Internet Communication Module 7845i-GSM Installation and Setup Guide
3-10
PROMPTS
ZONE
TRIG.
4204/
2-4204
ENTRY OPTIONS
DESCRIPTION
Re-enter the password as confirmation.
If the password doesn't match the first entry, the
following is displayed followed by the "Exit Prog.
Mode?" prompt:
7
✔
✔
[0-9, A-F, N,
S, T, X, Y]
Verify Not OK
PSWD not created
Verify Password
Otherwise, the "Exit Prog. Mode?" prompt is
displayed directly.
8
Exit Prog. Mode?
Y/N_
✔
✔
[Y], [N]
[ESC]
Exits program mode.
Press [N] to go back to Prompt 3.
Press [ESC] to load factory defaults.
Refer to the
Exiting Programming Mode
paragraph
in this section.
9
Device Mode
(ECP)_
✔
✔
•
ECP
•
Zone Trig.
•
4204 Emu
•
Two 4204s
Press the [space] key to scroll through the modes of
operation.
Press [ENTER] to select mode.
See
Table 3
for ECP mode programming.
Important Information Regarding Primary Account (Questions 10-12)
Account information is provided by the central station administrator.
10
Primary City ID
(??)_
✔
✔
[01-99]
Enter the 2-digit primary city ID, 01-99 (decimal).
11
Primary CS ID
(???)
✔
✔
[01-FE]
Enter the 2-digit primary central station ID
number, 01-FE (HEX).
12
Primary Sub ID
(????)
✔
✔
[0001-9999]
Enter the 4-digit subscriber account number, 0001-
9999 (decimal).
13
Device Address
(12)_
✔
[01-15]
The 7845i-GSM communicates with the control
panel as a 4204 relay module. Enter the
appropriate address. For VISTA-10P, and
FA130CP Series control panels, this must be
address 12. For other controls, see the control
panel’s Installation and Setup Guide.
NOTES:
1. The 4204 protocol limits address range to 01-15.
If using 2-4204 mode, the 7845i-GSM assigns
the second 4204 to the next higher device
address (e.g., if entering address 12 for the first
4204, then address 13 is automatically assigned
to the second 4204 module). Program the
control panel accordingly.
2. The device address(es) must be unique from the
"Direct Wire Addr" entered in Prompt 15 and
any other address used on the control panel.
14
Enable DW Y/N
(N)_
✔
[Y], [N]
Applies only to VISTA-128BP/250BP and FBP
Series controls, and FA1660C and 1700C Series
controls.
Enables Direct Wire Downloading over IP.
If [N], skip to Prompt 16: "Supervision."