7845GSM/7845GSMCN Installation and Setup Guide
3-6
PROMPTS ENTRY
OPTIONS
DESCRIPTION
Sends a low-battery report when a low battery
condition exists.
25
Low Bat Rpt Y/N
(Y)_
[Y], [N]
UL NOTE:
Must be set to "Y"
unless used with
LynxR-I series controls. Must be set to "N" when using
LynxR-I series controls.
Sends a tamper report when the module detects a
tamper condition. A tamper restore is automatically
sent when the tamper condition clears.
26
Tamper Rpt Y/N
(Y)_
[Y], [N]
UL NOTE:
Must be set to "Y."
Important Information Regarding Zone Input Options
ECP mode
supports two optional hardwire zone input triggers by making connections to the module’s zone 6 and/or
zone 7 terminals and programming the appropriate zone trigger options below.
Each zone input can be programmed to cause an alarm under one of the following conditions:
•
(V+), where a positive voltage causes an alarm for normally low connections (voltage trigger, NO, NC)
•
(V–), where a ground trigger causes an alarm for normally high connections (open collector, NO, NC)
•
(EOLR) End of Line Resistor, where the input is supervised by a 2K EOL resistor. The zone can be triggered
by open collector, voltage trigger, NO, NC.
In addition to the above, zones can be programmed for an Inverted Trigger, where the alarm and normal states of
the zones are inverted; this can serve a fail-safe supervisory purpose for certain installations.
These zone inputs can also be programmed for restore reporting, and for delayed reporting, which allows time for
the user to abort false alarms.
NOTE:
Optional hardwire zones report in ADEMCO High-Speed format.
27
Enable Zn6 Y/N
(N)_
[Y], [N]
Enables alarm reporting for zone 6.
If [N], skip to Prompt 32: "Enable Zn7."
28
Zn6 Trigger Type
(V+)_
•
(V+)
•
(V–)
•
(EOLR)
Selects the triggering method for this zone input.
Press the [space] key to scroll through choices.
29
Invert Zn6 Y/N
(N)_
[Y], [N]
Inverts the alarm and normal states of the zone 6
trigger; otherwise uses normal input signal.
30
Restore Zn6 Y/N
(Y)_
[Y], [N]
Enables restore reporting for zone 6.
31
Delay Zn6 (secs)
(00)_
[01-15]
[00] = no delay
Defines the reporting delay in seconds for zone 6.
32
Enable Zn7 Y/N
(N)_
[Y], [N]
Enables alarm reporting for zone 7.
If [N], skip to Prompt 37: "Review."
33
Zn7 Trigger Type
(V+)_
•
(V+)
•
(V–)
•
(EOLR)
Selects the triggering method for this zone input.
Press the [space] key to scroll through choices.
34
Invert Zn7 Y/N
(N)_
[Y], [N]
Inverts the alarm and normal states of the zone 7
trigger; otherwise uses normal input signal.
35
Restore Zn7 Y/N
(Y)_
[Y], [N]
Enables restore reporting for zone 7.
36
Delay Zn7 (secs)
(00)_
[01-15]
[00] = no delay
Defines the reporting delay in seconds for zone 7.