range and or block RF transmissions from wireless transmitters Do not locate the cabinet in an area of high RF interference revealed by frequent or prolonged lighting of the LED in the receiver after it is operational random flicker is OK ANTENNA MOUNT 2 PLACES ANTENNA 2 SCREW 2 BLACK M...

Page 9: ...ntary power if the control s aux power load for all devices exceeds 700mA Suggested power supply AD12612 Keypad Addresses Keypad Address Keypad Address no 1 16 no 5 20 no 2 17 no 6 21 no 3 18 no 7 22 no 4 19 no 8 23 The first keypad is address 16 which is always enabled and set for partition 1 with all sounds on Aux Power Supervision Connections To supervise aux power 1 Use the Trigger Module term...

Page 10: ...ery supplies this current Do NOT perform steps 2 and 3 if using a self activated siren Wiring the AC Transformer Transformer Connect the Transformer to terminals 1 and 2 on the control board See wiring table at right for wire size to use Use wired in or plug in 220VAC transformer with 16 5VAC 25VA output VISTA 48A XF1 Model 60844CK Ap11 V 99090 E148 36 Using Powerline Carrier X 10 Devices If using...

Page 11: ...pected levels of lightning and electrical discharge and does not normally require an earth ground If an earth ground is desired for additional protection in areas of severe electrical activity terminal 25 on the control board or the cabinet may be used as the ground connection point The examples of good earth grounds listed at the left are available at some installations AUXILIARY DEVICE CURRENT D...

Page 12: ... zone identifications for normally closed sensors connected to each basic wired zone but does not increase the total number of zones supported by the control Do not use zone doubling for fire zones If enabled Zone Programming mode Hardwire Type prompt option 3 basic wired zones are automatically paired as follows Zone Paired with zone 1 9 2 10 3 11 4 12 5 13 6 14 7 15 8 16 NOTE A short across the ...

Page 13: ...shown in the following table Expander Module Addresses For Zones Set Module to Device Address 09 16 07 not available if zone doubling enabled 17 24 08 25 32 09 33 40 10 41 48 11 3 Connect sensors to the module s loops 4 If using relays with the 4229 connect the desired field wiring to the unit s relay contact terminals Notes Supports up to 40 expansion zones NO or NC using 4219 4229 Zone Expander ...

Page 14: ...the keypad s relay contact terminals See 6164 Keypad Instructions for other mounting wiring and programming information Notes Each 6164 keypad supports up to 4 wired expansion EOLR or double balanced zones and one relay output Use 2000 ohm end of line resistors at the end of loops connected to the 6164 keypads Enter 6164 keypad program mode by pressing and holding down both the 1 and 3 keys within...

Page 15: ...KEYPAD CONNECTION POINTS 5882 LOCATION TO RELEASE CIRCUIT BOARD REMOVE SCREWS AND BEND BACK TABS NOTE CIRCUIT BOARD IS MOUNTED IN CONTROL S CABINET GROUNDING LUGS 2 PROVIDED MUST BE INSERTED IN LEFT HAND TERMINALS OF ANTENNA BLOCKS AND SECURED TO CABINET SEE RECEIVER S AND CONTROL S INSTRUCTIONS SOCKET PLUG MODEL NO IS INDICATED ON CIRCUIT BOARD 5881 003 V0 INSERT IN RIGHT HAND TERMINALS Figure 9 ...

Page 16: ...17 output 18 trigger connector pins 3 Connect a 2000 ohm EOL resistor across the momentary switch 4 You can wire an optional closed circuit tamper switch model 112 in series with the zone If the switchplate is then removed from the wall the tamper will open disabling keyswitch operation until the system is next disarmed from the keypad If the tamper is opened when the system is armed an alarm will...

Page 17: ...ss lxx or 91 if field 199 set for 2 digit display where xx is the module s address If communication tamper failure occurs on a device with zones wired to it all zones on the device will be displayed in their respective partitions Relay Module Addresses 4204 6164 Address 4229 6164 Address no 1 12 no 1 zn 09 16 07 no 2 13 no 2 zn 17 24 08 no 3 14 no 3 zn 25 32 09 no 4 15 no 4 zn 33 40 10 no 5 zn 41 ...

Page 18: ...ne Carrier devices you must use a Powerline Carrier Device Modulator It supplies signals from the control panel through the premises AC mains wiring to the Powerline Carrier devices which are plugged into AC outlets You can then make devices that are plugged into Powerline Carrier devices perform various functions in response to commands you enter at the security system keypads 7 8 USE SA4120XM 1C...

Page 19: ...orient the Trigger Module as shown on the Summary of Connections diagram then press down firmly until the Trigger Module s standoffs are seated on the main PC board Notes The Trigger module Trigger G provides supervision of auxiliary power and trigger power and provides connections for the two onboard triggers There are two on board triggers that can be used to activate output devices These output...

Page 20: ...tions use one of the on board triggers Suggested AAV Module ADEMCO UVS shown or Eagle 1250 Notes Set field 91 for AAV and program the appropriate output output 17 or 18 using 80 Menu mode select zone type 60 For voice session monitoring connect an EOLR zone to UVCM module terminals 6 7 and program the zone as zone type 81 56 Menu mode E g Using output 18 for the trigger program an output function ...

Page 21: ... zone and pager zones 82 Alpha Programming Create alpha descriptors for easy zone identification Scheduling Mode code 64 Create schedules to automate various system functions or determine user access Zones and Partitions Each protection zone needs to be programmed with various attributes using 56 Zone Programming mode or 58 Expert Programming mode Refer to those sections for detailed procedures Th...

Page 22: ... switch equipped wireless keypads for each partition 25 Arming Prevention Override 67 Transmitter Low Battery Report Code 75 Transmitter Low Battery Restore Report Code 173 RF Reporting Options 178 RF Supervision RF Jam Options Use 56 Menu mode to program wireless zones 9 48 and wireless button zones 49 64 Transmitters Use 56 or 58 Zone Programming Menu modes to program zone information and enroll...

Page 23: ...e types are defined below Zone Type Description Type 00 Zone Not Used Program a zone with this zone type if the zone is not used Type 01 Entry Exit Burglary 1 Assign to zones that are used for primary entry and exit Provides entry delay when zone type is faulted if control is armed in the Away Stay or Night Stay modes No entry delay provided when the panel is armed in the Instant Maximum mode Entr...

Page 24: ...ne Works as a dynamic monitor of a zone fault trouble not alarm In the case of a short open the message ALARM 24 Hr Non Burg XXX where XXX is the zone number will be sent to the Central Station The system keypad will display a CHECK message indicating the appropriate zone but keypad beeping does not occur Upon restoral of the zone the message RESTORE 24 Hr Non Burg XXX will be sent to the Central ...

Page 25: ...sent Type 82 Blockschloss Used with special blockschloss lock and key System arms 5 seconds after the key is fully turned arms MAXIMUM key can then be removed When armed the blockschloss zone is shorted An open circuit on this zone causes trouble condition If zones are not ready the key will not turn fully and the system will not arm Contact ID report code is 409 Once the system is armed using blo...

Page 26: ...e Alpha display keypad will display the first of a series of prompts requesting entries After making the appropriate entry press the key to accept the entry and continue to the next prompt Loading Factory Defaults Initializing for Download To Load Default Entries Data Field System and Zone Defaults The VISTA 48A and VISTA 48E each have two unique sets of default entries The complete default tables...

Page 27: ...04 6164 module 1 6164 relay only module 2 6164 relay only module 3 6164 relay only module 4 6164 relay only 12 13 14 15 112 113 114 115 79 output device programming device address prompt entered at device address prompt entered at device address prompt entered at device address prompt entered at device address prompt Keypads keypad 1 keypad 2 keypad 3 keypad 4 keypad 5 keypad 6 keypad 7 keypad 8 1...

Page 28: ...Installation Instructions 3 8 ...

Page 29: ... 23 Quick Forced Bypass 0 no quick bypass 1 allow quick bypass code 6 All zones bypassed by this function will be displayed after the bypass is initiated 24 RF House ID Code 00 disable all wireless keypad usage 01 31 House ID for partition 1 2 3 The House ID identifies receivers and wireless keypads If a 5827 or 5827BD wireless keypad or 5804BD 5804BDV transmitter is being used a House ID code mus...

Page 30: ...LD TITLE and DATA ENTRIES EXPLANATION 31 Single Alarm Sounding Per Zone per armed period 0 no limit on alarm sounding per zone 1 limit alarm sounding to once per arming period for a given zone Select whether a zone going into alarm should sound more than once per armed period 32 Fire Alarm Sounder Timeout 0 yes fire sounder timeout after time programmed in field 33 1 no fire sounder timeout contin...

Page 31: ...ed to access an outside line Do not fill unused spaces 0 9 11 for 12 for 13 for a pause 2 seconds To clear entries from field press 40 If fewer than 6 digits need to be entered exit by pressing which advances to the next field Call Waiting If the subscriber s phone service has call waiting and is not using PABX enter 70 11 plus 13 pause as the PABX entry to disable call waiting during control pane...

Page 32: ...s delay of BURGLARY ALARM report to the central station which allows time for the subscriber to avoid a false alarm transmission This delay does not apply to zone type 24 alarms silent burglary or to 24 hour zone types 6 7 and 8 silent panic audible alarm auxiliary alarm which are always sent as soon as they occur 51 Part 3 Primary Subs Acct No Enter digits 0 9 11 for B 12 for C 13 for D 14 for E ...

Page 33: ...t to the Central Station office Entries in the second entry pair are ignored An entry of 0 in the first box disables the report FIELD TITLE and DATA ENTRIES EXPLANATION 59 Exit Error Report Code 0 no report 1 F report code see description above After arming the system zones remaining open after exit delay expires cause an alarm sound at the keypad and external sounder keypad also displays EXIT ALA...

Page 34: ...t when a system low battery condition is restored to normal 75 RF Low Battery Restore Code 0 disable 1 F see description above 59 Sent when a transmitter s low battery condition is restored i e new battery installed 76 Test Restore Report Code 0 disable 1 F see description above 59 Sent when the Test mode is exited Miscellaneous System Fields FIELD TITLE and DATA ENTRIES EXPLANATION 77 Summer Time...

Page 35: ...5 seconds to 15 min It can be assigned to zones with sensors that provide a trouble indication when an oil or gas tank is low or similar applications for critical condition monitoring where a non alarm response is desired and where the zone response time should be very long to avoid reacting to normal transient faults 88 Exit Options 0 all intrusion zones must be intact before arming 1 All intrusi...

Page 36: ...armed Entry 1 Sets the length of time a phone line fault must remain after detected before the second digit option is activated Entry 2 Selects the desired phone line fault response Option 2 may be used even if a relay unit or Powerline carrier device is not connected to the control Programmed Output Device must either be programmed to be STOPPED in field 80 or STOPPED by entry of security code 8 ...

Page 37: ...cates that the system is reporting a closing system arming 102 by User 5 in partition 2 162 Pager 1 Report Options 0 No reports sent 1 Open close for all users enabled to page 4 All alarms and troubles 5 All alarms troubles and open close for all users enabled to page 12 Alarms and troubles for zones entered in zone list 9 13 Alarms and troubles for zones listed in zone list 9 and opens closes for...

Page 38: ...conds keypad sounds immediately 177 Device Duration 1 2 Duration 1 Device Action 5 Timer 0 15 secs 6 2 1 2 min 12 8 min 1 30 secs 7 3 min 13 10 min 2 45 secs 8 4 min 14 12 min 3 60 secs 9 5 min 15 15 min 4 90 secs 10 6 min 5 2 min 11 7 min Duration 2 Device Action 6 Timer 1 7 1 to 7 days These entries set the duration for output action options 5 duration 1 and 6 duration 2 programmed in 80 Output ...

Page 39: ...ing 2 switch on Friday morning Select the appropriate summer time switchover day 183 Date Time Format 0 12 hour time MMDDYY date 1 12 hour time DDMMYY date 2 24 hour time MMDDYY date 3 24 hour time DDMMYY date Select the desired time and date format 185 Downloader Suppression Options 0 no suppression 1 suppress user code viewing 2 suppress commands and program download when armed 3 suppress user c...

Page 40: ...n 0 no suppression 1 suppress arm disarm and E E beeps 2 suppress chime beeps only 3 suppress arm disarm E E beeps and chime beeps Keypad 2 Entry 1 enter the partition in which the keypad is located Entry 2 Enter the desired sound option for this keypad NOTE Address 16 is reserved for keypad 1 which is factory set to partition 1 with all sounds enabled 191 Keypad 3 Device Address 18 Keypad 3 See f...

Page 41: ... Confirm 0 no 1 yes If 1 Yes is entered the XMIT TO CONFIRM prompt appears later in this procedure after entering RF transmitter serial and loop numbers and lets you confirm the programming of each RF transmitter We recommend that you confirm every transmitter If 0 No is entered the XMIT TO CONFIRM prompt is automatically skipped This option is ignored if programming wired zones only Enter Zn Num ...

Page 42: ...1 08 automatically applies to each zone s associated doubled zone 10 INPUT TYPE RF TRANS 3 Input Device type In 2 AW Aux wired zone 3 RF supervised RF transmitter 4 UR unsupervised RF transmitter 5 BR unsupervised button type RF transmitter 7 RM supervised RF motion detector to continue This prompt is skipped for zones 9 16 if zone doubling was enabled at Hardwire Type prompt All of the RF transmi...

Page 43: ...d in error simply re enter the loop number or press and the serial number will return to the display XMIT TO CONFIRM PRESS TO SKIP Confirmation Option Activate the loop input or button to continue This prompt will only appear if you answered Yes at the first prompt in this section The system will enter a confirmation mode so that the operation of the actual programmed input can be confirmed Activa...

Page 44: ...number 00 quit to continue OR D to go to prompts for wireless key programming templates A summary screen will appear showing zone 1 s currently programmed or default values Enter the zone number being programmed then press which displays a summary screen for that zone See next prompt in this example zone 10 is being entered If programming a wireless key press the D key then skip to the Wireless Ke...

Page 45: ... appear if the first prompt after entering 58 was answered Yes To confirm activate the loop input or button that corresponds to this zone The system checks for a duplicate If a duplicate exists a long error beep will sound Press to back up and re enter the serial and or loop number Entd A022 4063 Rcvd A022 4064 If Serial or Loop Numbers do not match after activating the transmitter to continue If ...

Page 46: ...he highest available consecutive 4 zone group the four zones in the case of the 5804 and 5804BD and display the lowest zone number of the group If you want to start at a different zone enter the zone desired and press If that zone number is displayed the system has the required number of consecutive zones available beginning with the zone you entered If not the system will again display a suggeste...

Page 47: ...ing Form then enter the other information zone number zone type loop number etc relevant to that device Wireless Key Predefined Default Templates YOU MUST PROGRAM THIS BUTTON LOOP 4 LOOP 3 ENROLL AS BR LOOP 1 LOOP 2 ON OFF 5804 001 V1 5804 Wireless Key Transmitter LOOP 3 LOOP 1 LOOP 2 LOOP 4 YOU MUST PROGRAM THIS BUTTON RED YELLOW LED GREEN YELLOW LED ENROLL AS BR 5804BD 007 V0 5804BD 2 Way Wirele...

Page 48: ...again Output Device programming involves 1 Use 79 Menu Mode to assign module and output numbers and map them to device addresses NOTE You must map output devices using 79 Menu Mode before you can use 80 Menu Mode 2 Use 80 Menu Mode to create output definitions which control the output devices 79 Menu Mode Output Device Mapping Use this menu to assign Relay Module device addresses and specific rela...

Page 49: ...pad 2 Powerline Carrier device to continue Select whether this is a relay or a Powerline Carrier X 10 device If relay is selected skip to B prompt If X 10 is selected go to A prompt A XX UNIT No yy Unit Number 01 16 predefined address to continue If X 10 is selected a prompt for the unit number appears Enter the unit code set at the device and press The system returns to the Output Number prompt B...

Page 50: ...nction is associated with only one output number This means that if more than one output device needs to perform this particular function you need to define another output function number with the same attributes but assign the appropriate output number i e output devices can be assigned more than one function number but each function number can only be assigned a single output number For example ...

Page 51: ...associated with this output number See below for a list of available zone types CHOICES FOR ZONE TYPES 00 Not Used 06 24 Hr Silent 15 Medical 01 Ent Exit 1 07 24 Hr Audible 16 Fire w verification 02 Ent Exit 2 08 24 Hr Aux 23 No Alarm Response 03 Perimeter 09 Fire 24 Silent Burglary 04 Interior Follower 10 Interior w Delay 77 Keyswitch 05 Trouble Day 12 Monitor Zone 81 AAV Monitor Zone Alarm Night...

Page 52: ...Enter the desired device action as listed below Press the key to continue 0 off 4 Change Device State 1 Close for 2 seconds 5 Duration 1 see data field 177 2 Close and Stay Closed 6 Duration 2 see data field 177 3 Continuous Pulse on off 1 sec ON 1 sec OFF Enter Output No R02 02 Output Number 01 16 output no 17 18 on board triggers Enter the device output number programmed in 79 Menu Mode you want...

Page 53: ...ample 01 02 03 After all zones are entered press 00 to continue IMPORTANT Do not include fire zones in zone lists that are used to STOP device actions 01 Del Zn List 0 No 1 Yes 0 Deleting Zone Lists 0 don t delete list 1 delete this zone list to continue To delete the zone list enter 1 All zones in the zone list will be deleted automatically and the system returns to the Zone List No prompt To sav...

Page 54: ...95 00 Define Key Function 00 12 see list to right to continue Returns to key number prompt with the next function key letter displayed System defaults to these function key settings For Options 09 12 note that there are only four macros per system Therefore be careful when assigning these macros to the various partitions Enter the desired function for this key 00 to 12 from the options listed 00 s...

Page 55: ...mpt to let you enter zone descriptors Pressing 1 lets you program a partition descriptor If selected the following prompt appears PART Enter the 2 digit custom word number 11 13 to be programmed then press Enter the descriptor as described in steps 1 3 in the Zone Number section below Zone No 00 Zone Number Enter the desired zone number to continue After pressing a cursor will appear at the second...

Page 56: ...bled pair must be assigned the same response to a short 90 Resp to open Armed 0 DArmd 0 Response to Opens 0 none 2 trouble 1 Alarm 3 fault to continue Select the type of response when zones assigned to this zone type are opened when the system is armed 90 Vent Zone 0 No 1 Yes Vent Zone 0 no 1 yes to continue If selected the system can be armed even if zones assigned to this zone type are faulted N...

Page 57: ...0 Trouble ID 000 Contact ID Report Codes 000 999 report code to continue returns to Enter configurable zone type number prompt Enter the desired 3 digit Contact ID report codes for faults and troubles occurring on zones assigned to this zone type IMPORTANT Make sure the code does not conflict with existing predefined Contact ID report codes See the System Communication section for a list of standa...

Page 58: ... all pagers in the user s partition message sent is 777 7777 User must be enabled for paging see User Attributes in System Operation section Auto Stay Arm event 04 and Auto Arm event 5 cannot be used if partition 3 is set as a common partition To use these scheduling features field 30 must be 0 making partition 3 a separate partition Disarm Time Window 08 System can be disarmed only during this ti...

Page 59: ...nts 1 relay on off 2 user access 3 child not home report use 00 23 if 24 hour time is enabled REPEAT OPTION 0 4 X Repeat Option 0 do not repeat 1 repeat schedule weekly 2 repeat schedule biweekly every other week 3 repeat schedule every third week 4 repeat schedule every fourth week to continue Enter the desired repeat option for this schedule e g To make a schedule that happens everyday you would...

Page 60: ...Installation Instructions 5 20 ...

Page 61: ...E on alpha keypads or FC on fixed word keypads Report Code Formats The following chart indicates the types of handshake kissoff frequencies that the panel supports and the different formats that can be sent with each FORMAT HANDSHAKE TRANSMITS DATA KISSOFF TRANSMIT TIME Low Speed 1400 Hz 1900Hz 10PPS 1400 Hz Under 15 secs 3 1 4 1 4 2 Standard report Sescoa Rad 2300 Hz 1800Hz 20PPS 2300 Hz Under 10...

Page 62: ...SS RTt RTRTRT RT t Bypass Res SSS S RB SSS S RB SSSS SS RBb RBRBRB RB b Characters in parenthesis are included in Robofon 8 format Where SSS or SSSS Subscriber ID C Close Code 1st Digit A Alarm Code 1st digit U User Number in hex Z Typically Zone Number 2nd digit Gg Test Code 1st 2nd digits Tt Trouble Code 1st 2nd digits R Restore Code Alarm Bb Bypass Code 1st 2nd digits RTt Restore Code Trbl 1st ...

Page 63: ...as in 4 2 format Signal flow Receiving equipment Dialing equipment Send start char w 77h Send message described above Acknowledge ACK 06h Delay greater than 500ms Send new start char w 77h Send next message if available Acknowledge ACK 06h etc Dialer should start sending the message no more than 200ms after start char If no response is detected the receiver retries sending start char three times i...

Page 64: ... 354 Failure to Communicate log only 373 Fire Loop Trouble 374 Exit Error Alarm 380 Trouble Zone Type 5 381 RF Sensor Supervision 382 Supervision Auxiliary Wired Zone sent after code 333 is sent 383 RF Sensor Tamper and Double Balanced Zone Tamper Code Definition 384 RF Sensor Low battery 393 Clean Me ESL smoke detectors only 401 Disarmed Armed AWAY Armed MAXIMUM 403 Scheduled Arm Disarm AWAY 406 ...

Page 65: ... only if it was used to arm the system 3 Duress see user performs security functions but also silently sends a duress message to the central station reports as duress code user number 4 Partition see user See Partition Master paragraph above used to assign Master other user numbers as partition masters Refer to the user guide for detailed procedures on adding deleting security codes and changing u...

Page 66: ...le Button Arming above Arming Instant Enter code INSTANT 7 Arming Maximum Enter code MAXIMUM 4 or simply press appropriate lettered key on the keypads see Single Button Arming above Disarming Enter code OFF 1 If entry delay or an alarm is active you do not need to press OFF entering the security code alone disarms the system Bypassing Zones Enter code BYPASS 6 zone number s Can bypass while system...

Page 67: ...r Zone If the follow me number is for a pager the message displayed on the pager is as follows 104 P ZZZ where P is the partition number ZZZ is the 3 digit zone number of the zone in alarm To enter a Follow Me phone number user code 6 1 The first follow me phone number if it exists is displayed FM Phone No 18009216704 _ To display follow me phone number 2 press 2 To display follow me phone number ...

Page 68: ...s sensor displayed zone 00 indicates a wireless keypad If the battery is not replaced within 30 days a CHECK display may occur Note Some wireless sensors contain a non replaceable long life battery which requires replacement of the entire unit at the end of battery life e g 5802 and 5802CP TELECOM FAULT 94 Telephone Line Failure indicates that a monitored telephone line if programmed in field 92 h...

Page 69: ...e transmitted with a TEST report The keypad will beep once per minute as a reminder that the system is in the Test mode NOTE Wireless motion detectors Passive Infrared units will send signals out only if they have been inactive for 3 minutes from their prior transmission conserves battery life 3 Test all sensors using the procedure described in the User s Guide Testing the System section 4 After c...

Page 70: ... transmitter to another location Usually a few centimeters in either direction is all that is required 4 If each transmitter produces the proper keypad response when it is faulted you can then permanently mount each of the transmitters according to the instructions provided with them 5 Exit the Go No Go Test mode by entering Installer code OFF Dialer Communication Test 1 Enter Installer Code 5 TES...

Page 71: ...unication section Ademco Contact ID 10 characters sec DTMF multi frequency Data Tones 1400 2300Hz ACK 1400Hz KISSOFF Robofon Contact ID same as ADEMCO except 2300Hz ACK LINE SEIZE Double Pole DOC Load No 3 4 Maximum Zone Resistance Zones 1 8 300 ohms excluding EOLR in standard EOLR zones COMPATIBLE DEVICES Keypads 6128RF 6148 6150 6150RF 6150V 6160V 6164 Wireless Receivers 5881ENL accepts up to 8 ...

Page 72: ...Motorized Bell Box Ademco 1011BE12M 25cm Motorized Bell Box Ademco 702 Outdoor Siren Ademco 719 2 Channel Siren Ademco 747 Indoor Siren Ademco 744 Siren Driver Ademco 745X3 Voice Siren Driver Ademco 705 820 12 5cm Round Speaker Ademco 713 Speaker System Sensor PA400B beige PA400R red Indoor Piezo Sounder Installation Instructions 8 2 ...

Page 73: ...tails regarding loop numbers etc Compatible 5800 Series Transmitters Table Model Product Input Type Description 5801 Wireless Panic Transmitter UR or RF Four pushbuttons each with a unique input loop code Programmable responses e g Panic Arm Disarm etc 5802 Pendant Personal Emergency Transmitter BR Only Has single pushbutton Usually programmed for response type of 24 Hr audible or 24 Hr Silent oth...

Page 74: ...que input loop codes Loop 1 Built in shock sensor loop wired to TB1 normally closed Loop 2 For a closed circuit contact loop using the built in reed switch in conjunction with a magnet Loop 3 Externally wired closed circuit loop connected to TB2 5827 Wireless Keypad Uses House ID only Can be used to turn the burglary protection on and off Features the same built in panic functions as wired keypads...

Page 75: ... NOTES 8 5 ...

Page 76: ... NOTES Installation Instructions 8 6 ...

Page 77: ...or intrusion that takes place behind walls ceilings floors closed doors glass partitions glass doors or windows Mechanical tampering masking painting or spraying of any material on the mirrors windows or any part of the optical system can reduce their detection ability Passive Infrared Detectors sense changes in temperature however as the ambient temperature of the protected area approaches the te...

Page 78: ...9 4 IBM Personal Computer 3 1 Ideal Model 61 035 2 5 Input Device Type 5 4 9 3 9 4 Installer Code 3 6 4 1 8 1 8 2 Interior Follower 3 3 5 2 5 11 Interior w Delay 3 4 5 2 5 11 keypad addresses 2 3 3 2 Keypad Programming Fields 4 11 Keyswitch 2 9 3 5 5 2 3 Kissoff 5 11 6 1 Lock 2 1 Long Range Radio 1 2 2 12 4 2 4 4 3 9 1 Low Battery Message 8 2 macros 1 1 Master Security Code 4 1 model 112 2 9 Modem...

Page 79: ...MS EOLR 2000 OHMS EOLR 2000 OHMS EOLR SYNC BLK COM VIO DATA BLU TO X 10 TRANS 18 19 16 15 14 13 10 9 6 5 4 1 2 3 4 5 6 SET RECEIVER S DIP SWITCH FOR DEVICE ADDRESS OF 0 SEE INSTRUCTIONS SET UNIT S DIP SWITCH FOR DEVICE ADDRESSES 7 15 SEE INSTRUCTIONS ZONE PAIRS 1 9 2 10 3 11 4 12 5 13 6 14 7 15 8 16 TYPICAL WIRING FOR ZONE DOUBLING TYPICAL WIRING FOR DOUBLE BALANCED ZONE REMOTE KEYPADS CAN USE 612...

Page 80: ...HEREOF IN NO CASE SHALL SELLER BE LIABLE TO ANYONE FOR ANY CONSEQUENTIAL OR INCIDENTAL DAMAGES FOR BREACH OF THIS OR ANY OTHER WARRANTY EXPRESS OR IMPLIED OR UPON ANY OTHER BASIS OF LIABILITY WHATSOEVER EVEN IF THE LOSS OR DAMAGE IS CAUSED BY THE SELLER S OWN NEGLIGENCE OR FAULT Seller does not represent that the product s it sells may not be compromised or circumvented that the product s will pre...

Reviews: