4-3
*35
Entry Delay 1
00 - 96 = 0 - 96 seconds
97 = 120 seconds
98 = 180 seconds
99 = 240 seconds
EN50131-1 Compliance: Entry delay must be
at least 30 seconds, but may not exceed 45
seconds.
Upon entering, the system must be disarmed before the time entered
expires, otherwise it sounds an alarm. Common area zones use same
delay as partition 1. When an entry delay zone is activated, the entry
delay time applies to ALL burglary zones in the partition.
UL installations:
For UL Residential Burglary Alarm installations,
must be set for a maximum of 30 seconds; entry delay plus dial delay
should not exceed 1 min. For UL Commercial Burglar Alarm, total
entry delay may not exceed 45 seconds.
*36
Entry Delay 2
See *35 for explanation.
*37
Audible Exit Warning
0 = no; 1 = yes
Warning sound consists of slow continuous beeps until last 10 seconds,
then it changes to fast beeps. Sound ends when exit time expires.
*38
Confirmation Of Arming Ding
Entry 1:
0 = no; 1 = yes, 1-second ding
(ding if armed from wired keypad)
Entry 2:
Enter 0-15 from table below.
(ding if armed from RF device)
Entry
Ding at Siren Trigger 2 Output
0 none
none
1 none
250mS
2
none
1 second
3
none
4 seconds
4
250mS
none
5
250mS
250mS
6
250mS
1 second
7
250mS
4 seconds
8
1
second none
9
1
second 250mS
#+10
1 second
1 second
#+11
1 second
4 seconds
#+12
4 seconds
none
#+13
4 seconds
250mS
#+14
4 seconds
1 second
#+15
4 seconds
4 seconds
Entry 1
for each partition selects whether arming from wired
keypads causes siren ding. Confirmation of arming is 1/2 second
external sounder “ding.” Ding occurs when closing reports is sent, or
when exit delay expires.
Entry 2
for each partition selects whether arming from remote RF
devices causes siren ding and/or activates trigger 2 output; also selects
siren ding/trigger activation duration (arm = 2 dings of selected
duration with 1 second off between; disarm = 1 ding of selected
duration). Ding occurs upon reception of the wireless arming command.
NOTE:
If using an option that activates trigger 2, trigger 2 must be
dedicated to only this function; do not assign any other functions to
trigger 2.
UL installations: Entry 1 must be “1” for UL Commercial Burglar
Alarm installations.
*39
Power-Up In Previous State
0 = always power-up in a disarmed state
1 = assume the system status prior to
power down
When the system powers up armed, an alarm will occur 1 minute
after arming if a zone is faulted at that time.
Note that if the previous state was armed AWAY or STAY, the
system will not respond to sensor changes for 1 minute, which allows
time for sensors such as PIRs to stabilize.
UL installations: must be 1 (power-up in previous state)
Dialer Programming (
∗∗∗∗
40 –
∗∗∗∗
50)
FIELD
TITLE and DATA ENTRIES
EXPLANATION
*40
PABX Access Code
Enter up to 6 digits if PABX is needed to
access an outside line. Do not fill unused
spaces.
0–9, # + 11 for ‘
∗
’, # + 12 for ‘#’, # + 13 for a
pause (2 seconds)
To clear entries from field, press
∗
40
∗
. If fewer than 6 digits need to
be entered, exit by pressing [
∗
], which advances to the next field.
Call Waiting:
If the subscriber’s phone service has “call waiting”
(and is not using PABX), enter “*70” (“# + 11”) plus “# + 13” (pause)
as the PABX entry to disable “call waiting” during control panel calls.
If the subscriber does not have “call waiting” and is not using PABX,
make no entry in this field.
*41
Primary Phone No.
Enter up to 30 digits. Don’t fill unused spaces.
0–9, # + 11 for ‘
∗
’, # + 12 for ‘#’, # + 13 for a
pause (2 seconds)
If you enter fewer than 30 digits, exit by pressing [
∗
]. To clear entries
from field, press
∗
41
∗
.
NOTE:
Backup reporting (in which 8 calls are made to the secondary
phone number if no kissoff is received after 8 attempts to the primary
number) is automatic only if there is a secondary phone number (
∗
42).
*42
Secondary Phone No.
Enter up to 30 digits. 0–9, # + 11 for ‘
✱
’, # +
12 for ‘#’, # + 13 for a pause (2 seconds)
If you enter fewer than 30 digits, exit by pressing [
∗
]. To clear entries
from field, press
∗
42
∗
. See backup reporting note for field
∗
41.
Don’t fill unused spaces.
*43
Part. 1 Primary Subs. Acct. No.
Enter digits 0–9; # + 11 for B, # + 12 for C, #
+ 13 for D, # + 14 for E, # + 15 for F.
Enter up to 10 digits, depending on the report format selected in field
*48. To clear entries from field, press
∗
43
∗
.