Section 3: Programming the 7845GSM
3-11
PROMPTS
ZONE
TRIG.
4204/
2-4204
ENTRY OPTIONS
DESCRIPTION
16
Supervision
(24 Hours)_
✔
✔
•
30 Day
•
24 Hrs
•
None
The AlarmNet network must hear at least one
supervisory message from the module during this
supervision period; otherwise, AlarmNet notifies
the central station that a communication failure
has occurred. (If the supervision period is changed
after registration, you must re-register the
module.)
Press the [space] key to scroll through choices.
UL NOTE:
Must be set to 24 hours.
Sets how long an undeliverable alarm is retried for
delivery to the central station. If the message is not
validated, it is retried until the old alarm time is
reached or the message is validated.
Press the [space] key to scroll through choices.
17
Old Alarm Time
(10 Minutes)_
✔
✔
•
10 Min
•
15 Min
•
30 Min
•
1 Hr
•
2 Hrs
•
4 Hrs
•
8 Hrs
•
12 Hrs
•
24 Hrs
UL NOTE:
Must be set to 10 minutes.
18
GSM Flt Time
(60 mins)_
✔
✔
[01-99]
[00] = not
used
In the event the module detects a communication
path failure, enter the time delay (in minutes)
before the module notifies the control panel with a
trouble message (and trips the Fault Output if
used (terminal 11); see next question). The control
panel can then notify the central station.
UL NOTE:
Must be two (02) minutes.
19
Flt Rel ON Y/N
(N)_
✔
✔
[Y], [N]
If enabled, the fault open collector output is
normally energized to ground, and de-energizes
(open circuit) in the event of a module fault. For
conditions that trip the fault relay refer to
Module
Supervision Features
in Section 1.
Set to [Y] if fail-safe mode is desired.
See
Wiring for
Module Fault Relay
in Section 2.
UL NOTE:
Must be set to "Y".
Sends a primary power loss report to the central
station within 1-3 hours after its detection. A
restore report is sent within 1-3 hours after power
is restored.
20
Pwr Loss Rpt Y/N
(Y)_
✔
✔
[Y], [N]
UL NOTE:
Must be set to "Y."
Sends a low-battery report when a low battery
condition exists. A low-battery restore is
automatically sent when the low battery condition
clears.
21
Low Bat Rpt Y/N
(Y)_
✔
✔
[Y], [N]
UL NOTE:
Must be set to "Y"
unless used with
LynxR-I series controls. Must be set to "N" when
using LynxR-I series controls.
Sends a tamper report when the module detects a
tamper condition. A tamper restore is
automatically sent when the tamper condition
clears.
22
Tamper Rpt Y/N
(Y)_
✔
✔
[Y], [N]
UL NOTE:
Must be set to "Y."