Section 3: Programming the 7845i-GSM
3-5
PROMPTS ENTRY
OPTIONS
DESCRIPTION
Sets how long an undeliverable alarm is retried for
delivery to the central station. If the message is not
validated, it is retried until the old alarm time is
reached or the message is validated.
Press the [space] key to scroll through choices.
23
Old Alarm Time
(10 Minutes)_
•
10 Minutes
•
15 Minutes
•
30 Minutes
•
1 Hour
•
2 Hours
•
4 Hours
•
8 Hours
•
12 Hours
•
24 Hours
UL NOTE:
Must be 10 minutes.
24
IP Flt Time
(60 mins)_
[01-99]
In the event there is a loss of contact with the network
over the Ethernet connection, enter the time delay (in
minutes) before the 7845i-GSM notifies the central
station. IP failure will always be sent to the central
station as Primary Communication Path Failure.
UL NOTE:
Must be two (02) minutes.
25
GSM Flt Time
(60 mins)_
[01-99]
In the event the module detects a communication path
failure, enter the time delay (in minutes) before the
7845i-GSM notifies the central station. A GSM failure
will always be sent to the central station as Secondary
Communication Path Failure.
UL NOTE:
Must be two (02) minutes.
26
Notify Panel Of_
(Neither Fault)
[Neither
fault]
[Both IP and
GSM Faults]
If "Both IP and GSM Fault" is selected, the device will
only notify the control panel if both communication
paths fail, but will always send notification of either
failure to the central station.
NOTE:
The fault relay output (if programmed) will be
triggered only if "Both IP and GSM Faults" is selected.
Press the [space] key to scroll through choices.
27
Flt Rel ON Y/N
(N)_
[Y], [N]
If enabled, the fault open collector output is normally
energized to ground, and de-energizes (open circuit) in
the event of a module radio fault.
Use if fail-safe mode is desired.
See
Wiring for
Module Radio Faults
in Section 2.
UL NOTE:
Must be set to "Y."
28
Pwr Loss Rpt Y/N
(Y)_
[Y], [N]
Sends a primary power loss report to the central
station within 1-3 hours after its detection. A restore
report is sent within 1-3 hours after power is restored.
29
Low Bat Rpt Y/N
(Y)_
[Y], [N]
Sends a low-battery report when a low battery
condition exists. A low battery restore is automatically
sent when the low battery condition clears.
NOTE:
Must be set to "N" for use with LynxR-I
controls.
30
Tamper Rpt Y/N
(Y)_
[Y], [N]
Sends a tamper report when the module detects a
tamper condition. A tamper restore is automatically
sent when the tamper condition clears.